Installation bracket TBLZ-1-53 for circular ducts or 
insulated flat ducts.

The duct diameter can be as small as 100 mm 
using the bracket.

• Check that the direction of the arrows is towards the direction of flow.
• Check that the plug for the test hole is properly installed.
• Check that the flow indicator shows flow (rocks).
• Full scale tests with smoke generator are recommended to check the function.

Troubleshooting.

The smoke detector deploys without any smoke 
present.

• The smoke detector is faulty, dirty or positioned so that 
condensation can build up, see point 8. The detector 
insert must be replaced.

Only the control unit triggers an alarm.

• Check that the termination resistor is installed in the last 
smoke detector.
• Check that the coil’s resistance is 2.2k

 from the control 

unit.
• Check that the control unit is OK by installing the 2.2k

Ω  

resistor in the smoke detector output on the control unit.
• Use a voltmeter to check that 21-24 VDC with the cor-
rect polarity is in terminal 1 (-) and terminal 2 (+).

10

8

9

The installation bracket is supplied flat.

The installation bracket is easy to 
bend/shape so that it fits circular or 
flat ducts.

Secure the bracket’s 
legs to the duct.

Hole ø 51 
mm. 

Rubber 
seal

Circular duct.

Insulated flat duct.

Rubber 
seal

Final checks

Installing different tubes in different duct widths.

Venturi tube 600 mm.

Venturi tube 1200 mm.

Hole 
ø 38 mm

Hole 
ø 38 mm

Cut the venturi 
tube to the correct 
length

The Venturi tube 
must go through 
the entire duct.

Important! 
Hole ø 51 mm

Max. tube of 30 mm outside the duct.

For ducts less than 600 mm use ven-
turi tube of 600 mm, standard.
For ducts between 600 mm and 1400 
mm, use venturi tube of 1500 mm.

• 

Cut the tube to the 

correct length. 

• 

Insert the end plug.

• 

Install the seal

• 

Install rubber seal TET 

26-35 as a bearing.

Содержание TBLZ-1-49-a GOLD

Страница 1: ...cket when installing on circular or insulated ducts 2 Function When combustion gas is detected the LED on the detector lights red and the alarm signal is forwarded to the control unit If the smoke detector becomes dirty it becomes more sen sitive and switches to alarm mode more slowly To prevent false alarms if dirty the detector is equipped with a service alarm green LED This indicates that the d...

Страница 2: ...he duct see example of inter fering sources below in the direction of airflow is the same as 3 x the duct s hydraulic diameter Nearest location after an interfering source must be at least 5 x the duct s hydraulic diameter MIN 3xdh MIN 5xdh GX GX MIN 3xdh MIN 5xdh GX GX MIN 3xdh MIN 5xdh GX GX MIN 3xdh MIN 5xdh GX GX MIN 3xdh MIN 5xdh MIN 5xdh GX MIN 3xd h GX MIN 5xdh GX MIN 3xd h GX GX MIN 3xdh G...

Страница 3: ...tector on the duct Secure the detector box at 3 points at the markings of the arrows Important IMPORTANT The direction arrows see the shape of the detector s base or the top of the housing must point in the same direction as the air flow in the duct End plug Stop screw Seal 5 Flow indicator The detector is equipped with an indicator a red plastic tab which when the detector is correctly installed ...

Страница 4: ...resistance is 2 2kΩ from the control unit Check that the control unit is OK by installing the 2 2kΩ resistor in the smoke detector output on the control unit Use a voltmeter to check that 21 24 VDC with the cor rect polarity is in terminal 1 and terminal 2 10 8 9 The installation bracket is supplied flat The installation bracket is easy to bend shape so that it fits circular or flat ducts Secure t...

Отзывы: