PARASOL
Zenith VAVc
10
Swegon reserves the right to alter specifications. 19/10/2020
Menu sensor module:
Press and hold the left and right-hand buttons for five seconds
to access the menu.
Use the left-hand button ( ) to steps through the menus. Use
the right-hand button ( ) to confirm your selection.
Press the left-hand
button and select:
1
. Alarm list
2
. Air commissioning
3
. Water commissioning
6
. Return to menu
Confirm selections
by pressing the
right-hand button
The alarm is shown with a number of LEDs when you select
Alarm list (1) in the menu.
Each LED represents a number as per the table above and the
numbers are added to form an alarm number.
E.g. Middle blue and the two last red are lit (xoxxoo)
Middle blue corresponds to 16, next last red 2 and last red 1.
The sum of these is 19, which is the alarm number.
Return to normal operation by pressing the right-hand button.
1. Alarm list:
See the complete alarm list to the right.
In the commissioning menus:
• Navigate between the menus by pressing the left-hand button
• Confirm selections by pressing the right-hand button
• When a selection has been confirmed, the blue LED will flash
for about 60 seconds.
• In order to return to normal operation, select "no adjustment"
2. Commissioning, air:
2.1. Min. airflow, no occupants
2.2. Min. airflow, occupancy
2.3. Max. air flow, occupancy
2.4. Min. airflow, holiday/longer period
of no occupancy
2.5. No adjustment
3. Commissioning, water:
3.1. Open the chilled water valve
3.2. Open heated water valve
3.3. No adjustment
4, 5 are not used
6. Return to menu
Alarm list for the sensor module
Alarm no. Type of alarm
32
16
8
4
2
1
Alarm 1
Supply voltage low
Alarm 2
Supply voltage critical low
Alarm 3
Ext temp missing
Alarm 4
Ext temp error
Alarm 5
Condensation sensor error
Alarm 6
SM temp sensor error
Alarm 7
SM button error
Alarm 8
CO
2
sensor missing
Alarm 9
VOC Error
Alarm 10 Low pressure
Alarm 17 SM comm error
Alarm 18 Slave comm error
Alarm 19 Pressure sensor comm error
Alarm 20 VOC sensor comm error
Alarm 21 No master request (slave)
Alarm 22 Slave incompatible version
Alarm 25 Heating comfort alarm
Alarm 26 Cooling comfort alarm
Alarm 27 Temp. Set point overlap alarm
Alarm 28 Air quality comfort alarm
Alarm 29 Condensation
Alarm 33 24 V Out 1 overload error
Alarm 34 24 V Out 2 overload error
Alarm 35 24 V Out 3 overload error
Alarm 41 Slave input sum alarm
Alarm 42 Slave output sum alarm
ON
1
2
Presence sensor
LEDs for temperature,
adjustment or alarm indication
Function keys
LED indicating function
- Green = Ok
- Flashing Green = condensation alarm
- Yellow = Alarm
- Green/Yellow = Comfort alarm (not acute)
Temperature sensor
3 parallel RJ12 ports
(Modbus) for connections
e.g. controller, additional
sensor module or PC with
the help of Cable converter
USB-RJ12
Addressing the sensor module. 10
sensor modules can be connected
to each master unit, each one must
have a unique address to work.
Switch for termination resistance.
On the last sensor module in the
circuit switch 1 is set to On.