SMART Link
Function
5. Settings
For basic facts on how to use the hand-held terminal, see
the Operation and Maintenance Instructions for the GOLD
air handling unit.
The chiller/heat pump functions must be manually acti-
vated under Functions/SMART Link.
The function can be activated, under Function.
Set the type supplied (water, heat pump/water, chiller/wa-
ter, reversible/DX, heat pump/DX, chiller/DX, reversible.
Set the required set point for cooling and/or heating water
as well as the permissible deviation under Settings. The set
points represent the reference temperature of the refrig-
erant and heating medium returning to the chiller/heat
pump. Set the limit for the outdoor temperature (mini-
mum permitted operating temperature).
The function for the optimization of the set point heating
and cooling can be activated under Optimize.
Other chiller/heat pump settings can be entered in the
chiller/heat pump.
If required, AQUA Link can be activated under AQUA Link.
Select alarm on open contact, alarm on closed contact or
contactor function for the pump alarm.
SMART Link
Settings
Optimize
AQUA Link
6. Status
The chiller/heat pump readings can be viewed under
Status.
No values can be changed in this menu group.
7.
Manual test
The actual input and output values on the circulation
pump in the cooling circuit can be manually controlled
under INSTALLATION – MANUAL TEST - SMART Link.
Status
SMART Link
Manual test