GB.TBLZ41.160408

Registered design. The company reserves the right to make design changes without prior notice.

4    www.swegon.com

3.2 GOLD, Version C/D

Place the communication unit on the DIN rail inside the 
electrical equipment cubicle of the air handling unit or 
inside an optional enclosure.

Connect the 24 V AC supply voltage to terminals Vin+ 
(24) and GND (23). Supply voltage can be obtained from 
the control unit of the air handling unit, see below and B 
in Fig. 5.

GOLDen GATE    

GOLD

Terminal 24 (Vin+) 

Terminal 58 or 60 (G) 

 

Terminal 23 (GND) 

Terminal 59 or 61 (G0)

Connect the network from the GOLDen GATE communi-
cation unit to the control unit of the GOLD (A in Fig. 5). 
Use a 3-wire cable. 

GOLDen GATE    

GOLD

Terminal 1 (A)   

Terminal 27 (A)

Terminal 2 (B) 

 

Terminal 28 (B)

Terminal 3 (Not used)
Terminal 4 (GND) 

Terminal 29 (GND)

The DIL switch must be in the ON position (see Fig. 1, Item 
5).

Connect the Lonworks-network to the communication 
unit, NET A (terminal 18 or 20), NET B (terminal 17 or 19) 
and shield, if required, to SHLD (terminal 21).

Start communication between the communication unit 
and the air handling unit by entering the settings de-
scribed below. The search path in the hand-held micro ter-
minal is the following: SETTINGS/INSTALLATION/COMMU-
NICATION/EIA485 and PROTOCOL/SETTINGS. See also the 
Operating and Maintenance Instructions for the GOLD.

Select the setting: LONWORKS/TREND under EIA-485/
PROTOCOL.

Check to make sure that the following values are set un-
der: EIA-485/SETTINGS. 

Address = 1.
Speed = 38400
Parity = none.
Stop bits = 1.

Fig. 5

A

B

Содержание GOLDen GATE Lonworks FTT-10

Страница 1: ...areful when you connect leads to the unit Never con nect leads to the unit while the supply voltage is switched on Doing so may result in injury to you and damage the unit Observe local electrical saf...

Страница 2: ...ial port Use the serial cable supplied with double 9 pin D subconnectors Start the configura tion program and select Golden Gate LonWorks See Fig 2 Select the appropriate serial port and version GOLD...

Страница 3: ...Terminal 1 A Terminal 2 B Terminal 2 B Terminal 3 Not used Terminal 4 GND Terminal 3 GND The DIL switch must be in the ON position see Fig 1 Item 5 Connect the Lonworks network to the communication un...

Страница 4: ...Use a 3 wire cable GOLDen GATE GOLD Terminal 1 A Terminal 27 A Terminal 2 B Terminal 28 B Terminal 3 Not used Terminal 4 GND Terminal 29 GND The DIL switch must be in the ON position see Fig 1 Item 5...

Страница 5: ...control unit of the COMPACT unit A in Fig 6 Use a 3 wire cable GOLDen GATE COMPACT Terminal 1 A Terminal 11 A Terminal 2 B Terminal 12 B Terminal 3 Not used Terminal 4 GND Terminal 13 GND The DIL swit...

Страница 6: ...e below GOLDen GATE GOLD Terminal 24 Vin Terminal 104 G Terminal 23 GND Terminal 103 G0 Connect the network from the GOLDen GATE commu nication unit Item 2 in Fig 1 to the control unit in the GOLD tap...

Страница 7: ...G Terminal 23 GND Terminal 7 G0 Connect the network from the GOLDen GATE communi cation unit to the control unit of the GOLD unit Use the communication cable supplied The communication cable has a 4...

Страница 8: ...GB TBLZ41 160408 Registered design The company reserves the right to make design changes without prior notice 8 www swegon com...

Отзывы: