INSTALLATION 

GOLDen GATE Lonworks FTT-10,  

TBLZ-3-1-1-41 and TBLZ-1-2-1-41

1. General

The GOLDen GATE Lonworks communiction unit is avail-
able in a number of kits for connecting up to GOLD and 
COMPACT units of various generations.

In addition to the communication unit itself (part no. 
019400), each kit also includes connection cables. 

TBLZ-3-1-1-41 Communications kit

Intended for use together with the Version B/C/D/E/F 
GOLD air handling units and COMPACT air handling units.

TBLZ-1-2-1-41 Communications kit

Intended for use together with the Version 4/A GOLD air 
handling units.

Safety precautions

Be careful when you connect leads to the unit. Never con-
nect
leads to the unit while the supply voltage is switched on.  
Doing so may
result in injury to you and damage the unit. Observe local 
electrical safety regulations when carrying out the electri-
cal installation work.

Communication unit 

The unit consists of the following components:
1.   4-module standard enclosure for DIN-rail mounting to 

IP20.

2.   9-pin D-subconnector for connection via serial cable 

to

 

computer for configuration or to a Version 4/A/B 
GOLD unit.

3.   Terminal for a 10-30 V AC/DC, 25 mA power supply 

for 24 V

4.   Terminal block for EIA 485 network
 

(Used by Version C/D GOLD units)

5.   DIL switch for the termination of the EIA 485 network
6.   Terminal block for the LonWorks network.
7.   ”Service-Request” PIN. 
8.  Service LED.  

 

9.  Module Status LED.
10.  Serial Status LED.

Fig. 1

2

4

5

1

7

17 18 19 20 21 22 23 24

Net B

Net A

Net B

Net A

SHL D

NC

GND

V

in+

6

3

1 (A)

2 (B)

3 (NC)

4 (GND)

10

9

8

Содержание GOLDen GATE Lonworks FTT-10

Страница 1: ...areful when you connect leads to the unit Never con nect leads to the unit while the supply voltage is switched on Doing so may result in injury to you and damage the unit Observe local electrical saf...

Страница 2: ...ial port Use the serial cable supplied with double 9 pin D subconnectors Start the configura tion program and select Golden Gate LonWorks See Fig 2 Select the appropriate serial port and version GOLD...

Страница 3: ...Terminal 1 A Terminal 2 B Terminal 2 B Terminal 3 Not used Terminal 4 GND Terminal 3 GND The DIL switch must be in the ON position see Fig 1 Item 5 Connect the Lonworks network to the communication un...

Страница 4: ...Use a 3 wire cable GOLDen GATE GOLD Terminal 1 A Terminal 27 A Terminal 2 B Terminal 28 B Terminal 3 Not used Terminal 4 GND Terminal 29 GND The DIL switch must be in the ON position see Fig 1 Item 5...

Страница 5: ...control unit of the COMPACT unit A in Fig 6 Use a 3 wire cable GOLDen GATE COMPACT Terminal 1 A Terminal 11 A Terminal 2 B Terminal 12 B Terminal 3 Not used Terminal 4 GND Terminal 13 GND The DIL swit...

Страница 6: ...e below GOLDen GATE GOLD Terminal 24 Vin Terminal 104 G Terminal 23 GND Terminal 103 G0 Connect the network from the GOLDen GATE commu nication unit Item 2 in Fig 1 to the control unit in the GOLD tap...

Страница 7: ...G Terminal 23 GND Terminal 7 G0 Connect the network from the GOLDen GATE communi cation unit to the control unit of the GOLD unit Use the communication cable supplied The communication cable has a 4...

Страница 8: ...GB TBLZ41 160408 Registered design The company reserves the right to make design changes without prior notice 8 www swegon com...

Отзывы: