3. Function

The preheating function

 is a completely independent 

control with its own duct temperature sensor. The tem-
perature sensor should be installed in a duct, at least 1.5 
metres downstream of the air heater TBLE (viewed in 
the direction of airflow, see figure below). The other air 
heaters, TBLF and TCLF, can be fitted directly to the air 
handling unit and the temperature sensor can then be 
mounted inside the air handling unit after the filter.

The duct temperature sensor is required to prevent alarms 
from tripping.

The control signal regulates the air heater to keep tem-
perature by sensor at the preset value.

The preheating control function begins when the supply 
air fan is running and an airflow reading appears in the 
terminal screen.

Air heater for hot water:

During the start-up phase, the preheating and postheating 
air heaters simultaneously heat each airflow.   

Electric air heater:  

The air heater for preheating is cooled down according to 
the same settings as those for the air heater for postheat-
ing.

The preheating function

 does not include any capacity 

reduction feature for unit operation in the low airflow 
mode.

An overheating protection with normally-closed contacts 
monitors the state of the air heater. If the contacts open, 
an alarm is initiated.

Air heater for hot water with anti-frost monitor:  

The heat-retaining function is automatically activated. 

The limits for heat retaining and alarms are identical to the 
limits of the air heater for postheating.

The anti-frost monitor sensor is required to prevent alarms 
from tripping.

Air heater for hot water without anti-frost monitor:  

No heat-retaining function and no alarm for a faulty anti-
frost sensor. 

When heating is required and the outdoor temperature is 
low, the relay for controlling the circulation pump oper-
ates in the same way as the GOLD control system’s regular 
heating relay. 

Exercising can be selected and operated in parallel with 
the air heater for postheating.

1,5 m

Duct temperature sensor

The sketch shows air heater TBLE. When 
having air heaters TBLF and TCLF, the air 
heater can be fitted directly to the air hand-
ling unit and the temperature sensor can 
then be mounted inside the air handling unit 
after the filter.

Содержание Gold TBLE Series

Страница 1: ...an also be installed in an exhaust air or extract air duct Preheating is interlocked to follow the supply air flow This means that the function cannot be used in the exhaust air or extract air duct while the supply air fan is switched off and the extract air fan alone is operating The preheating function has a relay function for control ling a circulation pump if required 2 Material Specification ...

Страница 2: ...e settings as those for the air heater for postheat ing The preheating function does not include any capacity reduction feature for unit operation in the low airflow mode An overheating protection with normally closed contacts monitors the state of the air heater If the contacts open an alarm is initiated Air heater for hot water with anti frost monitor The heat retaining function is automatically...

Страница 3: ...rol unit of the air handling unit Digital temperature sensors require correct polarity they are con nected Communication cable to the control unit of the air handling unit where it should be connected to one of the connections for the Internal EIA 485 The function selector switch must be set to the 9 position Air heater for hot water T1 GR R1 RD Jack for wall moun ting 019611 Brown White S S 1 6 3...

Страница 4: ... 24 21 20 22 23 L1 L2 456 7 8 9 A B C D E F 0 1 2 3 Temp sensor for preheated air 0 10 V Electric air heater Swe gon Standard with control cable 8 pole G0 Overheating protection S Communication cable to the control unit of the air handling unit where it should be con nected to one of the connec tions for Internal EIA 485 Function selector switch in Position 9 S R1 RD Jack for wall mounting 8 pole ...

Страница 5: ...se Control 1 6 3 2 4 5 7 12 9 8 10 11 13 18 15 14 1617 19 24 21 20 22 23 L1 L2 456 7 8 9 A B C D E F 0 1 2 3 Temp sensor for preheated air 0 10 V Electric air heater G0 S Communication cable to the control unit of the air handling unit where it should be connec ted to one of the connections for Internal EIA 485 Function selector switch in Position 9 S R1 RD T1 GR Jack for wall moun ting 019611 Ove...

Страница 6: ...EATER 0 10 V W COIL WITH FP W COIL WITHOUT FP PREHEAT FUNCTION OFF ON SETTINGS PREHEAT TEMPERATURE 5 0 C 5 Adjustment For basic facts on how to use the hand held micro termi nal see the Operation and Maintenance Instructions for the GOLD unit The PREHEAT function must be manually activated under INSTALLATION FUNCTIONS IQNOMIC PLUS in the hand held terminal Select PREHEAT Under FUNCTION OFF ON sele...

Страница 7: ...m the GOLD unit s control unit A flashing light emitting diode L1 indicates correct com munication with the GOLD unit s control unit Temperature sensor Current temperatures can be read under INSTALLATION READINGS IQNOMIC PLUS PREHEAT If the tempera ture readings are reasonable wiring has been carried out correctly 1 6 3 2 4 5 7 12 9 8 10 11 13 18 15 14 1617 19 24 21 20 22 23 L1 L2 456 7 8 9 A B C ...

Страница 8: ...GB PREHEAT 130225 Specifications are subject to change without notice 8 www swegon com ...

Отзывы: