4. Electrical Connections

IQnomic Plus module 

1) 

Temp. sensor** 

for preheated air

24 V AC*

Valve actuator

G G0 Y 

Anti-frost 

monitor**

Control of circulation pump

* The 24 V AC power-

supply conductors can 

be connected to Termi-

nals 60 (G) and 61 (G0) 

in the control unit of 

the air handling unit.

** Digital temperature 

sensors require correct 

polarity they are con-

nected.

Communication cable to the control 
unit of the air handling unit, where 
it should be connected to one of the 
connections for the Internal EIA-485.

The function selector switch 

must be set to the 9 position.

Air heater for hot water

T1
GR

R1

RD

Jack for wall moun-

ting, 019611

Brown

White

– S – S

1

6

3

2

4 5

7

PE N L

Pump controls

Supply voltage to 1-phase pump, max 1.5 A, can be obtained by 

wiring to the following terminals inside the air handling unit:

GOLD:

 Terminal 101 (L), terminal 102 (N).

COMPACT Unit & Top:

 Terminal 201 (L), terminal 202 (N).

Содержание GOLD series

Страница 1: ...re designed for installation in an outdoor air duct however they can also be installed in an exhaust air or extract air duct Preheating is interlocked to follow the supply air flow This means that the function cannot be used in the exhaust air or extract air duct while the supply air fan is switched off and the extract air fan alone is operating The preheating function has a relay function for con...

Страница 2: ...ing to the same settings as those for the air heater for postheat ing The preheating function does not include any capacity reduction feature for unit operation in the low airflow mode An overheating protection with normally closed contacts monitors the state of the air heater If the contacts open an alarm is initiated Air heater for hot water with anti frost monitor The heat retaining function is...

Страница 3: ...rol unit of the air handling unit Digital temperature sensors require correct polarity they are con nected Communication cable to the control unit of the air handling unit where it should be connected to one of the connections for the Internal EIA 485 The function selector switch must be set to the 9 position Air heater for hot water T1 GR R1 RD Jack for wall moun ting 019611 Brown White S S 1 6 3...

Страница 4: ... 24 21 20 22 23 L1 L2 456 7 8 9 A B C D E F 0 1 2 3 Temp sensor for preheated air 0 10 V Electric air heater Swe gon Standard with control cable 8 pole G0 Overheating protection S Communication cable to the control unit of the air handling unit where it should be con nected to one of the connec tions for Internal EIA 485 Function selector switch in Position 9 S R1 RD Jack for wall mounting 8 pole ...

Страница 5: ...se Control 1 6 3 2 4 5 7 12 9 8 10 11 13 18 15 14 1617 19 24 21 20 22 23 L1 L2 456 7 8 9 A B C D E F 0 1 2 3 Temp sensor for preheated air 0 10 V Electric air heater G0 S Communication cable to the control unit of the air handling unit where it should be connec ted to one of the connections for Internal EIA 485 Function selector switch in Position 9 S R1 RD T1 GR Jack for wall moun ting 019611 Ove...

Страница 6: ...EATER 0 10 V W COIL WITH FP W COIL WITHOUT FP PREHEAT FUNCTION OFF ON SETTINGS PREHEAT TEMPERATURE 5 0 C 5 Adjustment For basic facts on how to use the hand held micro termi nal see the Operation and Maintenance Instructions for the GOLD unit The PREHEAT function must be manually activated under INSTALLATION FUNCTIONS IQNOMIC PLUS in the hand held terminal Select PREHEAT Under FUNCTION OFF ON sele...

Страница 7: ...m the GOLD unit s control unit A flashing light emitting diode L1 indicates correct com munication with the GOLD unit s control unit Temperature sensor Current temperatures can be read under INSTALLATION READINGS IQNOMIC PLUS PREHEAT If the tempera ture readings are reasonable wiring has been carried out correctly 1 6 3 2 4 5 7 12 9 8 10 11 13 18 15 14 1617 19 24 21 20 22 23 L1 L2 456 7 8 9 A B C ...

Страница 8: ...GB PREHEAT 101010 Specifications are subject to change without notice 8 www swegon com ...

Отзывы: