Installation – Commissioning – Maintenance

20170705

Accessories

Mounting frame, EXCT 2

Mounting frame with rubber seal-fitted spigot connection.

Mounting frame EXCT 3

Mounting frame with insertion joint dimensions for con-
nection to spigots. The mounting frame has a larger inner 
diameter than the connecting duct component fitted with 
a spigot, e.g. a duct bend.

Installation

Size of opening, see the dimension of the connecting 
duct. The mounting frame should be inserted into the 
connecting duct and fixed in position with blind rivets 
from the inside. Be careful when positioning the blind 
rivets so that they will not impede attaching the air dif-
fuser in the mounting frame. Rotate the diffuser into the 
bayonet mount of the mounting frame. See Figure 1.

Commissioning

Rotate the inner cone clockwise (-) to increase the pres-
sure drop and counterclockwise (+) to decrease it. Lock 
the position of the cone by tightening the lock nut on 
the rear side of the diffuser.
The air diffuser can be commissioned by measuring the 
pressure or the airflow. For pressure measurement, use a so-
called "measuring hook" and for airflow measurement use a 
commonly marketed airflow meter. See Figures 2 and 3.
The rated coefficient of performance (K-factor) is speci-
fied on the identification label of the product and in the 
relevant commissioning instructions at www.swegon.com.

Maintenance

The air diffuser can be cleaned, if necessary, using luke-
warm water with dishwashing detergent added or by 
vacuum cleaning using a brush nozzle. The duct system 
can be reached for cleaning after the air diffuser has been 
rotated out of its mounting frame. 

Figure 3. Commissioning.

q

 = flow reading l/s

p

 = current pressure reading (Pa)

k

 = commissioning factor

k-factor

p

k

p

q

=

k

p

q

=

(    )

2

EXC 125

Tomelilla

Sweden

            -10   -5    0    +5  +10

k = 1,3  1,9  2,6  3,2  3,9

k

q

Figure 1. Installation.

Figure 2. Commissioning.