background image

Installation

Suspend the air diffuser with hangers from the ceiling. An 
M8 pop nut, i.e. a threaded grommet that facilitates instal-
lation, is provided at the top and in the centre of the air dif-
fuser. On the size 315 and 400 air diffusers, there are three 
M8 pop nuts for more stable mounting. Figure 1.

Commissioning

Commissioning should be carried out with the diffuser face 
mounted. Pull the measuring tubes and the damper adjust-
ment cords out of the air diffuser through one disc in the 
diffuser face. Then connect the manometer to the correct 
measuring tube(s): two blue tubes for supply air and one 
transparent tube for extract air. The rated coefficient of per-
formance of the air register can be used in a calculation to 
determine the required commissioning pressure. Conclude 
commissioning by adjusting the damper to the correct blade 
position, tie a commissioning knot in the damper cords to 
indicate the damper position. See Figure 1.
The K-factor is specified on the product’s identification label 
and last in these instructions.

Maintenance

The air diffuser can be cleaned, if necessary, using lukewarm 
water with dishwashing detergent added or by vacuum 
cleaning using a brush nozzle.
The duct system can be reached for cleaning by removing 
the diffuser face plate. The perforated air distribution plate 
and damper in the commissioning box can be removed by 
turning the wing nuts, positioned on each side of the inlet, 
¾ of a turn. See Figure 1.

Figure 1. Installation. Commissioning. Maintenance.
1. Not included in the supply. 
2. Measuring unit

Length of straight duct

Type of obstruction 
upstream of

Length of straight duct upstream of the 

EAGLE Free

EAGLE Free

m

2

 = 5%

m

2

 = 10%

One 90° bend

3 ·Ød

2 ·Ød

Two 90°bends in 
the same plane

4 ·Ød

2 ·Ød

Two 90° bends 
in alignment at 
right angles to one 
another.

4 ·Ød

2 ·Ød

One 45° damper

6 ·Ød

3 ·Ød

One T-piece

4 ·Ød

3 ·Ød

m

2

 = accuracy of the method according to NVG’s report 

T32:1982

k

p

q

=

k

p

q

=

(    )

2

EAGLE Free x 

Tomelilla

Sweden

XXX

k = XX

k

p

 

q

TILLUFT / SUPPLY AIR

TILLUFT / SUPPLY AIR

FRÅ

NLU

FT /

 EXTR

ACT AI

R

q

 = flow reading l/s

p

 = current pressure reading (Pa)

k

 = commissioning factor

k-factor

EAGLE 

Free e

Installation – Commissioning – Maintenance