Sizing
There are many factors that influence what size of cooling
unit is required.
The CoolDX units have been designed to enable them to
meet many different prerequisites.
For correct sizing we refer to our ProUnit unit selection
program.
10 GENERAL TECHNICAL DATA
Cooling system CoolDX
CoolDX
Capacity
Rated
Rated
Refrigerant Minimum
Power supply
Weight
Size
variant
cool. power power req. data R407c (kg) airflow
(kg)
(kW)
1)
(kW)
Circuit 1 Circuit 2
(m
3
/s)
08-1
1
10
3,69
1,2
1,6
0,46
3-phase, 400V, 16A
247
08-2
2
14
5,02
1,2
2,2
0,46
3-phase, 400V, 16A
257
12-1
1
14
4,95
1,3
2,7
0,68
3-phase, 400V, 16A
305
12-2
2
20
6,94
1,4
2,9
0,9
3-phase, 400V, 20A
332
20-1
1
14
4,95
1,3
2,7
0,68
3-phase, 400V, 16A
323
20-2
2
20
6,94
1,4
2,9
0,9
3-phase, 400V, 20A
351
20-3
3
26
9,88
2,3
3,3
0,9
3-phase, 400V, 25A
373
30-1
1
27
9,00
2,0
4,2
1,25
3-phase, 400V, 25A
440
30-2
2
32
10,66
2,2
4,7
1,5
3-phase, 400V, 32A
486
30-3
3
45
16,47
3,4
5,6
1,5
3-phase, 400V, 40A
527
40-1
1
39
12,24
2,6
5,3
1,8
3-phase, 400V, 40A
572
40-2
2
45
14,54
2,9
5,9
2,1
3-phase, 400V, 40A
605
40-3
3
58
21,42
5,1
8,1
2,1
3-phase, 400V, 63A
672
60-1
1
58
18,94
4,9
8,0
2,6
3-phase, 400V, 50A
720
60-2
2
69
20,20
4,9
8,0
3,2
3-phase, 400V, 63A
819
60-3
3
95
33,18
7,9
11,9
3,2
3-phase, 400V, 80A
944
1)
For an outdoor temperature of 28°C, 50% RH and an extract air temperature of 25°C.