background image

SDHWM.230817

Swegon reserves the right to make changes.

7

www.swegonhomesolutions.com

Smart Extension Temperature module

 Sensor

T6   T7

T8   T9

Smart unit

SET2    SET1

DI

max 50 VDC

NC  NC  NC

1         2         3         4         5         6         7         8         9         10     11     12

max 250 V / 6 A

Relay 1

4         3           2      1 

max 250 V / 6 A

Relay 2

NC

4         3           2      1 

AO3

AO2

AO1

NC

NC NC

SET

1

1

230 V

7

9

6

3

Important

If the SET module is used for 230 VAC 
control, the module must be installed, 
according to the electrical safety 
directives, in a separate enclosure.

Make sure that the strain relief is 
arranged for the connections according to 
the electrical safety directives.

!

!

1: CASA Smart ventilation unit* | 3: Outdoor air temperature sensor 
| 6: Solenoid valve* | 7: Circulation water pump* | 9: Power source 
24 VDC* | 
*) Not included in the delivery.

Содержание CASA

Страница 1: ...nstallation operation and maintenance instructions for design engineers installation engineers and service personnel SDHWM_c_EN m Swegon CASA Air heater cooler in combination with ground source heat pump ...

Страница 2: ...d the ducts are clean and that there are no loose objects in them before you commission the ventilation system Ensure that the heating medium pipe system is mounted and insulated and that the venting sleeves are mounted Do not commission the air heater cooler until all work that produces large quantities of sanding dust or other impurities has been completed Sizing the heating medium circuit Consi...

Страница 3: ... space at the sides of the unit in the plans 3 2 Pipe connections for the heating medium The pipes for the air heater cooler s heating medium is connected to the unit s pipe connections Cu 22 mm for the outgoing solution and the return solution Remember the need to vent the heating medium pipes in connection with the pipe installation The air heater cooler s coarse filter must always be installed ...

Страница 4: ...preheater External liquid coil 8 C Liquid heating out limit Liquid cooling out limit 15 C 2 C Commissioning of the air heater cooler Select operation of the unit by highlighting the menu item External after heater Limit value heating Select the required start temperature for external pre heating When the outdoor temperature transferred outside temperature measured before the air heater cooler drop...

Страница 5: ...unction The unit s doors can be lifted from their hinges after their fastening catches have been opened The radiator in the unit can e g be cleaned by gently brushing the surface or gentle rinsing with water only at low pressure Any dirt that has accumulated on the bottom of the condensate tray can be wiped off using a cloth and mild detergent The function of the water trap and drainage pipes for ...

Страница 6: ... Heat pump 6 Solenoid valve 7 Circulation water pump 8 Extract air 9 Power source 24 VDC 10 Operating switch for the circulation water pump ON OFF Not included in the delivery M M T 230V 24V 24VDC Smart Extension Temperature module Sensor T6 T7 T8 T9 Smart unit SET2 SET1 DI max 50 VDC NC NC NC 1 2 3 4 5 6 7 8 9 10 11 12 max 250 V 6 A Relay 1 4 3 2 1 max 250 V 6 A Relay 2 NC 4 3 2 1 AO3 AO2 AO1 NC ...

Страница 7: ... 2 1 AO3 AO2 AO1 NC NC NC SET 1 1 230 V 7 9 6 3 Important If the SET module is used for 230 VAC control the module must be installed according to the electrical safety directives in a separate enclosure Make sure that the strain relief is arranged for the connections according to the electrical safety directives 1 CASA Smart ventilation unit 3 Outdoor air temperature sensor 6 Solenoid valve 7 Circ...

Страница 8: ...e loss kPa 5 9 7 9 8 7 10 0 10 6 Pipe connection DN 25 25 25 25 25 Air heater cooler s performance data The unit s function for use as a preheater has been sized with 28 ethanol Air heater cooler s performance data Cooling Capacity kW 0 8 1 2 1 4 Air flow l s 40 100 150 INCOMING AIR Temperature C 25 25 25 Relative humidity 55 55 55 OUTGOING AIR Temperature C 13 17 18 Relative humidity 95 87 82 INC...