GB.CACZ08.050101
Specifications are subject to alteration without notice.
2 www.swegon.se
Adjusted
total flow
l/s
1
2
3
4
277
177/100 211/166 229/48 241/36
222
144/78 172/50 183/39 191/31
167
104/63 127/40 133/34 145/22
Distribution not throttled/throttled
diffusor, total flow, m
3
/h, model
4. Air distribution plate
In order to distribute the air flow to the different rooms
in an another way than half to each, air distribution plate
is used. The air flow is throttled, according to table to
the right, in the diffusor where air flow distribution plate
is mounted. If for example decreased air flow for the
room where unit is located is required, the air distribution
plate shall be mounted in the lower section of the unit. If
decreased air flow is required in the room where separate
lower section is located, the air distribution plate shall be
mounted in separate lower section.
5. Mounting of air distribution
plate in lower section of unit
The air distribution plate is fastened, with 8 screws, in
silencer baffle (through perforated holes) and bottom
(through pre-drilled holes), as shown in the sketch.
6. Mounting of air distribution plate
insepa
rate lower section.
1. Mount the inner baffle, see 3.2.4 in "Installation and
maintenance".
2. The air distribution plate is fastened, with 8 screws,
in silencer baffle (through perforated holes) and bottom
(through pre-drilled holes), as shown in the sketch.
3. Mount the rest of the baffles and front, see 3.2.4 in
"Installation and maintenance".
7. Mounting of bench top
The bench top is fixated on top of the separate lower sec-
tion. This is appropriately carried out by glueing or scre-
wing the top to the lower section.
Specification:
Air distribution plate
CACZ-1-10-a
Model
1, 2, 3, 4
Section from side, unit
Front,
unit
Section from side, unit and separate lower section
Air
distribution plate
Air
distribution plate