3.1 Analogue Value (RO): AV R
O b j e c t
Instance
Object Name
Min/Max
1
Setpoint – Preheat Temperature
-9,9-9,9 [°C]
Preheat T° setpoint
2
Setpoint – Comfort Temperature
0,1-99,9 [°C]
Current Comfort T° setpoint (KWout/NV/BA+/BA-) (0=OFF)
3
Current Postheat setpoint
0,1-99,9 [°C]
Current Postheat setpoint (KWout/NV/BA+/KWext) (0=OFF)
4
Current Postcool setpoint
0,1-99,9 [°C]
Current PostCooling setpoint (BA-) (0=OFF)
5
OUT INT HYDRAULIC POSTHEAT
0-10,0 [V]
Output for the power control of the hydraulic postheater inside the unit
6
OUT EXT HYDRAULIC POSTHEAT
0-10,0 [V]
Output for the power control of the hydraulic postheater external to the unit
7
OUT EXT HYDRAULIC POSTCOOL
0-10,0 [V]
Output for the power control of the hydraulic postcooler external to the unit