Swegon ADAPT Parasol EXb 1290 Скачать руководство пользователя страница 10

ADAPT 

Parasol EX

10

Swegon reserves the right to alter specifications.                   20191101

 

X-shape

Fan-shape

Commissioning/Checking the airflows

Constant pressure in the zone with the CONTROL Zone 
damper or similar damper. 

•   Check that all the WISE products are energized.
•   Make sure that all the ADAPT Parasol EX modules have 

their correct K-factors. 

•   Make sure that all the modules are set to the max. flow 

commissioning mode. (On delivery, the product is set to 
this mode, 3 blue LEDs + 3 red LEDs are lit). 

•   Connect up to the control unit on the ADAPT Parasol EX 

(see separate SWICCT instructions) and carry out a per-
formance check.

•   Test the operating modes, the min./max. flows, open/

close the actuators. If the ADAPT Parasol EX has been 
configured at the factory, check that the settings agree 
with the project design data. If the module is an ADAPT 
Parasol EX stock (stocked product), it must be program-
med according to the data for which the product has 
been calculated. Make also sure that the Modbus addres-
ses agree if SuperWISE or some other BMS system will be 
used.

•   If SuperWISE will be used, make sure that all products are 

in the SuperWISE tree structure. If all the products are 
not in the tree structure, look over the Modbus addresses 
via SWICCT and check cables and connections. (See the 
separate instructions for the SuperWISE).

•   Make sure that the pressure sensor and sensor module 

have the correct Modbus address. The Master must have 
a 0 setting on the pressure sensor and sensor module. Set 
the Slaves, if required, in number sequence: 1, 2, 3, 4, 5, 
6, 7, 8, 9

•   Before you begin commissioning, make sure that the air 

handling unit is started up and the fire damper, if re-
quired, is fully open and that the zone damper is in full 
operation.

•   Check the flow compared to the max. flow in the zone, 

adjust the pressure set point until the correct flow is ob-
tained with TUNE Control. If Max. flow is not achieved, it 
will be necessary to close another/other zone damper(s). 

•   The reference product can be found, i.e. the one with the 

greatest deviation from the design max. flow, by measur-
ing the max. flow of all the ADAPT Parasol EX modules in 
the zone.

•   Measure and record the airflow with the damper set to 

the max. position on the reference ADAPT Parasol EX 
in the zone. Reset the module to the min. flow setting, 
measure and record the airflow. 

•   Set the module back to the max. flow setting.
•   Carry out the same procedure for all the ADAPT Parasol 

EX modules in the zone.

•   Decrease the pressure set point on the zone damper if 

pressure is needed for other zones, for example: 5 Pa.

•   Commission the remaining zones following the same 

procedure.

•   Check/ adjust the previous shut off zones in the same 

way.

•   Reset the pressure set points on all the zone dampers.
•   Identifiy the reference zone, i.e. the zone with the lowest 

flow compared with the design max. flow (for example 
by checking relevant flow across each zone damper using 
the TUNE Control hand-held terminal).

•   Set the min. flow on a number of ADAPT Parasol EX mo-

dules or use the zone damper for setting the min. flow so 
that the ventilation system responds to the simultaneous 
load.

•   Adjust the pressure set point of the air handling unit 

until the zone damper of the reference zone is 85 – 90% 
open. (Managed by the SuperWISE if one is used).

•   Reset all the settings and set all the ADAPT Parasol EX to 

the normal operation setting.

•   Check and measure the max. flow and min. flow with the 

SWICCT or the SuperWISE.

Содержание ADAPT Parasol EXb 1290

Страница 1: ...ADAPT Parasol EXb Installation Commissioning Maintenance 20191101 Art 942428024 A1 B1 B2 A2 Installation...

Страница 2: ...ADAPT Parasol EX 2 Swegon reserves the right to alter specifications 20191101 A3 A4 A5 B3 B4 A6 B5 M8...

Страница 3: ...reserves the right to alter specifications ADAPT Parasol EX utv ndig g nga DN 1 2 A7 B6 d 2 A8 B7 Water Control equipment Note that clamp ring couplings require support sleeves inside the pipes DN15...

Страница 4: ...G0 G0 Sensor Condens 24V 24V blue US black brown US white brown white brown US white 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 2 2 2 3 2 4 2 5 black brown blue black white G Condens brown...

Страница 5: ...MB id 4 Master 20 Master 21 Slave 22 Slave 23 Modbus 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 22 23 24 25 Modular 6 6 RJ12 Modular 6 6 RJ12 22 23 24 25 Modular 6 6 RJ12 1 2 3 4 5 6 7 8 9 10 11 12 1 3 1...

Страница 6: ...ADAPT Parasol EX 6 Swegon reserves the right to alter specifications 20191101 A11 B10 A12 B11 TORX T 25 1 x 8 A13 B12 ON 1 2 Click A14 B13 ON 1 2...

Страница 7: ...7 20191101 Swegon reserves the right to alter specifications ADAPT Parasol EX A15 B14 A16 B15 A17 B16...

Страница 8: ...ADAPT Parasol EX 8 Swegon reserves the right to alter specifications 20191101 A18 B17 A19 B18...

Страница 9: ...1290 H 2 4 1 825 Nozzle configuration H M L H M L 1 x 8 T 25 Pi 2 4 Pi 1 3 Commissioning 1 k 1 3 pi 1 3 q 1 3 The K factor of the short sides together with the commissioning pressure reading of these...

Страница 10: ...unit is started up and the fire damper if re quired is fully open and that the zone damper is in full operation Check the flow compared to the max flow in the zone adjust the pressure set point until...

Страница 11: ...25 Heating comfort alarm Alarm 26 Cooling comfort alarm Alarm 27 Temp Set point overlap alarm Alarm 28 Air quality comfort alarm Alarm 29 Condensation Alarm 33 24 V Out 1 overload error Alarm 34 24 V...

Страница 12: ...ADAPT Parasol EX 12 Swegon reserves the right to alter specifications 20191101 ON 1 2 ON 1 2 2 1 3 5 6 7 8 4 9 Maintenance...

Отзывы: