Swegon reserves the right to alter specifi cations. 

20100215 

www.swegon.com

WISE

Figure 4. Wiring of Master/Slave air diffusers and accessories

1. ADAPT Master air diffuser
2. ADAPT Slave air diffusers
3. CONNECT Adapt, wiring terminals
4. 230-24 V AC Transformer 
5. 5 m long LINK Adapt (RJ45 cable)
6. 5 m long LINK Modbus (RJ45 cable)
7. DETECT Quality (3 VA) or TUNE Temp (1 VA)
8. LUNA AT-2 Radiator control (max 3 valves at 6 VA)
9. Relay for lighting
10. Connection to main control system (Modbus RTU)
11. SPLIT Link

24 V

Modbus

Figure 6. Commissioning.

Maintenance

The exterior surface of the ADAPT air diffusers can be 
cleaned whenever necessary using lukewarm water with 
dishwashing detergent added. Normally the best method 
of cleaning is vacuuming with a brush nozzle. 
The duct system is accessible through the air diffuser and 
the commissioning box. 

Electrical connections.

All the connections are wired to the CONNECT Adapt 
junction box. From there, the Master air diffuser is con-
nected by means of the LINK Adapt (RJ45) cable included 
in the delivery. The slave air diffusers, if required, are 
connected by means of the same type of cable to their 
respective slave contacts. If there are more than 2 slave 
air diffusers, a SPLIT Link should be used for further con-
nection to the last slave air diffuser. See Figure 5. If SPLIT 
Link is used, the maximum permissible length of the LINK 
Adapt cable from the junction box to the last air diffuser 
is 15 metres. If ADAPT is to be connected up to Modbus 
communication, this should be done by means of the 
LINK Modbus (RJ12) cable. All cables and contacts are 
different so that they will not be confused or incorrectly 
connected.

Electrical data

ADAPT is supplied with power via the junction box. See 
the wiring diagram. It is important that cables with appro-
priate cross-sectional area, transformers of correct size 
and power supply cables of correct length are selected 
according to the specifi cations in the sizing documents 
available on www.swegon.com. 

Supply voltage

24 V AC ±10 % 

Max. power consumption

3 VA

Cable rating

0,6 A

Ambient temperature:

0 °C - +50 °C

Commissioning

All the ADAPT Air terminals are supplied preset to the 
so-called commissioning mode, which means that the air 
diffuser is controlled by force to the max. airfl ow setting. 
More information about the commissioning process itself 
can be read in the Project Manual for the WISE system 
and in the instructions for TUNE Adapt. When the ADAPT 
air diffuser is in commissioning mode, the light-emitting 
diode shines orange. 
Steady green LED: Normal operation, the air diffuser is 
operating normally.
Flashing green LED: The air diffuser has just been ener-
gised and calibration is in progress.
Steady red LED: The voltage (24V AC) is too low
Flashing red LED: Internal sensor error
Steady orange LED: The commissioning mode, max. 
airfl ow
Flashing orange LED: Other commissioning modes and 
all the forced control situations of the feed-back control 
system.

2

3

1

Figure 5. Air diffuser connections

1. Connection for LINK Adapt cable (RJ45)
2. Connection for the LINK Modbus cable (RJ12). Only the master 
air diffuser should be connected.
3. Direct 24 V connection if a junction box is not used and the air 
diffuser will be completely “stand alone”.

  20

Master

  21

Slave

  22

Slave

   23

Modbus

5

1

6

 1    2    3   4    5    6    7    8    9  10  11  12  13  14  15  16 

1

2

6

5

4

3

9

8

7

5

5

7

2

2

10

11

5

D1 D0 C

A1  A2 

 

1   3

G

G0

OUT1