2
Swegon reserves the right to alter specifications. 20220627 LNNN00356 (5.4)
Actionair CSS Installation Guide
Application
Installation Method
Actionair CSS
Vertical Application In A Plasterboard Wall
Page 3,
[AA/F13440] 1xType F board each side.
[AA/F12820] 2xType F boards each side.
Vertical Application In A Masonry Wall
Page 4, [AA/F12822]
Horizontal Application In A Slab
Page 5, [AA/F12821]
• The instructions are based on the tested method using
Actionair CSS.
•
Our CSS dampers are designed to be used with fire
separating elements to maintain fire compartments.
The CSS is an actuated failsafe close damper with low
smoke leakage, often referred to in the industry as a
Fire/Smoke damper.
• Under the Fire Damper Product standard BS EN 15650
our Fire Damper products are tested to BS EN 1366-2
and classified under BS EN 13501-3.
• For smoke control, the product you use should be
tested to BS EN 12101-8 and drive open, drive closed
without failsafe position, see our website for informa-
tion on the Actionair SmokeCommand smoke con-
trol damper documentation and suitable installation
methods.
CE Installation Method Overview