Sussman ES 24A Скачать руководство пользователя страница 6

Before Installing your new elements be sure the
McDonnell Miller low water cut-off and aux. low

water cutoff (if supplied) is operating properly. The float chamber and
lower equalizer column of the MM control must be completely clear of
sludge or other foreign matter. Failure to do this may cause the imme-
diate burn-out of the new elements. If the unit is probe equipped,
check condition of the probes and isolator.
All elements are thoroughly checked before shipment The manufactur-
er cannot be responsible for burn-outs caused by a faulty low water
cut-off.
The lower equalizer column can best be examined by breaking the
unions on either side and then visually and manually examining the
piping with your finger or probes to see if it is clear and clean.

1.

Disconnect boiler from electric power supply at main safety switch or

fuse panel. Then turn boiler switch to “OFF" position.

2.

Close water supply valve on incoming water supply line.

Drain boiler completely of water.

3.

Open boiler door to access heating element.

4.

Disconnect wire (electric) leads connecting element to main power system of boiler.

Again, note wire connections to facilitate re-assembly. Proceed to remove
and discard (6) bolts from flange.

IMPORTANT:

Note the wire connections to facilitate re-assembly (see wiring schematic).

Remove and discard six (5/16"-18) bolts from flange. Do not reuse these bolts.

5.

Thoroughly clean boiler flange of all foreign material. Be certain no part of old gasket

remains on flange.

6.

Apply "Slic-Tite" Gasket Compound (or equal) to both surfaces of new gasket supplied

with replacement element. Proceed to install element flange assembly with gasket
between boiler flange and element flange. In doing this, be careful to align flange holes
so element wire connection terminals on element assembly are in line with previously
disconnected wire leads to facilitate easy connections.

NOTE:

Observe markings on element flange. Install element marking “TOP” on top.

7.

Use only new element flange bolts. Tighten all (6) element flange bolts to a torque value

of 22 lb-ft each (see illustration).

8.

Connect all wires to the terminals. Tighten all element terminals to a torque value of

20 lb-in each (see illustration). Make sure all wires are clean and bright to assure good
electrical contact.

9.

Check that the wires are correctly connected to the contactor terminals and are tight-

ened to a torque value of 45 lb-in. (see illustration). Make sure all wires are clean and
bright to assure good electrical contact.

10.

Open water valve to allow water supply to reach boiler feed mechanism.

11.

As boiler automatically refills, observe the new flange assembly for possible leaks.

If water is noticed, the bolts must be re-tightened. Before doing this, turn the boiler
off at the main fuse safety switch.

12.

When boiler reaches working pressure, check flange assembly again for leaks.

Follow maintenance instructions provided with the boiler.

ES 24A Electric Steam Generator

Installation, Operation and Maintenance Manual

_____________________________________________________________________________

6

Element Replacement

Torque Values:

Element Flange Bolts: 22 lb-ft

Element Terminals: 20 lb-in

Contactor Terminals: see Torque chart

For Illustrative Purposes Only.
Power wiring shown in approximate
factory-installed location

TORQUE VALUES

________________________________________

Element Flange Bolts

22 lb-ft

________________________________________

Element Terminals

20 lb-in

________________________________________

Contactor Terminals

45 lb-in

Torque
Wrench

Torque
Wrench

Torque
Wrench

READ INSTRUCTIONS COMPLETELY BEFORE STARTING WORK

Boiler with

McDonnell Miller

1

1

2

1” Steam Equalizing Pipe

Pump and Low Water Control

Normal Boiler Water Line

Cut-Off Level is Arrow Mark

Blowdown Valve

1” Water Equalizing Pipe

!

CAUTION

!

CAUTION

Содержание ES 24A

Страница 1: ...enerator operating pressure or you will require high pressure water feed w motor and pump Products Covered by this Manual Refer to National and all applicable Local Codes for specific installation req...

Страница 2: ...16 F 41 16 G 215 16 H 21 2 I 31 2 J 91 8 K 21 4 L 105 16 M 45 16 N 25 8 O 83 4 P 21 2 Dimensional Table Model 24A Item Description 1 1 4 NPT Strainer 93806 2 1 4 NPT 120V 60HZ Solenoid 1 4 OBIF 99042...

Страница 3: ...wire only Purchaser should use a disconnect switch employing circuit break ers or fuses between the main power source and the boiler Boilers are susceptible to lightning dam age because of plumbing w...

Страница 4: ...k Close steam outlet valve by customer and adjust operating pressure control to a low pressure setting Set hi limit control at 10 PS1G above that setting Switch boiler on to allow for steam pressure b...

Страница 5: ...e boiler switch unless further operation is desirable 6 If you have been supplied with a Manual Reset Low Water Control as required in some states the reset button on the control must be pushed before...

Страница 6: ...with previously disconnected wire leads to facilitate easy connections NOTE Observe markings on element flange Install element marking TOP on top 7 Use only new element flange bolts Tighten all 6 ele...

Страница 7: ...ds of the gauge glass Push both packings about an inch up the gauge glass 4 Gently insert one end of the glass into the top gauge fitting Keeping the glass inside the top fitting gently rotate the top...

Страница 8: ...on at least a once a day basis If boiler water or feed water are outside the above limits a more frequent blowdown is required RECOMMENDED LIMITS WITHIN A BOILER TOTAL DISSOLVED SOLIDS ppm 3500 TOTAL...

Отзывы: