ES 24A Electric

Steam Generator

Installation, Operation and Maintenance Manual

A Division of Sussman-Automatic Corporation

PN 101167 5/12

43-20 34th Street, Long Island City, NY 11101

(718) 937-4500

1-800 238- 3535

Fax: (718) 937-4676

www.sussmanboilers.com

Email: [email protected]

Model No. ___________________________

Power Circuit Voltage

___________________

Boiler Serial No.

__________________

Control Circuit Voltage

__________________

National Board No ____________________

Amps ________ Phase ________ Cy ________

IMPORTANT:

This data file contains the National Board Registration Certificate

approving your generator. It must be kept near the generator at all times.

KW

Design

Max. Work

Model

Range

Steam Rate

BHP

Pressure

Pressure*

__________________________________________________________________________________________

24A

24

73 lbs./hr

2.44

100 PSIG

90 PSIG

__________________________________________________________________________________________

*Line water pressure must be a minimum of 10 PSIG higher than generator operating pressure or you will require high pressure water feed

w/motor and pump.

Products Covered by this Manual

Refer to National and all applicable Local Codes for specific installation requirements.

NOTE:

Reference heating element clearance requirements for particular boiler to allow for removal of elements.

Standard minimum suggested clearance is 21 inches.

1. The boiler should be mounted on a solid level foundation.
2. All piping should be installed by a licensed plumber.
3. When any type water feed other than a pump feed is used, the existing water supply pressure must be 10 PSIG

greater than boiler operating pressure to assure water supply maintains proper water level in boiler. Lack of
water can result in improper boiler operation. Keep feed water valves open at all times during normal operation.

4. Connect steam line with customer supplied outlet valve to boiler steam outlet.
5. During normal operation, keep drain valve closed.
6. If pump and boiler are plumbed within 30 ft (pipe length), a minimum of two check valves are required on boil-

er to avoid damage to pump.

NOTE:

THE SAFETY VALVE SHALL NOT BE PLUMBED WITH A DRAIN

LINE SIZED LESS THAN THE OUTLET SIZE OF THE SAFETY VALVE.

Installation

!

CAUTION

Содержание ES 24A

Страница 1: ...enerator operating pressure or you will require high pressure water feed w motor and pump Products Covered by this Manual Refer to National and all applicable Local Codes for specific installation req...

Страница 2: ...16 F 41 16 G 215 16 H 21 2 I 31 2 J 91 8 K 21 4 L 105 16 M 45 16 N 25 8 O 83 4 P 21 2 Dimensional Table Model 24A Item Description 1 1 4 NPT Strainer 93806 2 1 4 NPT 120V 60HZ Solenoid 1 4 OBIF 99042...

Страница 3: ...wire only Purchaser should use a disconnect switch employing circuit break ers or fuses between the main power source and the boiler Boilers are susceptible to lightning dam age because of plumbing w...

Страница 4: ...k Close steam outlet valve by customer and adjust operating pressure control to a low pressure setting Set hi limit control at 10 PS1G above that setting Switch boiler on to allow for steam pressure b...

Страница 5: ...e boiler switch unless further operation is desirable 6 If you have been supplied with a Manual Reset Low Water Control as required in some states the reset button on the control must be pushed before...

Страница 6: ...with previously disconnected wire leads to facilitate easy connections NOTE Observe markings on element flange Install element marking TOP on top 7 Use only new element flange bolts Tighten all 6 ele...

Страница 7: ...ds of the gauge glass Push both packings about an inch up the gauge glass 4 Gently insert one end of the glass into the top gauge fitting Keeping the glass inside the top fitting gently rotate the top...

Страница 8: ...on at least a once a day basis If boiler water or feed water are outside the above limits a more frequent blowdown is required RECOMMENDED LIMITS WITHIN A BOILER TOTAL DISSOLVED SOLIDS ppm 3500 TOTAL...