Installation Instructions

Determine the location of the fireplace as

described in the fireplace installation manual. Then
plan the location of the duct termination and the route
of the duct run between the fireplace and the 
duct termination.

Duct run must be limited to a maximum distance 

of 40' (12.2m) from the fireplace pipe collar to duct 
termination. This will provide the least restriction to air
flow. No more than four (4) 90º elbows can be used.
Duct run may be horizontal, vertical, inclined or any
combination of these. (Fig. 11) You are now ready to
install the Outside Air Kit.

1. Remove the screws retaining the outside air 

coverplate, if provided. (Located on the left side of
front open units, on backside of multi-sided units.)
Discard coverplate. (Fig. 12)

2. Secure the inlet collar assembly to the outer casing

with four screws (screws not provided). 

3. Slide the duct over the collar and attach the duct to

the collar using the plastic tie straps or three (3)
screws (screws not provided). Continue attaching
the ducting together using three (3) screws at each
joint until you have installed sufficient duct to arrive
at your duct termination locations.

4. At the termination end, install the duct termination.

This should be installed from the outside of the
home. Cut a hole in the desired location 
approximately 4" in diameter, caulk around the
hole, and slide the termination through the opening
from outside the home. The termination/rain cap 
should be caulked around its perimeter to assure 
a tight seal. The rain cap opening should be 
positioned downward. 

The Outside Air Kit is now installed and ready 

for use.

D

DETAIL D

Fig. 12

Ceiling

Duct

Duct
Termination

40ʼ Max
Duct Run

Soffit Termination

Exterior Wall Termination

Exterior Wall

40ʼ Max. Duct Run

Duct

Duct Termination

Rain Cap

Fig. 11

Soffit Termination

40' Max

Duct Run

Exterior Wall Termination

Exterior Wall

Rain Cap

40' Max. Duct Run

Duct

Duct Termination 

 

Содержание VFLB32

Страница 1: ...IN THIS FIREBOX UNLESS THIS FIREBOX MEETS THE MINIMUM DIMENSIONS REQUIRED FOR THE INSTALLATION Homeowner s Installation and Operating Manual Vent Free Universal Firebox model numbers VFLB32 VFLB36 VFL...

Страница 2: ...ed dimensional clearances for firebox size must be followed Refer to the manual that is packed with the log set for operating instructions Table of Contents Safety Information 2 Before You Start 5 Hea...

Страница 3: ...installation of the logs proper location of the heater and annual cleaning are necessary to avoid potential problems with sooting Sooting resulting from improper installation or operation can settle o...

Страница 4: ...he appliance and its appliance main gas valve must be disconnected from the gas supply piping systems during any pressure testing of that system at test pressures in excess of 1 2 psig 3 5kPa 22 The a...

Страница 5: ...he appliance Do not attempt to install any art of the appliance unless you have all the parts in good condition Make Sure That You Have Received All Parts Check your packing list to verify that all li...

Страница 6: ...orative Type Unvented Room Heaters For use with Any ANSI Z21 11 2 Unvented Room Heaters MODEL Front Width Brick to Brick A Back Width Back to Brick B Hearth Depth C VFLB32 29 5 749 mm 16 406 mm 17 432...

Страница 7: ...36 VFLB 42 A 32 36 42 B 30 30 30 C 37 41 47 D 3 3 3 E 38 38 38 F 40 15 40 15 40 15 G 11 35 11 35 11 35 H 20 20 20 J 5 5 5 K 22 26 32 L 21 5 21 5 21 5 M 62 5 66 5 72 5 N 31 25 33 25 36 25 P 44 47 51 2...

Страница 8: ...d licensed plumber Main gas supply must be off when plumbing gas line to fireplace or performing service Consult all local codes All gas piping must be installed to comply with local codes or in the a...

Страница 9: ...ure natural gas pressure is regulated 10 5 w c maximum before operating unit Drafts Do not locate the fireplace in high traffic areas or areas exposed to high drafts and winds Locate the fireplace awa...

Страница 10: ...Use of this mantel guard is required in order to reduce mantel heights as shown in figure 6 When the mantel guard is installed a combustible mantel piece may project 2 from the wall at 6 above the fi...

Страница 11: ...Shim if necessary Step 4 Secure the Firebox Four 4 nailing flanges are supplied with the fireplace to level the box and secure firmly in place Bend the nailing flanges from the sides of the fireplace...

Страница 12: ...mantles to rustic wood paneling stone or brick IT IS IMPORTANT THAT THE BLACK FACE OF THE FIREPLACE NOT BE COVERED WITH ANY TYPE OF COMBUSTIBLE MATERIAL Noncombustible facing materials such as marble...

Страница 13: ...e sure the termination area has 100 square inches of ventilation opening to outside air The duct termination must be located so it does not compete for air flow with exhaust fans gas vent hoods or oth...

Страница 14: ...ot provided 3 Slide the duct over the collar and attach the duct to the collar using the plastic tie straps or three 3 screws screws not provided Continue attaching the ducting together using three 3...

Страница 15: ...or questions concerning prices and policies covering replacement parts Parts may be ordered through your Sure Heat distributor or dealer You will need the correct name part number and model number of...

Страница 16: ...ability of fitness for the purpose and of all other obligations or liabilities Sure Heat Mfg Co does not assume for it any other obli gations or liabilities in connection with the sale or use of the a...

Отзывы: