EHTC7425A

%RH

 °C

HEAT

%RH

Fan

SET

 Rotate

        L

     R

C(on/off)

  HSET

  TSET

Heater relay is activated

In “Running Mode”, indicates the measured relative humidity value.

In “Programming Mode”, indicates the parameter value or unit.

In “Running Mode”, indicates the measured temperature value.

In “Programming Mode”, indicates the parameter name.

In “Running Mode” , switces off the buzzer.

In “Programming Mode”, increase the value or changes the parameters.
In “Running Mode”, changes the humidity set value.

In “Running Mode”, changes the temperature set value.

In “Programming Mode”, indicates the parameter value.

In “Running Mode” , switches off the control outputs.

In “Programming Mode”, decrease the value or changes the parameters.

FRONT PANEL COMMANDS & USAGE

unl

Locking & Unlocking Keypad

Loc

During "Running Mode", if            and           keys are pressed together for 2 seconds,  

  message is displayed and the keypad locked. While keypad is locked, if

Loc

and         keys are pressed together for 2 seconds,  

  message is displayed and the keypad unlocked and "Running Mode" is entered. While keypad is locked, if one of

unL

the key is pressed,  

  message is displayed. During keypad locked, temperature and humidity set values can be displayed but can not be changed.

Loc

Keypad Locked

Keypad Unlocked

Activating / Deactivating Control Outputs

During "Running Mode", if          key is pressed for 2 seconds,  

  message displayed and the control outputs become deactivated and device works as an indicator.

C.di5

While control outputs deactivated, by pressing          key for 2 seconds,  

  message displayed and device continues to control functions.

C.EnB

 Stopping Buzzer Alam

When an alarm condition occurs, an audible alarm is triggered. By pressing

key, buzzer alarm can be turned off.

,

Default Settings

r 001

.

Powered on device by pressing

message appears on display and device reset to default settings.

            key,

Displaying Revision Number

If

keys are pressed together in "Running Mode", revision number

appears on display.

d.par

Displaying and Changing Temperature Set Values

Ölçüm
değerleri

t.5Et

1000

43.0

57.2

57.1

During "Running Mode", if           key is preset, temperature setpoint value flashes for 3 seconds. While flashing, by pressing          and          keys, temperature value can be
changed. If no key is pressed for 3 seconds or if one of the set keys is pressed again, adjusted set value is saved and the "Running Mode" is entered.

1000

27.4

5.71

t.5Et

t.5Et

Ölçüm
değerleri

h.5Et

1000

43.0

61.1

61.0

During "Running Mode", if          key is preset, humidity setpoint value flashes for 3 seconds. While flashing, by pressing           and          keys, humidity set value can be
changed. If no key is pressed for 3 seconds or if one of the set keys is pressed again, adjusted set value is saved and the "Running Mode" is entered.

1000

27.4

61.0

h.5Et

h.5Et

Measurement

Value

1000

43.0

1000

27.4

 SET

 SET

 SET

 SET

 SET

 SET

                                         HUMIDITY TEMPERATURE CONTROLLER

ROTATION
RELAY

r.ofF r.on r.ofF

r.on r.ofF r.on

ROTATION
RELAY

L

R

(*)

(

)

r.on

(

)

r.ofF

Rotation process runs sequentially for left and right directions,

Rotation process runs consecutively as opened until open duration
time

and closed until close duration time

ROTATION OUTPUT GRAPHICS

Indicator(s) LEDs illuminates if ;

Humidity relay is activated

Fan relay is activated

Left relay (rotation)is activated

Right relay (rotation)is activated

Displaying and Changing Humidity Set Values

3. / 7

E-mail :   [email protected]
Internet : www.suran-elektronik.de

Tel.:  +49 (0)7451 / 625 617
Fax:  +49 (0)7451 / 625 0650

SURAN

Industrieelektronik

 / D-72160 Horb a.N

Dettinger Str. 9

EHTC7425A-E-10052019

Содержание ENDA EHTC7425A

Страница 1: ...C Supply Voltage 4 ModBus Blank N A RS ModBus I Specify at Order 1 AS Analog Input DS Digital Input Input Life expectancy for relay 7 x mm sized 2 72 Dual 4 digits display 0 4 20mA 0 10V 1 5V analog o...

Страница 2: ...t be carried on by a qualified staff and must be according to the relevant locally applicable regulations Panel SENSOR Must be ordered separately Silicon cable Brown SDA Black SCL Yellow 3 3V Blue GND...

Страница 3: ...d By pressing key buzzer alarm can be turned off Default Settings r 001 Powered on device by pressing message appears on display and device reset to default settings key Displaying Revision Number If...

Страница 4: ...elf tune menu exits and Running Mode is entered Temperature control will be performed by according to the new PID parameters SELF TUNE OPERATION 5 Err Sensor Failure Check the sensor connection The au...

Страница 5: ...is active when the temperature is below set value cooling control Lo Hi The output is active when the temperature is above the set value heating control Temperature output delay time after power up Hu...

Страница 6: ...arm A b5 Alarm values are A tLo and A tHi rEF Alarm values are A tlo and t 5Et A tlo A tHi t 5Et A tHi Alarm message display delay time after power up Humidity upper level alarm If A htP is changed th...

Страница 7: ...ve no Ye5 YE5 nO YE5 Fan OFF time duration Rotating OFF time duration PARAMETER LIST h inp 0 20 1 5 0 20 Humidity input type 0 20mA 4 20mA 0 10V 1 5V 0 20 4 20 0 10 1 5 mA V A tlo A tHi A tH5 A ttp A...

Страница 8: ...s a parameter value of 140 will be read in Relevant parameters for a period of mm ss type ones in seconds hh mm while those species defined in minutes t HY5 Temperature output delay time after power u...