SURAN ENDA EHTC7425A Скачать руководство пользователя страница 1

                                         HUMIDITY TEMPERATURE CONTROLLER

EHTC7425A

%RH

 °C

HEAT

%RH

Fan

SET

 Rotate

        L

     R

C(on/off)

   HSET

   TSET

EHTC7425A-E-10052019

1  / 7

.

ENDA EHTC7425A  HUMIDITY AND TEMPERATURE CONTROLLER

Thank you for choosing 

 Humidity and Temperature Controller

ENDA EHTC7425A

OUTPUT

Sensor Supply

15VDC , Max. 50mA

30.000.000 Switching for no-load operation; 300.000 switching for 10A resistive load at 250VAC.

HOUSING

Housing type

Suitable for flush-panel mounting according to DIN 43 700.

Dimensions

 W72xH72xD97mm

 Weight

Approx. 350g (after packing)

Enclosure Material

Self extinguishing plastics

While cleaning the device, solvents (thinner, gasoline, acid etc.) or corrosive materials must not be used.

±%0,5 (Full scale)

Approx. 100kΩ

Approx. 10Ω

INPUTS

Input Resistance

Measurement Range Measurement Accuracy

Input Type

0-20mA
4-20mA

1-5V
0-10V

AS

DS

-40.0....125.0  C

º

   0....100 %RH

---------------

EHTD-CB-100

TECHNICAL SPECIFICATIONS

Read this document carefully before using this device. The guarantee will be expired by
damaging of  the device if you don't attend to the directions in the user manual. Also we don't
accept any compensations for personal injury, material damage or capital disadvantages.

ENVIRONMENTAL CONDITIONS

 Height

 Max. 2000m

80  

up to 31

Relative humidity for temperatures

%

°C  decreasing linearly  

50% at 40°C.

,

to

 Ambient/stroge temperature
 Max. Relative humidity

0 ... +50°C/-25 ... 70°C (Without icing)

Rated pollution degree

According to EN 60529        Front panel   : IP6     ,     Rear

5

 panel   : IP20

 Do not use the device in locations subject to corrosive and flammable gases.

Order Code  :  EHTC7425A -        -           -

1

2 -

     230..........230V AC
     SM..........9...30V DC
                     7...24V AC

Supply Voltage

4 ModBus

 -

Blank......N/A
RS ...... ModBus

I

...

                     Specify at Order .

(

)

1 -

      AS.......Analog Input
      DS......Digital Input

Input

  Life expectancy for relay

7  x 

mm sized

2

72

Dual 4 digits display
0/4-20mA, 0-10V, 1- 5V analog or digital input (Specify at Order)
Heating or cooling control selection
PID, On-Off Temperature control selection
PID Auto-calculation (SELF TUNE)
Humidification or drying control selection
Internal supply output for sensor
Timer control for fan relay output
2 Relay outputs with time setting for incubation operations
Adjustable buzzer alarm feature for measurement values
CE marked according to European Norms.

2

3

Sensor must be ordered separately.

                   230V AC ±10%, 50/60Hz  or  9...30V DC / 7...24V AC

 Supply
 Power consumption

Max. 7VA
2.5mm² screw-terminal connections

 Wiring

 EMC

 Safety requirements

 EN 61326-1: 2013
 EN 61010-1: 2010 (pollution degree 2, overvoltage category II)

ELECTRICAL CHARACTERISTICS

0~20mA / 0~10V can be selected for analog output sensors. Temperature range for digital output Enda Sensor is -40~125°C

 Temperature input range

 Humidity input range

0~20mA / 0~10V can be selected for analog output sensors. Humidity range for digital output Enda Sensor is 0~100 RH

When the device is in current measurement mode, the input impedance is 10 . Therefore voltage input should not be connected to the device while

Ω

in current mode. Otherwise the device will deteriorate. If it is necessary to switch from the voltage measurement mode to the current measurement

mode while the device is running, It must be removed and then changed to one of the input type current measurement modes.

E-mail :   [email protected]
Internet : www.suran-elektronik.de

Tel.:  +49 (0)7451 / 625 617
Fax:  +49 (0)7451 / 625 0650

SURAN

Industrieelektronik

 / D-72160 Horb a.N

Dettinger Str. 9

english

Содержание ENDA EHTC7425A

Страница 1: ...C Supply Voltage 4 ModBus Blank N A RS ModBus I Specify at Order 1 AS Analog Input DS Digital Input Input Life expectancy for relay 7 x mm sized 2 72 Dual 4 digits display 0 4 20mA 0 10V 1 5V analog o...

Страница 2: ...t be carried on by a qualified staff and must be according to the relevant locally applicable regulations Panel SENSOR Must be ordered separately Silicon cable Brown SDA Black SCL Yellow 3 3V Blue GND...

Страница 3: ...d By pressing key buzzer alarm can be turned off Default Settings r 001 Powered on device by pressing message appears on display and device reset to default settings key Displaying Revision Number If...

Страница 4: ...elf tune menu exits and Running Mode is entered Temperature control will be performed by according to the new PID parameters SELF TUNE OPERATION 5 Err Sensor Failure Check the sensor connection The au...

Страница 5: ...is active when the temperature is below set value cooling control Lo Hi The output is active when the temperature is above the set value heating control Temperature output delay time after power up Hu...

Страница 6: ...arm A b5 Alarm values are A tLo and A tHi rEF Alarm values are A tlo and t 5Et A tlo A tHi t 5Et A tHi Alarm message display delay time after power up Humidity upper level alarm If A htP is changed th...

Страница 7: ...ve no Ye5 YE5 nO YE5 Fan OFF time duration Rotating OFF time duration PARAMETER LIST h inp 0 20 1 5 0 20 Humidity input type 0 20mA 4 20mA 0 10V 1 5V 0 20 4 20 0 10 1 5 mA V A tlo A tHi A tH5 A ttp A...

Страница 8: ...s a parameter value of 140 will be read in Relevant parameters for a period of mm ss type ones in seconds hh mm while those species defined in minutes t HY5 Temperature output delay time after power u...

Отзывы: