SERVICE 

(Must only be carried out by Authorised Personnel) 

 

Thermostat Re-Calibration – for NG & LPG 

 

1. 

Set temperature to 149

0

C. 

 

2. 

Remove thermostat dial from control by simply pulling forward. 

 

3. 

Remove lock-nut and bush locating washer. 

 

4. 

Remove bush. 

 

5. 

By watching carefully the temperature rise of the oil with the thermostat, turn the control off by means of 

gripping the splined spindle when the temperature is approximately 10

0

C under149

0

C. 

 

Note: 

This allows for a slight latent heat rise after the burner is shut off. 

 

6. 

Place some grease into the serrated internal edge of the bush for adhesion purposes, then fit the bush into 

the thermostat dial. 

 

7. 

Push the dial and  bush over the splined spindle firmly, ensuring that the 149

0

C mark lines up with the 

reference pointer on the thermostat case. When this is done remove the dial and the bush should remain 

in position by means of grease. All that remains now is to replace the bush locating washer and lock-nut 

and replace the dial. 

 

Removal of Thermostat Cover 

 

Pilot regulating screw is located under the control cover as well as a flame rate adjuster if required. This is normally 

set at the factory; however, if it becomes necessary to remove the cover, the following steps are required: 

 

1. 

Set dial to the OFF Position. 

 

2. 

Remove thermostat dial by pulling forward. 

 

3. 

Unscrew the two screws and remove the cover. Make sure that the stop does not catch against the lower 

plate; it is to avoid this that operation (1) is necessary. On units it may be necessary to remove a button 

cover off the control first. 

 

 

 

 

 

DIAGRAM 

 

 

 

 

 

 