background image

Chapter 1 

Introduction

1-1 Overview

The Supermicro PDU system is a rack mounted power distibution unit that can be 

fi tted to a server rack to provide power outlets to rack mounted components. 

1-2  Supermicro PDU Specifi cations

The Supermicro PDU system has the following specifi cations:

Output

Specifi cation

A Source

B Source

Nominal output voltage for each AC output

200-240V

200-240V

Maximum total current draw per phase

24A

24A

Output connections

(21) IEC 320 C13

(21) IEC 320 C13

Overload protection

Yes

Yes

Input

Nominal input voltage

200-240V

200-240V

Input frequency

50/60 Hz

50/60 Hz

Regulatory derated input current (North America)

24A

24A

Input connections

NEMA L6-30P

NEMA L6-30P

Cord length

3.05 meters

3.05 meters

Number of power cords

1

1

Maximum input current per phase

30A

30A

Load capacity

4992 VA ( Input = 208V)

4992 VA ( Input = 208V)

Environmental

Operating Environment

-5 - 50

o

 C

Operating Relative Humidity

5 to 95% RH, Non-condensing

Operating Elevation

0-3000 meters

Storage Temperature

-25 - 80

o

 C

Storage Relative Humidity

0 - 95%

Storage Elevation

0 - 15000 meters

Conformance

Regulatory Approvals

Standard Warranty

2 Years Repair or Replace

Environmental Compliance

RoHS 7b Exemption

Chapter 1: Introduction

1-1

Содержание Power Distribution Unit

Страница 1: ...SUPER Supermicro Power Distribution Unit User s Guide 1 0...

Страница 2: ...f any such disputes Super Micro s total liability for all claims will not exceed the price paid for the hardware product FCC Statement This equipment has been tested and found to comply with the limit...

Страница 3: ...ians only The SuperRack system is a high end rack mounted PDU that can be mounted in different rack systems to provide power managment to rack components Manual Organization Chapter 1 Introduction The...

Страница 4: ...Supermicro PDU User s Guide iv Notes...

Страница 5: ...PDU Specifications 1 1 1 4 Returning Merchandise for Service 1 3 1 5 Contacting Supermicro 1 4 Chapter 2 System Safety 2 1 Electrical Safety Precautions 2 1 2 2 General Safety Precautions 2 2 2 3 ESD...

Страница 6: ...vi Table of Contents Notes...

Страница 7: ...Input Nominal input voltage 200 240V 200 240V Input frequency 50 60 Hz 50 60 Hz Regulatory derated input current North America 24A 24A Input connections NEMA L6 30P NEMA L6 30P Cord length 3 05 meter...

Страница 8: ...1 2 Supermicro PDU User s Guide Figure 1 1 PDU Single Phase Diagram...

Страница 9: ...service RMA authorizations may be requested online at http www supermicro com support rma Whenever possible repack the chassis in the original Supermicro carton using the original packaging material...

Страница 10: ...Super Micro Computer B V Het Sterrenbeeld 28 5215 ML s Hertogenbosch The Netherlands Tel 31 0 73 6400390 Fax 31 0 73 6416525 Email sales supermicro nl General Information support supermicro nl Techni...

Страница 11: ...own the operating system first and then unplug the power cords When working around exposed electrical circuits another person who is familiar with the power off controls should be nearby to switch off...

Страница 12: ...r body which are excellent metal conductors that can create short circuits and harm you if they come into contact with printed circuit boards or areas where power is present After accessing the inside...

Страница 13: ...omponents and printed circuit boards PCBs in their antistatic bags until ready for use Touch a grounded metal object before removing the board from the antistatic bag Do not let components or PCBs com...

Страница 14: ...r Reduced Air Flow Equipment in a rack should be installed so that the amount of air flow required for safe operation of it is not compromised Mechanical Loading Mount the equipment in the rack so tha...

Отзывы: