background image

Figure 16

Rain Cap

Flashing Collar

Flashing

Firestop

68” Min.

(1727mm)

39” Min.

(990mm)

Non-Combustible

Facing

Roof Support

Attic Radiation Shield

The duct system must be installed respecting 

the following:

1. Remove the plates closing up the 8” dia. 

holes on top of the fireplace.  Then, cut 

the insulation in order to obtain two 8” dia. 

openings.  Fix the adaptors on the fireplace 

openings by turning clockwise (

Figures 14 

and 15

)

.

2. Maintain at least a 2” (50 mm) clearance 

between the ducts and any combustible 

material; the required hole size is 13”  x  13” 

(330 mm x 330 mm).

  Exception #1:  For the grills, the fram-

ing can be 10-3/4” x 10-3/4” (275 mm 

x 275 mm) to provide the clearance as 

required by the integral spacers on the 

double outlet duct system.

3.  The maximum number of elbows in a run of 

duct is two.

4. Maintain at least 6-1/2” (160 mm) clearance 

from the outlet grill framing to a combustible 

ceiling, side wall, mantel or floor.

5.  When traversing a combustible wall or floor, 

a firestop must be installed at the wall or floor 

penetration.  The hole size must be 13” x 13” 

(330 mm x 330 mm)

6.  Do not connect the hot air ducts to a central 

heating system.  Malfunction of the heating 

system’s blower will cause the fireplace to 

overheat.  A furnace duct is only single wall 

and not double wall as is required for the 

WRT3820WS fireplace hot air exhaust.  

7. Use only IHP grills and components as 

described in this manual. Other grills or 

registers, for example, may be too restrictive 

and may overheat the fireplace or ceiling.

8. Do not use insulated flexible ducts as they 

will overheat.

9. Do not use tees or any other components 

than the ones specifically listed here.

10. Never allow the ducting to pitch down as 

hot air will be trapped creating a fire hazard. 

 

Never route the ducting downwards.

11. The hot air outlet grills must be installed with 

the louvers pointing downwards in order to 

prevent overheating adjacent ceilings.

6-1/2” Min.

(165mm) to ceiling

u

Combustibles are not allowed below top spacers 

above the fireplace. Facing in front of fireplace must 

be non-combustible below this area.

u

12

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

Central Forced Air Kit 

NOTE: Not tested under EPA certification. If 

installed, this appliance no longer qualifies 

for EPA certification.

The knock-outs provided on the back and on 

the sides of the WRT3820WS fireplace allow 

the connection of insulated flexible pipe which 

enables you to heat adjacent rooms up to 50 

feet from the fireplace hot air outlet.

The ducting system must be installed as de-

scribed below:

A) Remove knock-out plate and cut insulation 

the adaptor at the back and/or the side of the 

fireplace.  Fix the adaptor by twist-locking it 

to the fireplace.  You can use more than one 

outlet on the fireplace 

(see 

Figure 17

).

B) Attach the 5” flexible pipe, using the collars 

provided. 

 Important: Make sure that the 

plastic wrapping around the flexible pipe 

will not be in contact with the fireplace.

C) Route the flexible pipe to the chosen location.  

The ducting system can be installed either 

in an upper room or in a lower room. 

D) Attach the flexible pipe to the blower, using 

the collars 

(

Figure 18

)

.

E) Fix the back draft damper to the blower 

outlet.

F) Attach a flexible pipe to the fan / flexible pipe 

adapter (square to round) and stretch it up 

to the location where the heat is required.

G) At that point, the flexible pipe can be attached 

to any air distribution grill.

H) Install the blower heating and cooling ther-

mostat (HCTW) in that part of the house to 

be heated by the hot air duct. The thermostat 

can be switched to a cooling thermostat and 

installed in the same room as the unit.  This 

thermostat will turn on the blower when the 

room where the fireplace is located becomes 

too hot.

This option requires electricity. Make sure that 

the connections to the blower have been made 

according to the local codes and comply with 

their requirements (see instruction provided 

with the thermostat). For more information 

regarding central forced and ducting, refer 

to the BISFWK-1 installation sheet provided 

with the kit.

Содержание WRT3820WS

Страница 1: ...ances Anymodificationoralterationofthefireplacesystem including but not limited to the fireplace chimney components and accessories may void the warranty listings and approvals of this system and coul...

Страница 2: ...own in front ofanopenflamewhenthewindow is opened Keep any combustible furniture materials or decorative pillows at least 48 1219 mm from the front fireplace opening WARNING Never leave your fireplace...

Страница 3: ...imney Model ASHT S 2100 HT6000 HT6103 or AC manufactured by Security Chimneys Inter national only OR 7 diameter chimney Model ASHT and HT6103manufacturedbySecurityChimneys International only 6 and 7 C...

Страница 4: ...WRT3820WS fireplace will operate best if attention is given to operating the unit with the damper fully opened after refueling in order to bring the firebox and the chimney system up to their optimum...

Страница 5: ...ense in the relatively cool chimney flue of a slow burning fire As a result creosote residue accumulates on the flue lining When ignited this creosote makes an extremely hot fire The chimney shall be...

Страница 6: ...slight amount of friction The door gasket does not need to be tight in all areas since a small amount of leakage is not hazardous or detrimental to the performance of your fireplace Figure 5 Door Ins...

Страница 7: ...et dirty unless the fuel firebox and glass are maintained at hot temperatures see Refueling For Best Performance To clean the glass there are a numberofspeciallydesignedcleaners YourIHP dealercanrecom...

Страница 8: ...e entire width of the fireplace The combustible floor in front of the fireplace must be covered with at least a 1 2 inch of non combustible material tile marble stone etc See Figure 7B Cold climate IN...

Страница 9: ...65 mm 31 11 16 805 mm 37 5 8 956 mm 10 254 mm 10 15 16 278 mm OUTSIDE CHASE G C A Back Wall of Chase Enclosure Including Finishing Materials if any Rough Framing Face Unfinished Shown Zero Clearance F...

Страница 10: ...in 51mm x 76mm Spacer Mantel and Facing Side View 2 Rock Board or Other Noncombustible Facing Drywall Insulate Joists Same As Ceiling Draft Stops Firestop CTDT Termination Note Non Combustible Chase F...

Страница 11: ...tible mate rial should be superposed or projecting over the front of the fireplace Noncombustible Facing Drywall 2 X 3 Min Rock Board or Other Spacer Figure 12 13 x 13 10 3 1m Max Figure 13 Maintain a...

Страница 12: ...m to ceiling uCombustibles are not allowed below top spacers above the fireplace Facing in front of fireplace must be non combustible below this area u 12 NOTE DIAGRAMS ILLUSTRATIONS ARE NOT TO SCALE...

Страница 13: ...e door closed it will pull only a slight amount of air from the house Nevertheless the outside air kit might be mandatory in your jurisdiction check your local building code To install an outside air...

Страница 14: ...are especially prone to flow reversal 2 The IHP fireplace model WRT3820WS may be installed only with Security Chimneys International Ltd 6 diameter chimney systems The WRT3820WS fireplace may also be...

Страница 15: ...between the roof and the flashing with roofing pitch see Figures 26 and 27 For sloping roofs place the flashing under the upper shingles and on top of the lower shingles Nail the flashing to the roof...

Страница 16: ...line up the center of the hole Cut a hole for the chimney in the ceiling floor Frame this hole as described previously refer to section Chimney Instal lation Instructions 5 From below install a firest...

Страница 17: ...22 mm 6 1 8 156 mm 11 280 mm 14 1 8 359 mm 16 7 8 429 mm 18 7 16 468 mm 23 584 mm 26 3 16 665 mm B 27 11 16 703 mm 33 1 2 851 mm 50 7 8 1292 mm 62 1 2 1588 mm 72 5 8 1845 mm 78 7 16 1992 mm 95 3 4 243...

Страница 18: ...d that you use the insulated wall radiation shield since it will maintain the home s thermal barrier RSM and RSMI30 RSMI45 Canada Only Chimney Model Angle Hole Size ASHT HT6103 6 dia Canada only 30 28...

Страница 19: ...provided with the support CHIMNEY MODEL MAXIMUM HEIGHT OF SUPPORTED CHIMNEY Offset Support Roof Support ASHT HT6103 6 dia 28feet 8 54m 29feet 8 84 m S 2100 HT6000 6 dia 18feet 5 49m 20feet 6 1 m AC 6...

Страница 20: ...nry chimney 2 In the middle of the oval drill a hole in the masonry chimney at 45 3 Increase the size of the hole until a 45 Tubinox liner elbow can be easily slipped through 4 Slide the liner down fr...

Страница 21: ...o disk VTU fan to flexible pipe adapter BISAVF back draft damper BISBD aluminium tape BISFWK 1 BISFWK 1 Flexible pipe 5 I D x 15 ft Long 5FLEX15 5FLEX15 Flexible pipe 5 I D x 30 ft Long 5FLEX25 5FLEX2...

Страница 22: ...ory PR SR2827 Front refractory 2 pieces PR SR2829 Secondary air tube back PR SR2906 Secondary air tube middle or front PR SR2830 Tube lock 2 pieces PR SR2873 Fireplace left side PR SR2848 Fireplace ri...

Страница 23: ...is needed immediately off the top of the fireplace an elbow starter section AC6SB30 is available oChimney Adaptor 7in If you want to install a 7in ASHT HT6103 chimney an adaptor is available 6AW7 Secu...

Страница 24: ...nsulated Wall Radiation Shield 6 12 6LRSMI 6LRSMI Adaptors to Masonry Chimney Masonry Chimney Adaptor 45 BISUMA for use with Tubinox liner CANADA ONLY BISUMA Masonry Chimney Adaptor 30 BISUMA30 for us...

Страница 25: ...normal use with approved fuels listed in the Operation Manual provided with the product This includes burning such fireplace fuels as wood and natural or propane gas Fuel products with abnormal burnin...

Страница 26: ...age 22 for a complete replacement parts list Use only parts sup plied from the manufacturer Normally all parts should be ordered through your IHP distributor or dealer Parts will be shipped at prevail...

Отзывы: