NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

27

Figure 48

TEST ALL CONNECTIONS FOR GAS LEAKS 
(FACTORY AND FIELD):

Turn on gas supply and test for gas leaks using a 
gas leak test solution (also referred to as bubble 
leak solution).  

Note: 

Using a soapy water solution 

(50% dish soap, 50% water) is an effective leak 
test solution but it is not recommended, because 
the soap residue that is left on the pipes/fi ttings 
can result in corrosion over time.

     

WARNING

Never use an open fl ame to check for leaks.

Turn on gas supply and test for gas leaks using 
a gas leak test solution. 

A. Light the appliance (refer to the lighting 

instructions label in control compartment 
or homeowner's manual).

B.  Brush all joints and connections with the gas 

leak test solution to check for leaks. If bubbles 
are formed, or gas odor is detected, turn the 
gas control knob (off/pilot/on) to the “OFF” 
position.  Either tighten or refasten the leaking 
connection, then retest as described above.

C.  When the gas lines are tested and leak free be 

sure to rinse off the leak testing solution, 

D. Turn on burner then observe the individual 

tongues of fl ame on the burner.  Make sure 
all ports are open and producing fl ame evenly 
across the burner.  If any ports are blocked, or 
partially blocked, clean out the ports.

Note:The gas supply line must be installed in 
accordance with building codes by a qualifi ed 
installer approved and/or licensed as requed by 
the locality.  In the Commonwealth of Massachu-
setts, installation must be performed by a licensed 
plumber or gas fi tter.

Step 6. CONNECTING GAS LINE 

Make gas line connections. All codes require a 
shut-off valve mounted in the supply line. 

Figure 

47 

 illustrates two methods for connecting the 

as supply. The fl ex-line method is acceptable 
in the U.S., however, Canadian requirements 
vary depending on locality. Installation must 
be in compliance with local codes.

These appliances are equipped with a gas fl ex 
line for use (where permitted) in connecting 
the appliance to the gas line.  A gas fl ex line 
is provided to aid in attaching the direct vent 
appliance to the gas supply.  The gas fl ex line 
can only be used where local codes permit.  
See 

Figure 47

  for fl ex line description. The fl ex 

line is rated for both natural gas and propane 
gas. A manual shut off valve is also provided 
with the fl ex line.

  The incoming gas line should be piped into 

the valve compartment and connected (see 

Figures 47 & 48

)

. The millivolt control 

valve has a 3/8" (10 mm) NPT thread 
inlet port. The electronic control valve 
has a 1/2" (13 mm) NPT thread inlet port 
and is fi tted with a 1/2" x 3/8" (13 mm x 
10 mm) NPT fi tting.

Secure all joints tightly using appropriate 
tools and sealing compounds (ensure propane 
resistant compounds are used in propane 
applications).

Optional: Seal around the gas line to prevent 
cold air leakage.

Figure 47

Gas
Valve

3/8" NPT  x

Flare Fitting

3/8" Flex Tubing

3/8" Nipple

3/8" Union

3/8" Close Nipple

3/8" Shut-off Valve

1/2" x 3/8" 

Reducer

Gas

Stub

1/2" x 3/8" Flare

Shut-off Valve

Gas Flex Line Connector

*Sediment Trap

*A Sediment Trap is recom-
mended to prevent moisture 
and debris in gas line from 
damaging the valve.

3"

Min

.

Gas Valve

Piezo Igniter

Latch for 

Glass Door

HI/LO (fl ame height 

control knob)

OFF/PILOT/ON (gas control knob)

Gas Flex Line

Optional OFF/ON 
Switch Can be 
Installed Here

Glass Door is Above

 Control Compartment

CONTROL COMPARTMENT ACCESS/LOUVER 
PANEL INSTRUCTIONS 

(

Ref. Figure 49)

NOTE: 

 The top louvered panel and the bottom 

louvered control panel door remove and install 
the same way as follows:

The gas controls can be found behind the control 
compartment access door. 

Removing Control Compartment Door:

Open the door by  gently lifting it upward until the 
hook catches on boths sides clear the locating 
slots. Then pull door out to remove.

On millivolt systems, the piezo igniter, HI/LO 
fl ame adjustment knob, and pilot and main 
gas OFF/ON control knob are located below 
the glass panel enclosure. The gas valve for 
electronic systems is also located below the 
glass enclosure panel. See 

Figure 48.

Figure 49

OPENING CONTROL 
COMPARTMENT DOOR

Control Valve

Lower Control 
Compartment Door

Lift the Lower Control 
Compartment Door 
up and pull out to 
remove.

Up

Out

Hook Catch

Reinstalling Control Compartment Door:

To reinstall, insert the hook catches on each 
side of the door into the corresponding slots 
in the control compartment opening, then 
gently push forward and slide down until it 
locks in place.

 

GAS CONNECTION

 Control Compartment 

Access

Содержание SSDVPF-CNE

Страница 1: ...uch any electrical switches Do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow your gas suppliers instructions If your gas supplier cannot be reach...

Страница 2: ...sted for operation and installation with the following vent com ponents only Secure Vent Direct Vent System Compo nents Secure Flex Flexible Vent Components manufactured by Security Chimneys Inter nat...

Страница 3: ...H I LO W H T P T H T P T P I L O T P I L O T O N i t OFF IN OUT Manifold Pressure Tap Inlet Pressure Tap SIT Millivolt Gas Valve Pilot Adjustment Screw HI LO Variable Flame Height Adjustment Main Gas...

Страница 4: ...zontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS Inspection The...

Страница 5: ...mproper installation or use of this appli ance can cause serious injury or deathfromfire burns explosion or carbon monoxide poisoning IMPORTANT These appliances must not be connected to a chimney or f...

Страница 6: ...le home where not prohibited by local codes This appliance may be installed as an OEM installation in a manufactured home USA only or mobile home and must be installed in accordance with the manufactu...

Страница 7: ...CES These instructions should be used as a guideline and do not supersede local codes in any way Install vent according to local codes these instructions the current National Fuel Gas Code ANSI Z223 1...

Страница 8: ...3 feet 91 cm within a height of 15 feet above the meter regulator assembly 3 feet 91 cm within a height of 15 feet above the meter regulator assembly I Clearance to service regulator vent outlet 3 fee...

Страница 9: ...on the appliance front and back faces with the following exception If the optional radiant panels are installed the non combustible material may cover any portion of the top radiant panel or the air g...

Страница 10: ...1 2 3 8 10 40 1 2 1 2 40 100 1 2 1 2 100 150 3 4 1 2 150 200 3 4 1 2 Table 8 Notes All appliances are factory equipped with a flexiblegaslineconnectorand1 2inchshutoff valve see Figure 47 on Page 27 S...

Страница 11: ...0 12 1 8 308 10 1 2 22 3 4 578 6 1 4 159 A 7 178 5 1 8 130 12 1 8 308 26 3 4 Provide additional space for Side Vent Seal Cap if installing against a solid wall Louvered Control Compartment Door Left S...

Страница 12: ...ry installed vent seal cap see Figures 15 16 on Page 13 in each flue outlet EFFICIENCIES SSDVPF 58 NG 61 LP Steady State 72 NG 73 LP AFUE 68 NG 68 LP Louvered Control Compartment Door Left Side View T...

Страница 13: ...nal Fuel Gas Code ANSI Z223 1 in the USA or the current standards of CAN CGA B149 1 and B149 2 in Canada Use only approved venting components See Approved Vent Compo nents Page 2 These fireplaces must...

Страница 14: ...1 0 3 0 0 4 5 3 7 5 2 1 6 1 0 0 2 0 3 5 9 7 5 2 6 6 0 1 0 2 0 3 1 8 5 7 6 0 0 0 1 1 2 0 9 5 7 0 2 1 0 1 4 5 1 9 5 2 6 7 0 0 2 0 1 3 3 9 5 7 7 0 0 0 0 2 2 6 9 8 1 0 1 2 0 4 5 7 9 5 2 1 8 1 0 0 0 2 3 2...

Страница 15: ...n installing in tight and confined spaces or where the vent run made up of fixed length pieces develops a joint in a undesirable location or will not build up to the required length The SV4 5LA Telesc...

Страница 16: ...tions See Figure 23 Use a carpenter s level to measure from a constant surface and adjust the support straps as necessary It is important to maintain the required clear ancestocombustibles 1 25mm atal...

Страница 17: ...needed then 4 feet minimum of V vertical vent will be required This table shows a 1 V to 5 H ratio Forevery1footof V verti cal you are allowed 5 feet of H horizontal run up to a maximum horizontal run...

Страница 18: ...1 524 2 0 610 1 0 305 10 3 048 4 1 219 2 0 610 15 4 572 6 1 829 3 0 914 20 6 096 8 2 438 4 1 219 V V1 H H1 40feet 12 2m Max H 8 feet 2 438 meters Max H H1 20 feet 6 096 meters Max Example If 20 feet...

Страница 19: ...with 8d nails or other ap propriate fasteners at each corner Remembertomaintain1 25mm clearance tocombustibles framingmembers andattic or ceiling insulation when running vertical chimney sections Atti...

Страница 20: ...seats against the exterior wall surface to which it will be attached Orient the housing of the termination with the arrow pointed upwards Secure the termination to the exterior wall The horizontal te...

Страница 21: ...ionKitand 6In Vent Section SV4 5L6 10 3 4 to 14 273 to 356 Termination Kit and 12 in Vent Section SV4 5L12 16 3 4 to 20 426 to 508 Termination Kit and Tele scopic Section SV4 5L12 11 3 4 to 20 299 to...

Страница 22: ...Spacer SV4 5HF When using Secure Flex use Firestop Spacer SF4 5VF When using Secure Flex use Firestop Spacer SF4 5HF Note See Table 11 as an aid in venting component selection for a particular range...

Страница 23: ...s Max H H1 H2 20 feet 6 096 meters Max Example If 20 feet total H H1 H2 horizontal vent run is needed then 4 feet minimum of V vertical vent will be required This table shows a 1 V to 5 H ratio For ev...

Страница 24: ...y around the inner flexible vent pipe push it back out of the way 2 ApplyabeadofMill PacBlack 700 F high temperature sealant Catalog No 10K81 to the inner adapter collar approximately 1 2 inch from th...

Страница 25: ...el OFF ON Switch TP TH TH Install OFF ON Switch millivolt models 1 Connect the 2 wires provided in Electrical Outlet Kit to the TP TH and TH terminals on valve 2 Pass the 2 wires through the opening w...

Страница 26: ...h wires CAUTION Remove the carton support from the control compartment before operating the appliance Electronic Wiring Diagram Honeywell Showing Blower Wiring for Optional FBK 100 FBK 200 FBK 250 Kit...

Страница 27: ...igure 47 for flex line description The flex line is rated for both natural gas and propane gas A manual shut off valve is also provided with the flex line The incoming gas line should be piped into th...

Страница 28: ...ce Checkout The pilot flame should be steady not lifting or floating Flame should be blue in color with traces of orange at the outer edge The top 3 8 10 mm at the pilot generator thermopile and the t...

Страница 29: ...top louver assembly by lifting it up and pulling it out 2 Remove the control compartment access door see removal instructions on Page 27 Removing Control Compartment Door 3 Locate the two 2 latches at...

Страница 30: ...erving the flame continu ouslytoensurethattheproperflameappear ance has been achieved see Figure 52 If the following conditions are present adjust accordingly If flame appears weak or sooty adjust the...

Страница 31: ...77L76 SV4 5E45 45 Degree Elbow 5 77L77 SV4 5E90 90 Degree Elbow 3 4 5 6 7 10 1 8 9 11 INSTALLATION ACCESSORIES The following flashings come packaged with a storm collar 6 77L78 SV4 5F Flat Roof Flashi...

Страница 32: ...12 Mill Pac Black High Temperature Sealant Bulk 12 pack 23 91L66 SF GC4 6 Gear Clamp 4 5 in 114 mm for flex 6 pieces 23 91L67 SF GC7 6 Gear Clamp 7 5 in 190 5 mm for flex 6 pieces 25 H1988 CTSA 33 Ch...

Страница 33: ...stallation is not proper and completeuntiltheoperationofthe convertedapplianceischeckedas specifiedintheownerinstructions suppliedwiththekit Thequalified service agency performing this installationass...

Страница 34: ...kit is available order Catalog No 87L54 Electronic Appliances Step 7 Honeywell Electronic Valves See Figure 61 and the instructions provided with the kit Remove the slotted cap screw o ring pressure...

Страница 35: ...nstall the rear burner in the front burner s position BRACKET A BURNER PORTS NOTE INSTALL REAR BURNER FIRST THEN FRONT BURNER BURNER ORIFICE Step9 Reassembletheremainingcomponents by reversing the pro...

Страница 36: ...o make changes at any time without notice in design materials specifications prices and also to discontinue colors styles and products Consult your local distributor for fireplace code information LHP...

Отзывы: