NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

TROUBLESHOOTING THE ELECTRONIC IGNITION SYSTEM

SYMPTOM

POSSIBLE CAUSES

CORRECTIVE ACTION

See Below.

Disconnect the two black wires from the wire nuts. Test switch(s) for
continuity with a multimeter. If continuity is not indicated, switch(s) is
defective and must be replaced.

Note:

 

Before replacing “OFF/ON” switch, be sure to check wiring for loose

connections or broken wires and repair as needed.

Check main burner orifice(s) for stoppage. Clean or replace.

Check vent system for obstructions.

A.

Faulty Valve System.

B.

“OFF/ON” or wall switch
defective.

A.

Burner orifice plugged.

B.

Obstructed vent system.

1.

Burner will not light.

2.

Burners come “ON” but
go “OFF.”

N

ote:

 Before troubleshooting, be sure that the appliance main line gas shut-off valve, the gas control valve and the wall switch are in

the “ON” position.

Important:

 Valve system troubleshooting should only be accomplished by a qualified service technician.

• Turn Off Gas Supply
• Assure Valve Switch Is In ON Position
• Disconnect Control Harness
• Set Thermostat To Call For Heat

• Check For Proper Voltage At Control Harness
  (See Insert A).  Voltage Should Be 24V
  Between Thermostat Or Pressure Switch
  And 24V Common And 24V Hot.

• Line Voltage Power
• Low Voltage Transformer
• Limit Controller
• Thermostat
• Wiring

2

CHECK

START

NO

• Plug Control Harness Into Valve.  Wait For
   Internal Check Delay.

YES

• Igniter Warms Up And Glows Red.

• With Pilot Burner Cable Connected, Measure
   Voltage At Valve HSI Element Output.  24V
   Nominal.  (See Insert B)

NO

• Replace Igniter/Flame Rod Assembly.

YES

• Replace Valve.

NO

• Turn On Gas Supply.    • Pilot Burner Lights.

• Check That Pilot Gas Is Flowing.  Wait To
   Assure Plot Gas Tubing Is Purged.  Recycle
   Call For Heat If Necessary.

NO

YES

NO

YES

YES

1

• Measure Voltage Between 24V Hot And 24V Common
  Leads To Valve Control.  Must Measure At Least 19.5
  VAC With Igniter Powered (See Insert A).  To Identify
  Proper Lead, This Check Must Be Done With The
  Valve Control Connected And Igniter Powered.

• Check Transformer And
   Line Volt Supply.

NO

• Replace Pilot Assembly.

YES

• Check That Pilot Flame Makes Good Contact With
   Pilot Burner Flame Rod.
• Check For Good Electrical Connection Through The
   Pilot Tubing.
• If Both Of The Above Are Good, Replace Igniter/Flame
   Rod Assembly.

• Cycle Thermostat Off And Back On.

YES

• Main Valve Opens And Main Burner Lights.

NO

YES

• System Is Okay.

YES

• Main Burner Lights.

NO

2

1

Igniter Will Cycle Off And Back On Once During
The 90 Second Ignition Trial.  All Voltage
Measurements Must Be Taken While The Igniter
Is Powered.

When Measured Voltage At Connections, Use
Care To Assure Terminals Are Not Damaged.

• Replace Valve.

• Replace Valve.

24 Volt Hot

End View Of
Control Harness
Connector

24 Volt
Common

24 Volt
Switched

Check For Damaged Or Missing Terminals
In Connector

Insert A

Igniter Terminals

Insert B

2

1

Содержание D-500CEN

Страница 1: ...ou la zone Appelez imm diatement votre fournisseur de gaz depuis un voisin Suivez les instructions du fournisseur Si vous ne pouvez rejoindre le fournisseur de gaz appelez le service dos incendies L...

Страница 2: ...ed to operate these units These appliances comply with National Safety Standards and are tested and listed by Omni Test Laboratories Report No 116 F 13 4 to ANSI Z21 88 2002 in Canada CSA 2 33 2002 an...

Страница 3: ...trolvalveshowninFigure3 SIT or Figure 4 Honeywell on page 4 Appliances with electronic systems will be fitted with the elec tronic valve shown in Figure 2 on page 4 Familiarize yourself with the gas c...

Страница 4: ...ep the appliance area clear and free from combustible materials gasoline and other flammable liquids 6 Remember Millivolt appliances have a con tinuous burning pilot flame Exercise caution when using...

Страница 5: ...DR 800 on page 7 andverifytheflamepatternandheightdisplayed bytheapplianceconformstothepicture Flames must not impinge on the logs Refer to Figure 10 SIT Millivolt Figure 11 Honeywell Millivolt or Fig...

Страница 6: ...opening on the main burner tube should be adjusted Normally the more offsets in the vent system the greater the need for the air shutter to be opened further WARNING NEVEROPERATETHEAPPLIANCE WITHOUTT...

Страница 7: ...DR 500 8 D DT DR 600 or 9 D DT DR 800 For more detailed placement instructions refer to the LOG PLACEMENT GUIDE accompanying this document Proper twig placement is critical to prevent sooting Twigs sh...

Страница 8: ...y pleasing appearance For best re sults spread in a non uniform manner while ensuringcompletecoverageoftheblacksheet metal surface Note Do Not place decorative volcanic stone on top of the gas burner...

Страница 9: ...on of the part 5 The quantity required 6 The installation date of the appliance SIT And Honeywell Millivolt Wiring Diagram If any of the original wire as supplied must be replaced it must be replaced...

Страница 10: ...display including room temperature in either metric or English units flame indicator and clock Fully programmable the Model RCL T allows for command over nearly all operational and temperature variab...

Страница 11: ...0 8 R 5 K L B 1 0 L 0 8 T 5 K L B 0 0 6 R D T D D 4 0 L 0 8 R 6 K L B 2 0 L 0 8 T 6 K L B 0 0 8 R D T D D 5 0 L 0 8 R 8 K L B 2 2 L 9 9 T 8 K L B s t i K l e n a P e c a F n a e l C o N l e d o M o N...

Страница 12: ...in gas control knob slightly and turn counterclockwise to PILOT 8 Push in control knob all the way and hold in Immediately light the pilot by triggering the spark ignitor pushing the button until pil...

Страница 13: ...que Ne vous servez d aucun t l phone dans votre difice Appelez imm diatement votre compagnie de gaz en utilisant le t l phone du voisin S il vous est impossible de contacter votre compagnie de gaz app...

Страница 14: ...use this appliance if any part has been under water Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has...

Страница 15: ...inspecter l appareil et remplacer toute pi cedusyst meder glageoucommandedugazquia t sous l eau 1 ARR TEZ Lisez les consignes de s curit au verso de cette plaque 2 Tournez l interrupteur mural la pos...

Страница 16: ...lot flame for maximum flame impinge ment on thermocouple Figure 10 on page 8 SIT Figure 11 on page 8 Honeywell Check burner orifice for stoppage and remove Checkthermopilewithmillivoltmeter Takereadin...

Страница 17: ...NO Plug Control Harness Into Valve Wait For Internal Check Delay YES Igniter Warms Up And Glows Red With Pilot Burner Cable Connected Measure Voltage At Valve HSI Element Output 24V Nominal See Insert...

Страница 18: ...z e i P 1 0 9 8 M 4 2 1 1 0 9 8 M 4 2 1 7 3 d l e i h S t o l i P 6 0 7 2 9 B L 1 6 0 7 2 9 B L 1 o N N O I T P I R C S E D 0 0 5 R D T D D 0 0 6 R D T D D 0 0 8 R D T D D o N t r a P y t Q o N t r a...

Страница 19: ...9 NOTE DIAGRAMS ILLUSTRATIONS NOT TO SCALE REPLACEMENT PARTS 4 2 1 13 2 5 41 40 21 14 12 6 43 23 22 24 42 3 26 25 30 31 32 33 34 35 15 D DT DR 500 16 36 11 27 37 20 10 8 D DT DR 600 D DR DR 800 9 17 7...

Страница 20: ...25 032M REV H 11 2004 The manufacturer reserves the right to make changes at any time without notice in design materials specifications prices and also to discontinue colors styles and products Consul...

Отзывы: