Hearth Extensions and Wall Shields

A hearth extension must be installed with
all fireplaces. It is to protect the combustible
floor in front of the fireplace from both radi-
ant heat and sparks. The hearth extension
must extend 8" beyond both sides of the
fireplace opening and 16" beyond the front
(

see Figure 48 ). Use a hearth extension

constructed of a durable noncombustible
material having an equal or greater insulat-
ing value of k = 1.28BTU/IN FT

HR 

°

F or a

thermal resistance that equals or exceeds r =
.78 HR 

°

F FT

2

 IN/BTU.  With these values,

determine the minimum thickness/material
required using the formula and the Table on
page 17.

Note:

 Any noncombustible material whose k

value is less than 1.28 or whose r value is more
than .78 is acceptable.

If the fireplace is installed on a combustible
floor, use the metal safety strips (provided)
on the floor extending half under the fireplace
and half under the hearth extension (refer to
Figures 6 and 7 ).

Figure 47

Typical Installation

*Both Of These Dimensions Must Be At Least 18”
When An Unvented Gas Log Set Rated At 26,000
BTU Or Higher Is Used.  (Maximum 40,000 BTU)

12"*
Min.

8 3/8"*

Fireplace
Opening

Combustible
Mantel
and Trim

12"

Max.

1 1/2"

Finished
Wall

Header

Spacer

Glass Doors

If glass doors are to be installed on these
fireplaces, refer to specific installation instruc-
tions packed with the glass doors. Use only the
doors that are listed for use with these fire-
places. Use of other non-listed glass door on
these fireplaces may constitute a potential fire
hazard and is not recommended.

CAUTION: CERTAIN GLASS DOORS OVERLAP
THE BLACK METAL FACING OF THE FIRE-
PLACE. IF THE FIREPLACE HAS BEEN FACED
WITH NONCOMBUSTIBLE MATERIALS, THERE
MIGHT NOT BE SUFFICIENT CLEARANCE TO
INSTALL THE GLASS DOORS OF YOUR
CHOICE. ENSURE ADEQUATE CLEARANCE IS
MAINTAINED AT ALL TIMES SO AS NOT TO
INTERFERE WITH THE INSTALLATION AND
OPERATION OF GLASS DOORS.

COLD CLIMATE INSULATION

If you live in a cold climate, it is especially
important to seal all cracks around the fire-
place opening with noncombustible material
and wherever cold air could enter the room.
Surrounding materials must be caulked where
it meets the black metal facing of the fireplace
to avoid cold air intrusion. Use noncombus-
tible caulking material only on fireplace facing
to seal. Also, the outside air inlet duct should
be wrapped with noncombustible insulation to
minimize the formation of condensation. Do
not place insulation materials on top of fire-
place or against chimney sections.

Note:

 A 2" air space must be preserved for all

combustible materials extending for any con-
tinuous length adjacent to the chimney.

It is especially important to insulate between
the studs of an outside chase cavity and under
the floor if the floor is above ground level. Do
not place insulation directly against the fire-
place or chimney system.

Figure 46

FIREPLACE FINISHES

Mantels and Trim

It is sometimes best to frame your fireplace
after it is positioned and the chimney is in-
stalled. Frame enclosure for chimney and fire-
place with 2 x 4’s (or heavier) lumber.

Note:

 The header may rest on the two (2) metal

top spacers on top of the unit but the header
must not be notched to fit around the spacers.

These fireplaces may sit directly on a combus-
tible surface.  A 2" air space is required be-
tween combustible framing and the chimney.
A 1" air space is required between combustible
framing and fireplace outer wrapper.  In Canada,
the minimum height for a combustible mantel
is 18" (457 mm) above the fireplace opening.
Figure 46 shows typical Canadian installa-
tions.  For installations other than Canada,
combustible mantels and trim may be in-
stalled 12" above the fireplace opening as per
NFPA 211, Section 7-2.3.3. and 

Figure 47.  If

a mantel is of a noncombustible material, it is
exempt from these requirements as long as it
does not interfere with the installation or op-
eration of glass doors.

Canadian Installation

Fireplace
Opening

Finished
Wall

Header

Spacer

8" Max.

(203mm)

18" Min.

(457mm)

Combustible

Mantel

Содержание CUSTOM SERIES RD-36

Страница 1: ...place or its components under any circumstances Any modification or alteration of the fireplace system including but not limited to the fireplace chimney components and accessories may void the warranty listings and approvals of this system and could result in an unsafe and potentially dangerous installation IMPORTANT TO ASSURE PROPER ALIGNMENT OF GLASS DOORS INSTALL THIS FIREPLACE IN A SQUARE AND...

Страница 2: ...physical damage as a result of handling or transporta tion These items should be inspected by your distributor or qualified factory representative to ensure safe condition When in doubt con sult your distributor 16 For additional safety considerations and complete operating instructions refer to the Care and Operation Manual provided with the fireplace TOOLS AND BUILDING SUPPLIES NORMALLY REQUIRED...

Страница 3: ...lled These fireplace systems are designed for in stallation in accordance with the National Fire Protection Standard for chimneys fireplaces and solid fuel burning appliances NFPA 211 and in accordance with codes such as the BOCA Basic National Codes the Standard Me chanicalCodeandtheUniformBuildingCodes WARNING FAILURE TO USE MANUFAC TUREPROVIDEDPARTS VARIATIONSIN TECHNIQUES AND CONSTRUCTION MA T...

Страница 4: ...urface Outside Base Insulation Thermal Barrier 8 Level Security s FTF8 Pipe Vertical Installation 15 0 One Offset 15 0 Two Offsets 25 0 Minimum System Height Note Do not insulate the chase cavity with blown or fill type insulation materials Note Local codes may not require firestopping at the ceiling levels for outside chase installa tions However it is recommended for safety and the reduction of ...

Страница 5: ...al safety strips beneaththefireplaceasillustrated Figures6 7 and 8 The safety strips should overlap for continual coverage of the floor Note Safety strips are not required when fire place rests on a noncombustible surface ASSEMBLY STEPS Note The following steps represent the normal sequence of installation Each installation is unique however and might require a different sequence 1 Position firebo...

Страница 6: ... measured from a finished surface If a wall covering such as drywall is to be attached to the rear wall then the 21 552 mm must be measured from the drywall surface It is important that this dimension be exact If the appliance is to be elevated above floor level a solid continuous platform must be constructed The header may rest on the top metal spacers but must not be notched to fit around them C...

Страница 7: ...ade Perpendicular to roof ridge A B Ceiling Framing C D Roof Framing FRAMING SPECIFICATIONS Figure 11 Figure 12 Figure 13 A G Inside Chase H Back Wall of Chase Enclosure Including Finising Materials if any Rough Framing Face Unfinished Shown FOAK Combustion Air Kit A Outside Chase G C H Back Wall of Chase Enclosure Including Finising Materials if any Rough Framing Face Unfinished Shown FOAK Combus...

Страница 8: ...replace and secure with two 2 screws from the kit s hardware package Step 7 Route the Class 0 air duct out the back or side wall up through the ceiling or floor joists to an outside wall The air inlet hood should be located above snow level or above any anticipated snow level Figure 19 Figure 19 Note If the fireplace is installed against an inside wall the class 0 air duct may be ex tended into a ...

Страница 9: ...ight assembly between sections Plan your chimney requirements carefully before assembly as chimney is diffi cult to disassemble after installation If disas sembled the tabs might become damaged Be certain tabs are properly formed to ensure locking tabs engage properly The Security FTF8 chimney system is a two piece chimney which snap together from the fireplace up Start with the inner flue section...

Страница 10: ...ny subsequent chimney sections following the stabilizer when installing Ensure each subse quent chimney section is securely attached by testing as noted in Step 4 Step 6 Select the proper Security roof flash ing based on pitch of roof Use chart below for selection Roof Pitch Model Flat to 6 12 F8F6 6 12 to 12 12 F8F12 Next slideroofflashingoverextendedchimney sectionthatpreviouslyhasbeeninstalleda...

Страница 11: ... point is established on the roof surface 10 horizontally from the chimney edge The top of the chimney must be at least 2 above this reference point In all cases the chimney cannot be less then 3 above the roof at the edge of the chimney The 2 in 10 rule is necessary in the interest of safety but does not ensure smoke free opera tion Trees buildings adjoining roof lines adverse wind conditions etc...

Страница 12: ...s FTF8 VERTICAL ELEVATION CHART Step 3 Use Elevation Chart as job estimator only Addnecessaryfirestopspacersandstabi lizers as required Firestop spacers must be used as shown in Figures 23 and 24 and stabi lizers as shown in Figure 29 Height Of Number Of FTF8 Chimney Only Chimney Lengths Inches Feet Inches 12 18 36 48 Height Of Number Of FTF8 Chimney Only Chimney Lengths Inches Feet Inches 12 18 3...

Страница 13: ... 35 69 1 0 0 1 0 1 37 73 1 0 0 2 1 0 38 75 1 0 0 0 2 0 39 77 1 0 2 1 1 0 41 80 1 0 1 4 0 0 43 83 1 0 1 0 2 0 44 85 1 0 0 0 1 1 45 87 1 0 0 3 1 0 46 89 1 0 0 1 2 0 48 91 1 0 2 0 2 0 49 94 1 0 1 0 1 1 50 95 1 0 0 0 0 2 51 97 1 0 1 1 2 0 54 103 1 0 0 2 2 0 55 104 1 0 1 0 0 2 56 106 1 0 2 1 2 0 58 109 1 0 0 1 0 2 61 116 1 1 1 0 3 0 64 121 1 1 0 1 3 0 67 124 1 1 2 0 3 0 68 128 1 1 0 0 1 2 70 130 1 1 1 ...

Страница 14: ...urn elbow to ensure locking joint has firmly engaged Step 5 Secure support straps to framing members by nailing under tension in sheer Figure 42 Figure 39 Figure 40 Figure 41 Chimney Section Joints No 8 x 1 2 SMS S c r e w s R e q u i r e d A t E v e r y J o i n t P a s t 6 N o S c r e w s R e q u i r e d I n J o i n t s F o r F i r s t 6 o f O f f s e t 4 6 Underside Of Chimney Chimney Section S ...

Страница 15: ...MBINGCONNECTIONSSHOULD ONLY BE PERFORMED BY A QUALIFIED LI CENSEDPLUMBER MAINGASSUPPLYMUST BE OFF WHEN PLUMBING GAS LINE TO FIRE PLACE OR PERFORMING SERVICE If you re installing a gas line connect it before the fireplace is framed and enclosed in the finished wall The gas knockout is determined by the indentation located at the bottom and slightly off center in the side refractories THE KNOCKOUT I...

Страница 16: ...OF GLASS DOORS COLD CLIMATE INSULATION If you live in a cold climate it is especially important to seal all cracks around the fire place opening with noncombustible material and wherever cold air could enter the room Surrounding materials must be caulked where it meets the black metal facing of the fireplace to avoid cold air intrusion Use noncombus tible caulking material only on fireplace facing...

Страница 17: ... 16 B 33 C 8 D 49 A B D C C R value 1 r x thickness of material used k Alternative Hearth Extension and Wall Shield Materials Listed Values Min Thick Material k r TL Millboard 1 28 0 78 1 Alternative Values Min Thick Materials k r TM Wonderboard 1 92 0 56 1 Common brick 5 00 0 20 3 Cement mortar 5 00 0 20 3 Ceramic tile 12 5 0 08 9 Marble 11 0 0 09 8 Micore CV230 0 43 2 33 U S Gypsum Ceraform 126 ...

Страница 18: ...all 8 45 Combustible Materials Allowed In Shaded Area Safe Zone 8 1 Min Distance To Protected Side Wall Fireplace A marble slab set in mortar covers the brick R for the marble and mortar becomes R M r x TM 0 09 x 068 R M r x TM 0 20 x 10 The sum of all R values is 70 10 068 10 968 This would be an acceptable combination of material for the hearth extension since the total calculated R value of the...

Страница 19: ...ation Square 63L51 FTF8 CT2 Forced Air Blower Kits Single Speed 80L84 FBK 100 Variable Speed 80L85 FBK 200 FBK 200 Models Only INSTALLATION COMPONENTS Chase Termination 96L20 FTF8 CTT Chase Termination 96L22 FTF8 ATT Storm Collar 63L59 FSC Locking Band 63L60 FLB Stabilizer 63L25 FTF8 S4 Firestop Spacer 30 63L32 F8FS30 2 Offset Return Package 30 63L22 FTF8 ES30 Attic Shield Assembly 63L67 FTF8 FSAS...

Страница 20: ...9M REV D 11 2003 The manufacturer reserves the right to make changes at any time without notice in design materials specifications prices and also to discontinue colors styles and products Consult your local distributor for fireplace code information 1110 West Taft Avenue Orange CA 92865 ...

Отзывы: