Superior CR-3835R Скачать руководство пользователя страница 18

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

18

These fireplaces may sit directly on a com-
bustible surface. A 2" air space is required
between combustible framing and the chim-
ney. A 1" air space is required between com-
bustible framing and fireplace outer wrapper.
Combustible mantels and trim may be in-
stalled 12" above the fireplace opening as per
NFPA 211, Section 7-2.3.3. and 

Figure 42. If

a mantel is of a noncombustible material, it is
exempt from these requirements as long as it
does not interfere with the installation or
operation of glass doors.

Figure 43

Figure 44

Hearth Extensions and Wall Shields

A hearth extension must be installed with
all fireplaces. It is to protect the combustible
floor in front of the fireplace from both radiant
heat and sparks. The hearth extension must
extend 8" beyond both sides of the fireplace
opening and 16" beyond the front (

Figure 43 ).

Use a hearth extension constructed of a durable
noncombustible material having an equal or
greater insulating value of k = 1.28BTU/IN FT

2

HR 

°

F or a thermal resistance that equals or

exceeds r = .78 HR 

°

F FT

2

 IN/BTU.  With these

values, determine the minimum thickness/ma-
terial required using the formula and the Table
on page 17.

Note:

 Any noncombustible material whose k

value is less than 1.28 or whose r value is more
than .78 is acceptable.

Figure 42

Typical Installation

*Both Of These Dimensions Must Be At Least 18”
When An Unvented Gas Log Set Rated At 26,000
BTU Or Higher Is Used.  (Maximum 40,000 BTU)

12"*
Min.

8 3/8"*

Fireplace
Opening

Combustible
Mantel
and Trim

12"

Max.

1 1/2"

Finished
Wall

False
Header

Header

Spacer

If the fireplace is installed on a combustible
floor, use the metal safety strips (provided) on
the floor extending half under the fireplace and
half under the hearth extension (refer to 

Figures

6 and 7 ).

A wall shield is required where a continuous
perpendicular side wall is within 12" of the
fireplace opening, (

Figure 44 ). Use a 24" W x

30" H wall shield constructed of millboard or a
durable, noncombustible material having an
equal or greater insulating value than K = .54BTU/
IN FT

2

 HR 

°

F.  At no time may a perpendicular

side wall be closer than 8".

If fireplace is installed diagonally across a 90

°

corner; no wall shields are required.

Glass Doors

If glass doors are to be installed on these
fireplaces, refer to specific installation instruc-
tions packed with the glass doors. Use only the
doors that are listed for use with these fire-
places. Use of other non-listed glass door on
these fireplaces may constitute a potential fire
hazard and is not recommended.

CAUTION: CERTAIN GLASS DOORS OVERLAP
THE BLACK METAL FACING OF THE FIRE-
PLACE. IF THE FIREPLACE HAS BEEN FACED
WITH NONCOMBUSTIBLE MATERIALS, THERE
MIGHT NOT BE SUFFICIENT CLEARANCE TO
INSTALL THE GLASS DOORS OF YOUR
CHOICE. ENSURE ADEQUATE CLEARANCE IS
MAINTAINED AT ALL TIMES SO AS NOT TO
INTERFERE WITH THE INSTALLATION AND
OPERATION OF GLASS DOORS.

COLD CLIMATE INSULATION

If you live in a cold climate, it is especially
important to seal all cracks around the fire-
place opening with noncombustible material
and wherever cold air could enter the room.
Surrounding materials must be caulked where
it meets the black metal facing of the fireplace
to avoid cold air intrusion. Use noncombus-
tible caulking material only on fireplace facing
to seal. Also, the outside air inlet duct should
be wrapped with noncombustible insulation to
minimize the formation of condensation. Do
not place insulation materials on top of fire-
place or against chimney sections.

Note:

 A 2" air space must be preserved for all

combustible materials extending for any con-
tinuous length adjacent to the chimney.

It is especially important to insulate between
the studs of an outside chase cavity and under
the floor if the floor is above ground level. Do
not place insulation directly against the fire-
place or chimney system.

FIREPLACE FINISHES
Mantels and Trim

It is sometimes best to frame your fireplace
after it is positioned and the chimney is in-
stalled. Frame enclosure for chimney and fire-
place with 2 x 4’s (or heavier) lumber.

Note:

 The header may rest on the two (2) metal

top spacers on top of the unit but the header
must not be notched to fit around the spacers.

8"

(203mm)

20"

(508mm)

12"

(305mm)

Min.

Outside Corner

Metal Safety Strip

20"

(508mm)

D

B

A

C

E

20"

(508mm)

Inside Corner

If Less Than 12"
(305mm) Wall
Shield Required

20"

(508mm)

40"

(1016mm)

Wall

Shield

40"

(1016mm)

Metal Safety

Strip

Wall Shield

Not Required

On This Wall

Hearth Extension Dimensions

A

20" (508 mm)

B

38" (965 mm)

C

8" (203 mm)

D

20" (508 mm)

E

12" (305 mm)

Содержание CR-3835R

Страница 1: ...ents under any circumstances Any modification or alteration of the fireplace system including but not limited to the fireplace chimney components and accessories may void the warranty listings and app...

Страница 2: ...l provided with the fireplace TOOLS AND BUILDING SUPPLIES NORMALLY REQUIRED Tools should Include Phillips screwdriver Hammer Saw and or sabersaw Level Measuring tape Plumb line Electric drill and bits...

Страница 3: ...s such as the BOCA Basic National Codes the Standard Me chanicalCodeandtheUniformBuildingCodes When complete these fireplace systems con sists of five basic sub systems 1 The Fireplace 2 The Chimney a...

Страница 4: ...r Chase Opening Optional Insulation In Outside Walls Of Chase Solid Continuous Surface Outside Base Insulation Thermal Barrier 8 Level Note Do not insulate the chase cavity with blown or fill type ins...

Страница 5: ...h installation is unique however and might require a different sequence 1 Position firebox prior to framing or into prepared framing 2 Install the chimney system 3 Connect house wiring to the fireplac...

Страница 6: ...02 mm Class 0 air duct provided to the collar on the chimney collarenclosurewiththescrewsprovidedinthe hardware kit IMPORTANT UNDER NO CIRCUMSTANCES CAN THE FIREPLACE TOP SPACERS FIGURE 6 BE REMOVED O...

Страница 7: ...mm 432 mm 483 mm 483 mm 6 12 16 19 17 19 19 21 419 mm 483 mm 432 mm 483 mm 483 mm 533 mm 12 12 16 23 17 24 19 26 419mm 597mm 432mm 610 mm 483mm 660 mm Perpendicular to roof ridge A B Ceiling Framing...

Страница 8: ...EY AIR SPACE TO COMBUSTIBLE FRAMING MEMBERS THROUGHOUT VERTI CAL OR OFFSET CHIMNEY INSTALLATION SEE NOTE A minimum 2 51 mm air space must be reserved for all combustible materials ex tending for any c...

Страница 9: ...And Room Above 10 Max Room Above 2 Min Air Space 2 Min Air Space Figure 24 Outer pipe section installs in just the opposite way the lanced end goes down and each new section goes OVER the outside of...

Страница 10: ...Note Do not caulk or seal the ventilating open ings Step 7 Secure flashing by nailing along the perimeter into roof using 8d nails If shingled roof slide upper end and sides of roof flashing under shi...

Страница 11: ...smoke free opera tion Trees buildings adjoining roof lines ad verse wind conditions etc may require a taller chimney should the fireplace not draft properly see Figure 33 MULTIPLE TERMINATIONS If more...

Страница 12: ...ng Do not puncture the inner flue Maximum offset of chimney system is 30 Two offsets must not be assembled to form a 60 offset However two sets of offset and return elbows may be used on a single flue...

Страница 13: ...imney Components Chimney Only Inches Feet Inches 12 18 24 36 48 S4 Meters 247 20 7 0 1 0 0 5 6 29 253 21 1 0 0 1 0 5 6 44 257 21 5 1 1 0 0 5 6 55 263 21 11 1 0 1 0 5 6 70 269 22 5 0 1 1 0 5 6 85 275 2...

Страница 14: ...hes Feet Inches 12 18 36 MM M 461 38 5 0 1 13 11722 11 72 465 38 9 2 0 13 11824 11 82 471 39 3 1 1 13 11976 11 98 479 39 11 0 0 14 12179 12 18 489 40 9 1 0 14 12433 12 43 495 41 3 0 1 14 12586 12 59 4...

Страница 15: ...1 1073 2064 44 85 1 1 0 1 1 1 0 1124 2159 45 86 1 1 0 0 1 0 1 1149 2197 47 90 1 1 0 0 2 1 0 1200 2286 48 91 1 1 0 0 0 2 0 1226 2330 49 93 1 1 0 2 1 1 0 1251 2381 51 97 1 1 0 1 4 0 0 1308 2470 53 100 1...

Страница 16: ...59 1 0 0 1 1 743 1505 31 63 1 0 2 0 1 794 1600 32 65 1 0 4 1 0 826 1651 34 68 1 0 1 1 1 870 1734 36 71 1 0 3 0 1 921 1822 37 73 1 0 0 2 1 946 1861 38 75 1 0 0 0 2 972 1905 39 77 1 0 2 1 1 997 1956 41...

Страница 17: ...pitch of the roof Offset Elbow Assembly Offset elbows install the same as chimney sections First snap the inner section INTO the preceding inner section of flue Check connec tion by pulling up slightl...

Страница 18: ...across a 90 corner no wall shields are required Glass Doors If glass doors are to be installed on these fireplaces refer to specific installation instruc tions packed with the glass doors Use only the...

Страница 19: ...Thick Materials k r TM Wonderboard 1 92 0 56 1 Common brick 5 00 0 20 4 Cement mortar 5 00 0 20 4 Ceramic tile 12 5 0 08 11 Marble 11 0 0 09 10 Micore CV230 0 43 2 33 U S Gypsum Ceraform 126 0 27 3 7...

Страница 20: ...kept within the shaded areas illustrated in Figure 46 Model Part Number Weight CR 3835R P N 015014 210 lbs CR 3835L P N 015013 210 lbs 63L30 F8FS30 63L32 F8FS30 2 Firestop Spacer 30 63L37 F10FS30 2 6...

Страница 21: ...Outside Combustion Air Kits with duct 81L87 FOAK without duct 81L88 FOAK LD 63L25 FTF8 S4 Stabilizer 63L26 FTF10 S4 Chimney Pack Conventional 63L70 FTF8 CP7 Contains 3 FTF8 36 1 F8FS 1 F8F6 1 FTF8 CT...

Страница 22: ...NOTE DIAGRAMS ILLUSTRATIONS NOT TO SCALE 22...

Страница 23: ...NOTE DIAGRAMS ILLUSTRATIONS NOT TO SCALE 23...

Страница 24: ...700 024M REV N C 05 2004 1110 West Taft Avenue Orange CA 92865 The manufacturer reserves the right to make changes at any time without notice in design materials specifications prices and also to disc...

Отзывы: