OPTIONAL OUTSIDE AIR KIT (MODEL AK4/AK4F)

The installation of an outside air kit should be performed during the rough 

framing of the fireplace due to the nature of it's location. Outside combus-

tion air is accessed through a vented crawl space (AK4F) or through a 

sidewall (AK4). See page 13 for instructions of operating air kit.

 CAUTION: Combustion air inlet ducts shall not 

terminate in attic space.

The maximum height for the air vent can not exceed 

3 feet below the flue gas outlet of the termination.

HEARTH EXTENSION

A hearth extension projecting a minimum of 16" in front of and a 

minimum of 8" beyond each side of the fireplace opening is required 

to protect combustible floor construction in front of the fireplace. 

Fabricate a hearth extension using a material which meets the fol-

lowing specifications: a layer of noncombustible, inorganic material 

having a thermal conductivity of k=0.84 BTU IN/FT, HR. F (or less) at 

1" thick. For example, if the material selected has a k factor of 0.25, 

such as glass fiber, the following formula would apply:
 

0.25 x 1.0" = 0.30" thickness required

 0.84
Thermal conductivity "k" of materials can be obtained from the manu-

facturer or supplier of the noncombustible material. If the hearth 

extension is to be covered, use noncombustible material such as 

tile, slate, brick, concrete, metal, glass, marble, stone, etc. Provide 

a means to prevent the hearth extension from shifting and seal gap 

between the fireplace frame and hearth extension with a noncom-

bustible material (see Figure 3). 

 WARNING: Hearth extension is to be installed only 

as shown in Figure 3.

Figure 3 - Hearth Extension

Seal Gap

Fireplace Front

Ember Protector

Fireplace Front Raised 

Hearth

Fireplace Front Elevated

Ember Protector

Ember Protector

Seal Gap

Hearth 

Extension

MANTELS

A mantel may be installed if desired (see Figure 4). Woodwork such 

as wood trims, mantels or any other combustible material project-

ing from the front face must not be placed within 12" of the fireplace 

opening and within 9" of top louver opening. Combustible materials 

above 12" and projecting more than 1

1

/

2

" from the fireplace must not 

be placed less than 12" from the top opening of the fireplace (NFPA 

211, Section - Clearance from Combustible Material).
Mantels or any other combustible material also may come up to the 

side edge of the black metal face of the fireplace if projection from  

front face falls within the limit shown in Figure 4.

Figure 4 - Mantel Clearances to Combustible Material

FIREBOX

SAFE ZONE

Top View of Fireplace

2" (51 mm) Max.

3.0"

(77 mm)

Min. to 

Perpendicular 

Side Wall 

12" (305 mm)

8" (204 mm)

33°

Combustible 

Material Must Not 

Overlap Front Face

FIREPLACE INSTALLATION  

Continued

12 

1

/

4

(312 mm)

Ref.

15" 

(381 mm)

Min.

12" 

(305 mm)

Min.

6" 

(153 mm)

Ref.

1

1

/

2

"

(38 mm) 

Max.

3" (77 mm)

Nom.

33°

Combustible 

Material

Safe Zone for 

Projection of 

Combustible 

Materials

Fireplace Opening

Upper 

Section of 

Fireplace

Содержание WRE3042WH

Страница 1: ...ADA The authority having jurisdiction such as the municipal building department fire department etc should be contacted before installation to determine the need to obtain a permit POUR LE CANADA L au...

Страница 2: ...Venting Installation 7 Optional Gas Line Installation 12 Operation and Maintenance Guidelines 13 Replacement Parts 14 Technical Service 14 Important Notices Canada 15 Parts 16 Accessories 18 Draft Sm...

Страница 3: ...canposeasignificanthazard IMPORTANT See appendix A page 21 for additional information regarding draft requirements smoking causes and troubleshooting WARNING BURNINGIMPROPERFUEL I E CHAR COAL CAN RESU...

Страница 4: ...1 1 2 39 mm 46 3 4 1188 mm 22 1 2 572 mm INNER DIA 12 3 8 315 mm 5 8 16 mm 36 915 mm 48 1220 mm OUTER DIA 15 381 mm 24 610 mm 8 204 mm 42 1067 mm 41 1042 mm 48 1067 mm 3 4 19 mm AIR SPACE BACK AND SI...

Страница 5: ...s or roof rafters will make installation easier 4 An outside air kit is available with this fireplace see Optional Outside Air Kit on page 7 MINIMUM CLEARANCE TO COMBUSTIBLES Ceiling 40 1016 mm minimu...

Страница 6: ...ss marble stone etc Provide a means to prevent the hearth extension from shifting and seal gap between the fireplace frame and hearth extension with a noncom bustible material see Figure 3 WARNING Hea...

Страница 7: ...he flue pipe section with the hemmed end up Press down on each pipe section until the lances securely engage the hem on the fireplace starter The wire will assure the proper spac ing between the inner...

Страница 8: ...ecurely nailed to rafters or joists see Figure 8 details A and B 3 Maximum length of pipe between supports return elbow or 12S 8DM is 6 of angle run Maximum of two 6 angle run sections per chimney sys...

Страница 9: ...uble wall pipe passes through a framed opening into an attic space the firestop must be placed into an attic floor as shown in Figure 11 NOTICE The installation of a firestop thimble FST30 or 38FST is...

Страница 10: ...st roof Replace as many shingles as needed to cover exposed area and flashing base Secure in position by nailing through shingles see Figure 13 DO NOT NAIL THROUGH FLASHING CONE Installing Flashing on...

Страница 11: ...of 10 feet see Figure 17 FINISHING FIREPLACE Combustible materials such as wallboard sheet rock drywall ply wood etc may make direct contact with sides and top around the fireplace face It is importan...

Страница 12: ...to wood framing to provide rigidity for threaded end 4 Repack insulation around gas line and into sleeve opening Seal any gaps between gas line and refractory knockout hole with refractory cement or c...

Страница 13: ...back from the doors and never allow flames to contact the glass WARNING FIREPLACES EQUIPPED WITH GLASS DOORS SHOULD BE OPERATED ONLY WITH DOORS FULLY OPENED OR DOORS FULLY CLOSED DOORS IF LEFT PARTLY...

Страница 14: ...through your IHP distributor or dealer Parts will be shipped at prevailing prices at time of order When ordering repair parts always give the following information 1 The model number of the fireplace...

Страница 15: ...all Pipe Snap Lock F0884 36 8HT 36 Section Hi Temp Double Wall Pipe Snap Lock F0885 48 8HT 48 Section Hi Temp Double Wall Pipe Snap Lock F0886 30E 8HT 30 Degree Hi Temp Offset and Return F0887 12S 8HT...

Страница 16: ...SuperiorFireplaces us com 127055 01_H 16 PARTS 9 24 16 31 25 16 4 30 32 19 12 23 20 28 17 8 1 5 21 2 18 11 14 3 13 22 10 6 35 29 7 33 34 26 27 15 MODEL CATALOG NO WRE3042WS F0453 WRE3042WH F0454...

Страница 17: ...r 1 16 J8013 Kit Screen Assembly 1 17 Firebox Top Assembly 1 18 J3980 Air Kit Door Assembly 1 19 Face Weldment 1 20 J4471 Air Deflector 1 21 Fireplace Top Insulation 1 22 J4052 Access Panel 1 23 J4513...

Страница 18: ...Her White S42 1 4 Refractory Rear Her White S42 1 5 Refractory Btm Rear White S42 1 6 Refractory Btm Frnt White S42 1 1 2 4 3 6 5 Stacked Refractory Shown ACCESSORIES REFRACTORY STAIN KITS Use the re...

Страница 19: ...ap Lock F0883 24 8HT 24 Section Hi Temp Double Wall Pipe Snap Lock F0884 36 8HT 36 Section Hi Temp Double Wall Pipe Snap Lock F0885 48 8HT 48 Section Hi Temp Double Wall Pipe Snap Lock 30 OFFSET AND R...

Страница 20: ...UVERS AND SLIP SECTION F0921 ETL 8DM Square Top with Slip Section F0893 ETL 8HT Hi Temp Large Pyramid Top with Slip Section MESH SQUARE TOP TERMINATION F0922 ETO 8DM Square Top with Mesh MESH SQUARE T...

Страница 21: ...electing the proper venting system for your installation American National Standards Institute ANSI NFPA 211 Standard for Chimneys Fireplaces Vents and Solid Fuel Burning Appli ances See Draft Section...

Страница 22: ...ance The best location to install your appliance is determined by consid ering the location of windows doors and the traffic flow in the room where the appliance is located allowing space in front of...

Страница 23: ...be subject to normal use with approved fuels listed in the Operation Manual provided with the product This includes burning such fireplace fuels as wood and natural or propane gas Fuel products with a...

Страница 24: ...7055 01 Innovative Hearth Products reserves the right to make changes at any time without notice in design materials specifications prices and also to discontinue colors styles and products Consult yo...

Отзывы: