Superiorfireplaces.US.com

127029-01_C

8

AIR FOR COMBUSTION AND VENTILATION  

continued

The space in the example is a confined space because the actual Btu/

Hr used is more than the maximum Btu/Hr the space can support. 

You must provide additional fresh air. Your options are as follows:
A.  Rework worksheet, adding the space of an adjoining room. If the 

extra space provides an unconfined space, remove door to adjoining 

room or add ventilation grills between rooms. See Ventilation Air 

From Inside Building.

B.  Vent room directly to the outdoors. See Ventilation Air From 

Outdoors.

C.  Install a lower Btu/Hr fireplace, if lower Btu/Hr size makes room 

unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space 

can support, the space is an unconfined space. You will need no ad-

ditional fresh air ventilation.

 WARNING: If the area in which the heater may be 

operated does not meet the required volume for indoor 

combustion air, combustion and ventilation air shall 

be provided by one of the methods described in the 

National Fuel Gas Code, ANSI Z223.1/NFPA 54, the 

International Fuel Gas Code, or applicable local codes.

VENTILATION AIR
Ventilation Air From Inside Building

This fresh air would come from an adjoining unconfined space. When 

ventilating to an adjoining unconfined space, you must provide two 

permanent openings: one within 12" of the ceiling and one within 12" 

of the floor on the wall connecting the two spaces (see options 1 and 

2, Figure 4). You can also remove door into adjoining room (see option 

3, Figure 4 ). Follow the National Fuel Gas Code, ANSI Z223.1/NFPA 

54, Air for Combustion and Ventilation for required size of ventilation 

grills or ducts.

Ventilation Air From Outdoors

Provide extra fresh air by using ventilation grills or ducts. You must 

provide two permanent openings: one within 12" of the ceiling and 

one within 12" of the floor. Connect these items directly to the out-

doors or spaces open to the outdoors. These spaces include attics 

and crawl spaces. Follow the National Fuel Gas Code, ANSI Z223.1/

NFPA 54, Air for Combustion and Ventilation for required size of 

ventilation grills or ducts.

IMPORTANT: Do not provide openings for inlet or outlet air 

into attic if attic has a thermostat-controlled power vent. 

Heated air entering the attic will activate the power vent.

Figure 4 - Ventilation Air from Inside Building

Or

Remove

Door into
Adjoining

Room,
Option

3

Ventilation Grills 

Into Adjoining Room,

Option 2

Ventilation

Grills Into

Adjoining 

Room,

Option 1

12"

12"

Figure 5 - Ventilation Air from Outdoors

Outlet

Air

Ventilated

Attic 

Outlet

Air

Inlet

Air

Inlet Air

Ventilated 

Crawl Space

To 

Crawl

Space

To Attic

Содержание VRE4536RH

Страница 1: ...plier SAVE THIS BOOK This book is valuable In addition to instructing you on how to install and maintain your appliance it also contains information that will enable you to obtain replacement parts or...

Страница 2: ...Anychangetothisfireboxoritscontrols can be dangerous WARNING Do not allow fans to blow directly into the firebox Avoid any drafts that alter burner flame patterns Ceiling fans can create drafts that...

Страница 3: ...inexpensive State of Massachusetts The installation must be made by a licensed plumber or gas fitter in the Commonwealth of Massachusetts Sellers of unvented propane or natural gas fired supplemental...

Страница 4: ...C 4 PRODUCT SPECIFICATIONS 36 MODELS Figure 1 36 Models VRE4536RS VRE4536WS VRE4536RH and VRE4536WH 20 1 4 Ref 1 1 4 22 1 2 19 36 HEARTH 29 30 1 2 30 36 54 1 2 11 1 8 45 1 8 36 3 8 35 1 4 9 1 2 3 3 8...

Страница 5: ...RODUCT SPECIFICATIONS continued 42 MODELS Figure 2 42 Models VRE4542RS VRE4542WS VRE4542RH and VRE4542WH 42 HEARTH 21 3 4 8 3 4 3 3 8 9 1 2 26 3 8 41 3 8 4 7 8 1 1 4 3 3 4 32 3 8 36 3 8 11 1 8 7 7 8 5...

Страница 6: ...6 Figure 3 50 Models VRE4550RS VRE4550WS VRE4550RH and VRE4550WH 21 3 4 8 3 4 9 1 2 3 3 8 13 50 50 7 30 34 3 8 38 3 8 4 7 8 49 3 8 36 3 8 59 1 8 54 1 2 11 1 8 3 3 4 32 3 8 7 7 8 23 Ref 50 HEARTH PRODU...

Страница 7: ...ia above you must provide ad ditional fresh air See Ventilation Air From Outdoors page 8 If your home does not meet all of the three criteria above proceed to Determining Fresh Air Flow For Firebox Lo...

Страница 8: ...ined space When ventilating to an adjoining unconfined space you must provide two permanent openings one within 12 of the ceiling and one within 12 of the floor on the wall connecting the two spaces s...

Страница 9: ...tom of your firebox except where standoff spacers are integrally attached If standoff spacers are attached to your firebox these spacers can be placed directly against wall or framing materials Use th...

Страница 10: ...al product standard Fol low all minimum clearances shown in this manual NOTICE Ifyourinstallationdoesnotmeettheminimum clearances shown you must do one of the following raise the mantel to an acceptab...

Страница 11: ...es This firebox may be installed using a cabinet mantel against a wall in your home The firebox and cabinet mantel can be installed directly on the floor Mantels may be available from your retailer or...

Страница 12: ...he right and left refractory panels with the gas line knock outs orientated down toward the bottom refractory Align the left and right panels with the rear panel so the grout lines line up 5 Install t...

Страница 13: ...rnace cement Install the gas appliance or cap off gas line if desired A gas line or gas log lighter may be installed for the purpose of installing a vent free decorative gas appliance incorporating an...

Страница 14: ...0 21 20 1 19 5 14 15 16 13 12 11 9 7 6 8 17 2 12 18 4 PARTS MODEL NO CATALOG NO VRE4536RS F0473 VRE4536WS F0474 VRE4536RH F0475 VRE4536WH F0476 VRE4542RS F0477 VRE4542WS F0478 VRE4542RH F0479 VRE4542W...

Страница 15: ...ULATION 1 8 RP110454 03 TOP FIREPLACE 36 1 RP110454 02 TOP FIREPLACE 42 1 RP110454 01 TOP FIREPLACE 50 1 9 J6997 SPACER FIREPLACE TOP 42MC 4 10 FIREPLACE SURROUND ASSEMBLY 1 11 J4362 SPACER CLEARANCE...

Страница 16: ...safety hazards 1 2 5 3 4 6 6 MODEL NO CATALOG NO VRE4536RS F0473 VRE4536WS F0474 VRE4536RH F0475 VRE4536WH F0476 VRE4542RS F0477 VRE4542WS F0478 VRE4542RH F0479 VRE4542WH F0480 VRE4550RS F0481 VRE4550...

Страница 17: ...K RED 1 J6625 REFRACTORY REAR 50 HER RED 1 5 J5109 ASSY ASH REFRACTORY 36 RED 1 J4584 REFRACTORY ASH 42 STK RED 1 J4594 REFRACTORY ASH 50 STK RED 1 6 J4466 RETAINER ASSY REF CORNER 2 KEY NO CATALOG NO...

Страница 18: ...r or dealer Parts will be shipped at prevailing prices at time of order CAT NO MODEL DESCRIPTION OPTIONAL AIR KITS F1091 AK4F Outside Air Kit For Floor Installation F1094 AK4 Outside Air Kit For Sidew...

Страница 19: ...urn either natural or propane gas only Burning conventional fuels such as wood coal or any other solid fuel will cause damage to the Product will produce excessive temperatures and could result in a f...

Страница 20: ...ealer name P127029 01 Innovative Hearth Products reserves the right to make changes at any time without notice in design materials specifications prices and also to discontinue colors styles and produ...

Отзывы: