LED Emergency Driver

Important: Read all instructions prior to installation.

BLD-YT08D-XXX Series

4400 Earth City Expy, St. Louis, MO 63045          

866-590-3533            superbrightleds.com

Rev Date: V1.0 04/29/2021

5

yr

User Manual

CAUTION: DO NOT JOIN BATTERY CONNECTOR OR ACTIVE BATTERY SWITCH UNTIL INSTALLATION  
IS COMPLETE AND AC POWER IS SUPPLIED TO THE EMERGENCY DRIVER.

1. Disconnect AC power from the LED luminaire/driver.
2. Mount the emergency LED driver by the mounting tabs using appropriate screws (not provided).  

Note: If the application requires the emergency LED driver to be mounted on top of the luminaire,  

flexible metal conduit should be used over wiring. 

3. Mount the supplied illuminated test switch in a location that is visible and accessible by maintenance  

personnel.  
Note: The switch mounts through a hole which will need to be added to the luminaire or nearby structure. 

4. Wire the test switch according to the wiring diagram. If wired correctly, the test switch indicator light  

should be on when AC power is supplied to the fixture, and the battery switch would be on indicating 

 

that the emergency inverter battery is charging.

5. Connect the emergency driver to the AC driver and LED load according to wiring diagram. Make sure  

all connections are in accordance with the National Electrical Code and any local regulations. 

6. After installation is complete, supply AC power to the emergency driver. At this point, power should  

be connected to both the AC driver and the emergency driver, and the charging indicator light should  
be illuminated indicating the battery is charging.