Adjust zero-point
1
Zero-point
adjustment
Head-separated
DP4
Digital Display
LED Bar Display
DP4
786
PRECAUTIONS FOR PROPER USE
Measurement
4
Pressure value
setting
2
Initial setting
Set ‘Display’, ‘Output
mode’, and ‘Unit’
3
Supplementary
setting
Set ‘NO / NC’, ‘Display
cycle’, ‘Response time’,
and ‘Pressure range’
Enter Set Value 1 (P-1),
Set Value 2 (P-2), Set
Value 3 (P-3)
Commence
measurement on
completion of setting
•
The displayed pressure when the pressure port is left
open is adjusted to zero.
•
The sensor will automatically enter the sensing
mode when power is supplied.
•
Let the pressure port be at atmospheric
pressure (i.e., no applied pressure condition),
and press, simultaneously, the UP and
DOWN keys continuously.
•
is displayed and, when the fingers are
released, zero-point adjustment is completed
and the sensor returns to the sensing mode.
DP
4
–101.3kPa
DOWN
MODE
UP
•
Pressure ‘Unit’, ‘Display’, and ‘Output mode’ of the outputs
are set.
•
In the sensing mode, press key while
pressing UP key.
•
Initial setting is displayed.
•
If sensor is being used for the first time,
is displayed.
•
The settable digit blinks.
•
The settable digit changes when UP key is
pressed and the setting is changed when
DOWN key is pressed.
MODE
DP
4
–101.3kPa
DOWN
MODE
UP
•
‘NO / NC’, ‘Display cycle’, ‘Response time’ and ‘Pressure range’ are set.
•
In the sensing mode, press both DOWN key
and key simultaneously.
•
The setting item and the setting condition are
displayed alternately.
•
The setting item changes when UP key is
pressed.
•
The set condition of each item changes when
DOWN key is pressed.
MODE
DP
4
–101.3kPa
DOWN
MODE
UP
•
Sets output to Set Value 1 to 3 (P-1 to P-3).
•
Press the key in sensing mode.
•
The mode changes in the order Set Value 1
(P-1) setting mode, Set Value 2 (P-2) setting
mode and Set Value 3 (P-3) setting mode each
time the key is pressed.
MODE
MODE
•
If key-protect has been set, make sure to release key-protect before operating the keys.
(Please refer to ‘Key-protect function’ on
•
Set Value 1 (P-1) and Set Value 2 (P-2) can be made common for all the output modes.
•
The setting of Set Value 2 (P-2) with respect to Set Value 1 (P-1) can only be towards the high pressure side in case of
the positive pressure type sensor and only towards the high vacuum side in case of the vacuum pressure type sensor.
•
The conditions which are set are stored in an EEPROM. Kindly note that the EEPROM has a life span and its guaranteed
life is 100,000 write operation cycles.
Setting
Setting procedure
1
Zero-point adjustment
3
Supplementary setting
4
Pressure value setting
2
Initial setting
:
:
:
:
Change with UP key
3rd digit
2nd digit
1st digit
Unit
Output mode
Display
: kgf/cm
2
bar
psi
mmHg
inHg
Positive and compound
pressure types
Vacuum
pressure type
: kPa or
MPa
: Hysteresis
mode
: Window
comparator
mode
: Forced output
mode
: Automatic
sensitivity
setting mode
:
:
Digital
display
Analog
bar
display
DOWN
DOWN
DOWN
UP
UP
: 256 ms
: 512 ms
: 1,024 ms
: 2 ms
: 16 ms
: 128 ms
: 512 ms
: 1 MPa
: 1,000 kPa
DOWN
DOWN
DOWN
DOWN
NO / NC selection
Display cycle
selection
Pressure range
setting (Note)
Response time
selection
UP
UP
UP
Change with UP key
: NO
: NC
Normally
open
(
)
Normally
closed
(
)
Note: Displayable only for positive pressure type DP4-52(P).
DP
4
–101.3kPa
DOWN
MODE
UP
Press key
MODE
Press key
MODE
Press key
MODE
Press key
MODE
Sensing mode
Set Value 3 (P-3) setting mode (Note)
•
Use the UP key and DOWN key
to check Set Value 3 (P-3).
Set Value 2 (P-2) setting mode
•
Use the UP key and DOWN key
to change Set Value 2 (P-2).
Set Value 1 (P-1) setting mode
•
Use the UP key and DOWN key
to change Set Value 1 (P-1).
•
Indicates sensing pressure.
Note: Set Value 3 is only displayed when automatic sensitivity setting mode
has been set. Furthermore, if Set Value 3 is between Set Value 1 and
Set Value 2, the UP key and DOWN key can be used to correct it.