This product is not a safety sensor. Its use is not
intended or designed to protect life and prevent body
injury or property damage from dangerous parts of
machinery. It is a normal pressure detection sensor.
䢇
In case this sensor is used within Japan, SI unit most
be used since use of pressure units in Japan is
restricted to SI units.
Gauge pressure
0 to
ⳮ
101.3kPa
0 to 100.0kPa
0 to 1.000MPa
5.1 to
ⳮ
101.3kPa
ⳮ
5.0 to 100.0kPa
ⳮ
0.050 to 1.000MPa
490kPa
1.47MPa
Non-corrosive gas
kgf/cm
2
, bar, psi, mmHg, inHg
kgf/cm
2
, bar, psi
12 to 24V DC % Ripple P-P 10% or less
50mA or less
<
Asian, North American (Standard NPN output
•
Flat
•
IP67 types)
>
NPN open-collector transistor
•
Maximum sink current: 100mA
•
Applied voltage: 30V DC or less (between comparative output and 0V)
•
Residual voltage: 1V or less (at 100mA sink current)
0.4V or less (at 16mA sink current)
Equipped with 4 types of modes: hysteresis mode, window comparator mode, dual output mode, automatic sensitivity
setting mode (selectable by key operation)
1 digit (However, variable in hysteresis mode and 2 digits when using psi unit)
Within
Ⳳ
0.2% F.S.
Ⳳ
1 digit
2.5ms or less
Incorporated
Output voltage: 1 to 5V (over rated pressure range)
Zero-point: within 1V
Ⳳ
5% F.S.
Span: within 4V
Ⳳ
5% F.S.
Linearity: within
Ⳳ
1% F.S.
Output impedance: 1k
Ω
approx.
3
1
/
2
digit red LED display (Sampling rate: 4 times/sec. approx.)
5.1 to
ⳮ
101.3kPa
ⳮ
5.0 to 100.0kPa
ⳮ
0.050 to 1.000MPa
LED bar display in steps of 10% F.S. approx.
Orange LED (lights up when Comparative Output 1 is ON)
Green LED (lights up when Comparative Output 2 is ON)
Standard
•
Flat
•
Light weight types: IP40 (IEC), IP67 type: IP67 (IEC)
ⳮ
10 to
Ⳮ
50
⬚
C (No dew condensation or icing allowed), Storage:
ⳮ
10 to
Ⳮ
60
⬚
C
35 to 85% RH, Storage: 35 to 85% RH
Over ambient temperature range
ⳮ
10 to
Ⳮ
50
⬚
C: within
Ⳳ
1% F.S. of detected pressure at 20
⬚
C
Standard
•
Flat
•
IP67 types: Rc (PT)
1
/
8
female thread, Light weight type: M5 female thread
Standard type: NPTF
1
/
8
female thread, Flat
•
IP67 types: NPT
1
1
/
8
female thread
Flat
•
IP67 types: G (PF)
1
/
8
female thread
Front case: ABS, Rear case: PPS (glass fiber reinforced), Display surface: Acrylic
Pressure port attachment: Die-cast zinc alloy [Light weight type: POM (glass fiber reinforced), pressure port is brass (nickel plated)]
Front cover (IP67 type only): Polycarbonate
0.15mm
2
5-core oil resistant cabtyre cable, 2m long (IP67 type: 5m long)
Extension up to total 100m is possible with 0.3mm
2
, or more, cable.
Standard type: 95g approx., Flat type: 120g approx., IP67 type: 370g approx., Light weight type: 70g approx.
Hexagon-socket-head plug for pressure port: 1 No. (Standard type only), Pressure unit label: 1 No.
5
1
Pressure
Output voltage (V)
High pressure
(Positive pressure type)
High vacuum
(Vacuum pressure type)
INSTRUCTION MANUAL
LED Display
•
Digital Pressure Sensor
DP2 Series
For use outside Japan
Thank you very much for using SUNX sensors. Please read
this Instruction Manual carefully and thoroughly for the
correct and optimum use of this sensor. Kindly keep this
manual in a convenient place for quick reference.
1
SPECIFICATIONS
Type of pressure
Rated pressure range
Set pressure range
Pressure withstandability
Applicable fluid
Selectable units
Supply voltage
Current consumption
Comparative outputs
Comparative Output 1
Comparative Output 2
Output modes
Hysteresis
Repeatability
Response time
Short-circuit protection
Analog voltage output
Display
Displayable pressure range
Analog bar display
Comparative Output 1
Comparative Output 2
Protection
Ambient temperature
Ambient humidity
Temperature characteristics
Asian
North American
European
Material
Cable
Cable extension
Weight
Accessories
Operation
indicators
Pressure
port
<
North American (Standard PNP output type), European
>
PNP open-collector transistor
•
Maximum source current: 100mA
•
Applied voltage: 30V DC or less (between comparative output and
Ⳮ
V)
•
Residual voltage: 2V or less (at 100mA source current)
Ⳮ
10
ⳮ
15
Type
Asian
North American (Note)
European
Vacuum pressure
Positive pressure
ⳮ
101kPa type
100kPa type
1MPa type
Standard Flat
IP67 Light weight Standard Flat
IP67 Standard Flat
IP67
DP2-20
DP2-60
DP2-80
DP2-21
DP2-41
DP2-61
DP2-22
DP2-42
DP2-62
DP2-20F(-P) DP2-40N DP2-60N
DP2-21F(-P) DP2-41N DP2-61N DP2-22F(-P) DP2-42N DP2-62N
DP2-40E
DP2-60E
DP2-41E
DP2-61E
DP2-42E
DP2-62E
Item
Model No.
2
CAUTIONS
DP2 series is designed for use with non-corrosive gas.
It cannot be used for liquid or corrosive gas.
䢇
Use within the rated pressure range.
䢇
Do not apply pressure exceeding the pressure
withstandability value. The diaphragm will get damaged and
correct operation shall not be maintained.
䢇
Make sure to carry out the wiring in the power supply off
condition.
䢇
Take care that wrong wiring will damage the sensor.
䢇
Verify that the supply voltage variation is within the rating.
䢇
If power is supplied from a commercial switching regulator,
ensure that the frame ground (F.G.) terminal of the power
supply is connected to an actual ground.
䢇
In case noise generating equipment (switching regulator,
inverter motor, etc.) is used in the vicinity of this sensor,
connect the frame ground (F.G.) terminal of the equipment to
an actual ground.
䢇
Do not use during the initial transient time (0.5 sec.) after the
power supply is switched on.
䢇
Do not run the wires together with high-voltage lines or power
lines or put them in the same raceway. This can cause mal-
function due to induction.
䢇
Cable extension, using 0.3mm
2
, or more, cable, should be
100m or less overall.
䢇
Avoid use of standard type, flat type and light weight type of
sensor in places where steam and dust is excessive.
䢇
Take care that the sensor does not come in direct contact
with water, oil, grease, or organic solvents, such as, thinner,
etc.
䢇
Do not insert wires, etc, into the pressure port. The
diaphragm will get damaged and correct operation shall not
be maintained.
䢇
Do not operate the keys with pointed or sharp objects.
3
SETTING OF PRESSURE LEAD
DIRECTION AND PIPING
Standard type
䢇
Setting of pressure lead direction
•
The pressure lead direc-
tion can be changed by
dismantling the pressure
port attachment and
changing the mounting
direction. The tightening
torque of the hexagon-
socket-head bolt (length
9mm or less) should be
0.29N
䡠
m or less.
Note: Please make sure to close any unused pressure port with
the hexagon-socket-head plug supplied as accessory.
Flat type, Light weight type
䢇
Setting of pressure lead direction
•
The pressure lead direction can be changed by dismantling
the pressure port attachment and changing the mounting
direction. The tightening torque of the hexagon-socket-head
bolt (length 9mm or less) should be 0.29N
䡠
m or less.
䢇
Piping
•
When connecting a cou-
pling to the pressure port,
hold the pressure port
attachment with a 16mm
(Light weight type: 10mm)
spanner and make sure that
the tightening torque is
9.8N
䡠
m or less (Light weight
type: 1.47N
䡠
m or less). Also, in order to prevent any leakage,
wind a sealing tape on the coupling when connecting.
Hexagon-socket-
head bolts
2-
"
4.3mm mounting holes
Pressure port
Pressure port attachment
Main body
16mm
(light weight type: 10mm)
spanner
Hexagon-
socket-
head bolts
Main body
Pressure port
attachment
Hexagon-socket-
head plug
Pressure
ports
䢇
Piping
•
When connecting a
hexagon-socket-head plug
or coupling to the pressure
port, hold the hexagonal
part of the pressure port
with a 12mm spanner and
make sure that the
tightening torque is 9.8N
䡠
m
or less. Also, in order to prevent any leakage, wind a sealing
tape on the coupling when connecting.
However, sealing tape is not required for North American type
using NPTF 1/8 coupling. (Sealing tape is required if NPT1/8
coupling is used.)
12mm spanner
IP67 type
䢇
Piping for pressure measurement inlet port
•
When connecting a coupling to the pressure measurement
inlet port, hold the pressure port attachment with a spanner
and make sure that the tightening torque is 9.8N
䡠
m or less.
Also, in order to prevent any leakage, wind a sealing tape on
the coupling when connecting.
䢇
Piping for atmospheric pressure inlet port
•
If there is a possibility of
water entering into the
sensor enclosure through
the atmospheric pressure
inlet port, connect a tube to
the atmospheric pressure
inlet port through a M5
coupling and extend the
other end of the tube to a
safe place. In this case,
ensure that this end of the
tube does not get clogged.
䢇
Fitting of front cover
•
Insert the bosses on the front cover into the guide holes at
the bottom of the pressure port attachment, and push in the
direction of the arrow to fit the hook.
When removing the front cover, release the hook first.
Atmospheric
pressure inlet port
Pressure measurement
inlet port
Tube
M5 coupling
Safe place,
where there is no
exposure to water
Guide holes
Hook
(
)
For use outside Japan
Note: Model Nos. of North American standard type having the suffix ‘-P’ are PNP output type.
MJE-DP2 No.0580-05