This product has been developed / produced for industrial use only.
Use within the rated pressure range.
Do not apply pressure exceeding the pressure withstandability value. The
diaphragm will get damaged and correct operation shall not be maintained.
Make sure that the power supply is off while wiring.
Take care that wrong wiring will damage the sensor.
Verify that the supply voltage variation is within the rating.
If power is supplied from a commercial switching regulator, ensure that the frame
ground (F.G.) terminal of the power supply is connected to an actual ground.
In case noise generating equipment (switching regulator, inverter motor, etc.) is used in the vicini-
ty of this sensor, connect the frame ground (F.G.) terminal of the equipment to an actual ground.
Do not use during the initial transient time (0.5 sec.) after the power supply is switched on.
Do not run the wires together with high-voltage lines or power lines or put
them in the same raceway. This can cause malfunction due to induction.
The specification may not be satisfied in a strong magnetic field.
Avoid dust, dirt, and steam.
Take care that the sensor does not come in direct contact with water,
oil, grease, or organic solvents, such as, thinner, etc.
Do not insert wires, etc, into the pressure port. The diaphragm will get
damaged and correct operation shall not be maintained.
Do not operate the keys with pointed or sharp objects.
Make sure that stress by forcible bend or pulling is not applied directly to the sensor cable joint.
CAUTIONS
16
Applied pressure range should be brought within
the rated pressure range.
Check the wiring when using the copy function.
Communication error
(Disconnection, faulty connection, etc.)
External input is carried out out-
side the rated pressure range.
Make sure that the system is configured of the
same models when using the copy function.
Communication error
(Incorrect model.)
Applied pressure range should be brought within
the rated pressure range.
The applied pressure exceeds the up-
per limit of the display pressure range.
The applied pressure exceeds the lower limit (re-
verse pressure) of the display pressure range.
Applied pressure at the pressure port should be brought to atmos-
pheric pressure and zero-point adjustment should be done again.
Pressure is applied during
zero-point adjustment.
Turn the power OFF and check the load.
The load is short-circuited caus-
ing an overcurrent to flow.
Error message
Corrective action
Cause
ERROR INDICATION
14
REMOTE ZERO-ADJUSTMENT FUNCTION
(HIGH-FUNCTION TYPE)
13
٨
The remote zero-adjustment function forcibly sets the pressure value to
'zero' when the external signal is input.
The setting value is not corrected when remote zero-adjustment is input.
Make sure that the pressure and setting value during remote zero-adjust-
ment do not exceed the settable pressure range.
Operation chart
Note: The setting values shift in the same manner during the EASY mode or the win-
dow comparator mode.
٨
The remote zero-adjustment value is cleared when the setting of the analog
voltage output / external input selection is changed or the power is turned ON
again, and normal operation based on the atmospheric pressure is resumed.
The remote zero-adjustment value can be confirmed when setting the
threshold value in RUN mode. Refer to the threshold value setting in
'
RUN MODE
'.
8
ON
OFF
10 20 30 40 50 60
0
10 20 30 40 50 60
0
Ԙ ԙ
10 20
Output
Applied pressure (kPa
)
Displayed value (kPa)
Set value (kPa)
During normal operation (each
comparative output set to N.O.)
Detected pressure at remote zero-adjustment input: 10kPa
Output mode: Hysteresis mode
During remote zero-adjustment input
(each comparative output set to N.O.)
Ԙ
10
ԙ
20
ON
OFF
10 20 30 40 50 60
0
-10
10 20 30 40 50
0
Output
Applied pressure (kPa
)
Displayed value (kPa)
Set value (kPa)
٨
The setting pressure range is wider than the rating pressure range so
that the auto-reference function can be handled.
If the corrected setting value exceeds the set pressure range when auto-reference input is
carried out, the setting value will be automatically corrected to within the set pressure range.
Thus, take care not to exceed the set pressure range.
Note: The setting values shift in the same manner during the EASY mode or the win-
dow comparator mode.
٨
٨
The detected pressure value at auto-reference input becomes 'zero'
when the setting of the analog voltage output / external input selection
function is changed or the power is turned ON again.
The auto-reference input value can be checked when setting the threshold value
in RUN mode. Refer to the threshold value setting in '
RUN MODE
' for details.
8
Operation chart
Settable range and set pressure range after correction
ON
OFF
10 20 30 40 50 60
0
10 20 30 40 50 60
0
Ԙ ԙ
10 20
Output
Applied pressure (kPa
)
Displayed value (kPa)
Set value (kPa)
During normal operation (each
comparative output set to N.O.)
Detected pressure at auto-reference input: 10kPa
Output mode: Hysteresis mode
During remote zero-adjustment input
(each comparative output set to N.O.)
ON
OFF
10 20 30 40 50 60
0
10 20 30 40 50 60
0
Output
Applied pressure (kPa
)
Displayed value (kPa)
Set value (kPa)
P(a)
10
Ԙ
20
ԙ
30
AUTO-REFERENCE FUNCTION
(ONLY HIGH-FUNCTION TYPE)
12
٨
٨
The auto-reference function corrects
the setting value using the detected
pressure value during auto-reference
input as the reference pressure.
Using the detected pressure value at
auto-reference input P(a) as a refer-
ence, the set value
Ԙ
' is automatical-
ly corrected to 'set value
Ԙ
+ P(a)'.
Pressure
Set value
Ԙ
Set value
Ԙ
'
P(a)
Atmospheric pressure
ON
OFF
ON
OFF
Set value
Ԙ
' after auto-
reference is:
Ԙ
'
㩷㪔㩷
Ԙ
P(a)
Before auto-
reference
A f t e r a u t o -
reference
Detected pressure value
at auto-reference input
SPECIFICATIONS
15
٨
Model
-100 to +100 kPa
-100 to +100 kPa
-0.1 to +1.0 MPa
-0.1 to +1.0 MPa
-100 to +100 kPa
-100 to +100 kPa
-0.1 to +1.0 MPa
-0.1 to +1.0 MPa
500 kPa
500 kPa
1.5 MPa
1.5 MPa
Type
Item
Pressure type
Rated pressure range
Set pressure range
Withstand pressure
Applicable fluid
Supply voltage
Gauge pressure
Non-corrosive gas
12 to 24 V DC
r
10%
Power consumption
Standard type
High-function type
Low-pressure type
Low-pressure type High-pressure type
High-pressure type
Normal operation: 840mW or less (current consumption 35mA or less at 24V supply voltage)
ECO mode (STD): 600mW or less (current consumption 25mA or less at 24V supply voltage)
ECO mode (FULL): 480mW or less (current consumption 20mA or less at 24V supply voltage)
<NPN output type>
NPN open-collector transistor
Maximum sink current: 100mA
Applied voltage: 30V DC or less
(between comparative output and 0V)
Residual voltage: 2V or less
(at 100mA sink current )
<PNP output type>
PNP open-collector transistor
Maximum source current: 100mA
Applied voltage: 30V DC or less
(between comparative output and +V)
Residual voltage: 2V or less
(at 100mA source current )
Comparative output
Output operation
Hysteresis
Selectable either N.O. or N.C., with key operation
Min. 1 digit (variable) (however, 2 digits when using psi units)
Material
±1% F.S.
(20
͠
reference)
2.5ms, 5ms, 10ms, 25ms, 50ms, 100ms, 250ms, 500ms, 1.000ms
or 5,000ms selectable with key operations
<High-function, low-pressure type>
Output voltage: 1 to 5V
Zero point: Within 3V
r
5% F.S.
Span: Within 4V
r
5% F.S.
Linearity: Within
r
1% F.S.
Output impedance: 1k
ǡ
approx.
<High-function NPN output type>
ON voltage: 0.4V DC or less
OFF voltage: 5 to 30V DC or open
Input impedance: 10k
ǡ
approx.
Input time: 1ms or more
<High-function PNP output type>
ON voltage: 5V to +V DC
OFF voltage: 0.6V DC or less or open
Input impedance: 10k
ǡ
approx.
Input time: 1ms or more
<High-function, high-pressure type>
Output voltage: 0.6 to 5V
Zero point: Within 1V
r
5% F.S.
Span: Within 4.4V
r
5% F.S.
Linearity: Within
r
1% F.S.
Output impedance: 1k
ǡ
approx.
Enclosure: PBT (with glass fiber), LCD display: Acrylic
Pressure port: Stainless steel (SUS 303)
Mounting screw section: Brass (nickel-plated), O-ring: H-NBR
Switch: Silicon rubber
Analog voltage output
External input
Ambient temperature
Ambient humidity
Response time
Repeatability
Temperature characteristics
-10 to +50
͠
(No dew condensation or icing allowed), Storage: -10 to +60
͠
35 to 85% RH, Storage: 35 to 85% RH
±0.5% F.S.
(20
͠
reference)
r
0.1% F.S.
r
within 2 digits
r
0.2% F.S.
r
within 2 digits
r
0.1% F.S.
r
within 2 digits
r
0.2% F.S.
r
within 2 digits
±1% F.S.
(20
͠
reference)
±0.5% F.S.
(20
͠
reference)
Weight
40g approx.(
DP-100-E
type: 45g approx.,
DP-100-M
type: 30g approx.) (Main body only)
Accessories
CN-14A-C2
(Cable with a connector, 2m long)
optional for J type), Unit switching label: 1 pc.
DP-10
غغ
-
غ
-
غ
-
غ
:
1
: Low-pressure type,
2
: High-pressure type
: None: Standard type,
A
: High-function type
: None: R
1
㧛
8
+M5 female screw,
E
: G
1
㧛
8
+M5 female screw,
M
: M5 female screw
N
: NPT
1
㧛
8
+M5 female screw
: None: NPN output type,
P
: PNP output type
: None: Cable with connector enclosed,
J
: No cable with connector
PRINTED IN JAPAN
Overseas Sales Dept. (Head Office)
2431-1 Ushiyama-cho, Kasugai-shi, Aichi, 486-0901, Japan
Phone: +81-(0)568-33-7861 FAX: +81-(0)568-33-8591
Europe Headquarter: Panasonic Electric Works Europe AG
Rudolf-Diesel-Ring 2, D-83607 Holzkirchen, Germany
Phone: +49-8024-648-0
US Headquarter: Panasonic Electric Works Corporation of America
629 Central Avenue New Providence, New Jersey 07974 USA
Phone: +1-908-464-3550
URL : sunx.jp
SUNX Limited
٨
The models listed under '
SPECIFICATIONS
' come with CE
Marking.
As for all other models, please contact our office.
15
INTENDED PRODUCTS FOR CE MARKING
17