4) Make sure the maximum output voltage of each PV string does not exceed 600V.
4.3.1.2 DC connector assembly procedure
1) Select the appropriate photovoltaic cable:

2) Peel off the DC cable insulation sleeve for 7 mm, as shown in Figure 4-9:

Figure 4-9

Wire Traverse area 2.5-4mm

2

7mm

Cable type

Traverse area (mm²)

General photovoltaic cable

Range (mm²)

Recommended value (mm²)

2.5-4.0

4.0

Figure 4-10

+

-

Crimping Plier

Open-end Wrench

Figure 4-11

Figure 4-12

3) Disassemble the connector in the accessory bag, as shown in Figure 4-10:

4) Insert the DC cable through the DC connector nut into the metal terminal and press the 
terminal with a professional crimping plier (pull back the cable with some power to check if 
the terminal is well connected to the cable), as shown in Figure 4-11:

5) Insert the positive and negative cables into the corresponding positive and negative 
connectors, pull back the DC cable to ensure that the terminal is tightly attached in the 
connector.
6) Use an open-end wrench to screw the nut to the end to ensure that the terminal is well 
sealed, as shown in Figure 4-12:

1.Before assembling the DC connector, make sure that the cable polarity is 

correct.

2.Use a multimeter to measure the voltage of the DC input string, verify the 

polarity of the DC input cable, and ensure that each string voltage is within 

600V.

Warning 

Figure 4-13

7) Insert the positive and negative connectors into the inverter DC input terminals respectively, a 
click sound should be heard if the terminals are well connected, as shown in Figure 4-13:

8) Seal the unused PV terminals with the terminal caps.

4.3.2 Connection of AC output
The Sunways STS 3~6kW series single phase inverter operates with grid voltage and frequency 
of 220/230V and 50/60Hz, respectively. 
This inverter includes an integrated residual current device (RCD) . 
If an external residual current device (RCD) is used, a device of type (A/AC etc) should be used, 
with a tripping current of 300mA or higher.

Содержание STS-3.6K

Страница 1: ...1 Grid connected PV Inverter Single Phase Dual MPPT STS 3K 3 6K 4 2K 4 6K 5K 6KTL User Manual Sunways Technologies Co Ltd...

Страница 2: ...15 4 3 Electrical Connection 17 4 4 Monitoring Device Installation 22 4 5 CT RS485 DRED Connection 23 4 6 System Layout of Units without Integrated DC Switch 26 5 Start and Stop 27 5 1 Start the Inve...

Страница 3: ...ance please contact the local designated personnel for system installation and maintenance 2 1 6 To use this grid connected inverter for power generation needs the permission of the local power supply...

Страница 4: ...late and packing box 2 4 1 Symbols on the Inverter Danger Warning Caution Dangerous situation if not avoided it could result in death or serious personal injury Description Symbol Potentially dangerou...

Страница 5: ...S 4 2KTL STS 4 6KTL STS 5KTL STS 6KTL 3 1 3 Applicable grid type The applicable grid types for the Sunways STS 3 6kW series are TN S TN C TN C S and TT When applied to the TT grid the voltage of N to...

Страница 6: ...2 2 Inverter side view 360mm 410mm Logo Display Name Plate 360mm 120mm Figure 3 4 Bottom view Figure 3 5 Inverter back view 3 2 3 Inverter bottom view 3 2 4 Inverter back view Back Rail Vent Valve 120...

Страница 7: ...n Figure 4 1 sunways 3 3 Display Interface Figure 3 6 Display interface Inverter 1 Wall Bracket 1 Expansion Bolt 4 PV Terminal 2 Figure 3 7 Packing list 3 4 Packing List The package of the inverter in...

Страница 8: ...tion angle of the inverter is recommended as shown in Figure 4 3 Figure 4 2 Recommended installation spacing Figure 4 3 Recommended installation angle Do not put flammable and explosive articles aroun...

Страница 9: ...se serious damage to the inverter Static may cause damage to the electronic components of the inverter Anti static measures should be taken during installation and maintenance Do not use other brands...

Страница 10: ...pull back the DC cable to ensure that the terminal is tightly attached in the connector 6 Use an open end wrench to screw the nut to the end to ensure that the terminal is well sealed as shown in Fig...

Страница 11: ...PE N wires for 8mm as shown in Figure 4 15 3 Insert the stripped end of each three wire into the appropriate hole of the terminal head yellow green wire to PE port red or brown wire to L port and blue...

Страница 12: ...GPRS LAN and RS485 communication Plug the WiFi LAN or GPRS module into the COM1 port in the bottom of inverter as shown in Figure 4 20 A slight click sound during the installation represents that the...

Страница 13: ...terminals which are defined as follows 4 5 2 RS485 Communication STS series single phase inverter supports multiple inverters daisy chain connection to a data logger via RS485 communication Multiple...

Страница 14: ...higher than the inverter start up voltage the inverter will start 3 When both AC and DC power supply are normal the inverter is ready to start The inverter will initiate checking its internal paramet...

Страница 15: ...creen displays Auto Test Record and hold the button 3 seconds to check the test results The auto test type will be chosen from Remote and Local before starting the auto test Remote is set as 1 by defa...

Страница 16: ...are all firmly connected and DC switch is on 2 Check whether the input voltage meets the working voltage Mains Lost 1 Check whether the mains supply is lost 2 Check whether the AC breaker and terminal...

Страница 17: ...let if necessary Six months to a year it depends on the dust contents in air Model STS 3KTL STS 3 6KTL STS 4 2KTL STS 4 6KTL STS 5KTL STS 6KTL DC Input Start up Voltage V 120 120 120 120 120 120 Max D...

Страница 18: ...egrated AC Over voltage Protection Integrated General Data Dimensions mm 410W 360H 120D Weight kg 13 Protection Degree IP65 Self consumption at Night W 1 Topology Transformerless Operating Temperature...

Отзывы: