Page | 32
What you can do from this page:
Tick ‘Gen Charge’ to charge the batteries from the gen I/P.
Tick ‘Grid Charge’ to charge the batteries from the grid I/P.
Tick ‘Gen Signal’ signal to auto-switch a relay box.
Tick ‘Grid Signal’ signal to auto-switch a relay box.
Gen Charge:
Uses the GEN input of the system to charge battery bank from an attached
generator.
Gen Signal:
Normally open (NO) relay that closes when the Gen Start signal state is
active.
Gen Max Run Time:
This indicates the longest
ti
me the generator can run in one day.
When the maximum running time is reached, the generator will be turned off. ‘24H’ means
the generator will run continuously.
Gen Down Time:
This indicates the delay-time of the generator to shut down after it has
reached the running time
Grid Charge:
It indicates that the grid will charge the battery.
Grid Signal:
Indicates when the grid should no longer charge the battery.
Recommended battery settings:
Battery Type
Absorption
Stage
Float Stage
Voltage (every 30 days 3hr)
AGM (or PCC)
14.2V (57.6V)
13.4V (53.6V)
14.2V (57.6V)
Gel
14.1V (56.4V)
13.5V (54.0V)
Wet
14.7V (59.0V)
13.7V (55.0V)
14.7V (59.0V)
Lithium
Follow its BMS voltage parameters
Using a generator with a Sunsynk inverter:
A generator can either be connected to the Grid side or to the Gen connection. When
connected to the Grid Input, the inverter will consider the power coming from the generator
as ‘Grid Supply’. Users should make sure this power goes to the LOAD only and should
not be exported to other outlets as this will damage the generator.
Do not alter these settings too many times on the same battery as it may damage the
battery.
NOTICE