SunSynk SUNSYNK-6K-SG02LP1 Скачать руководство пользователя страница 1

 

 

 

 

 

 

 

RACK-MOUNTED HYBRID PARITY  

(SUPER) INVERTER 

 

 

 

INSTALLER MANUAL 

SUNSYNK-6K-SG02LP1 / SUNSYNK-7.6K-SG02LP1  

 

Global Tech China Ltd, 3 Floor, Wai Yip Industrial Building. 

171 Wai Yip Street, Kwun Tong, Kowloon, Hong Kong. 

Tel: +852 2884 4318 Fax: +8522884 4816 

www.sunsynk.com / [email protected] 

www.globaltechhk.com 

 

Version 5.0 (05/20/2021)

 

Содержание SUNSYNK-6K-SG02LP1

Страница 1: ...YNK 6K SG02LP1 SUNSYNK 7 6K SG02LP1 Global Tech China Ltd 3 Floor Wai Yip Industrial Building 171 Wai Yip Street Kwun Tong Kowloon Hong Kong Tel 852 2884 4318 Fax 8522884 4816 www sunsynk com sales gl...

Страница 2: ...ECTION 14 4 6 CONNECTING THE AC 16 4 7 INSTALLING THE CT COIL 18 4 8 EARTH CONNECTION MANDATORY 20 4 9 CONNECTING THE PV 21 4 9 1 PV MODULE SELECTION 21 4 9 2 PV MODULE WIRING 21 5 OPERATION 23 5 1 DI...

Страница 3: ...46 5 17 SOLAR POWER GENERATED 48 5 18 GRID POWER 49 5 19 ADVANCED SETTINGS FOR WIND TURBINE 49 5 20 ADVANCED SETTINGS FOR AUXILIARY LOAD 51 5 21 ADVANCED SETTINGS FOR PEAK POWER SHAVING 52 5 22 FAULT...

Страница 4: ...ffering from a physical or mental impairment that would affect their ability to follow this manual install maintain or repair this device Any untrained personnel who might get near this device while i...

Страница 5: ...ing to reduce the risk of electrical shock The unit is not explosion proof so it should not be installed in an explosive atmosphere Never touch electrical components immediately after the power supply...

Страница 6: ...Visual power flow screen Smart settable 3 stage MPPT charging for optimized battery performance Auxiliary load function Parallel multi invert function grid tied and off grid COMPATIBLE Compatible with...

Страница 7: ...rable AC solar generator charger priority by LCD setting SECURE Overload over temperature short circuit protection Smart battery charger design for optimized battery protection Limiting function insta...

Страница 8: ...tput Frequency and Voltage 50 60Hz 120 240Vac split phase 208Vac 2 3 230Vac single phase Grid Type Split phase 2 3 phase Single phase Current Harmonic Distortion THD 3 Linear load 1 5 Efficiency Max E...

Страница 9: ...Page 9 3 1 System Diagram...

Страница 10: ...ances that adversely affect the equipment such as sulphuric gas chlorine gas acid or alkali These can cause the copper pipes and brazed joints to corrode and fail to conduct electricity reliably Areas...

Страница 11: ...res so that they cannot reach and touch the unit Install the indoor unit on the wall where the height from the floors is higher than 1600mm For proper heat dissipation allow a clearance of approximate...

Страница 12: ...d DC isolator see next page In some applications switching devices may not be required but overcurrent protectors must be used Please refer to the typical amperage in the table below for the required...

Страница 13: ...from the batteries to the inverter in compliance with the battery manufacturer guidelines The cables have two ends one to be specifically connected to the BMS and another to be connected to the invert...

Страница 14: ...Page 14 4 5 Battery Temperature Connection When connecting more than one battery ensure they are set in the configuration of master and slave NOTICE...

Страница 15: ...oth the battery and the inverter When using more than one battery the first battery will be the master and the other batteries will be the slaves Please check the battery manufacturer specification fo...

Страница 16: ...LOAD and GEN port connections 1 Before making GRID LOAD and GEN port connections make sure to turn off the AC breaker or disconnector first 2 Remove 10mm sleeve from each wire unscrew the bolts insert...

Страница 17: ...ted before attempting to connect it to the inverter Insert AC output wires according to the polarities indicated on the terminal block and tighten the terminal screws Be sure to connect corresponding...

Страница 18: ...er to prevent feeding power to the grid This feature is also known as Zero Export 1 Fit the coil sensor around the live cable on the main fuse feeding the building and run the cable back to the invert...

Страница 19: ...the CT coil is fitted in the wrong way then this variable will have negative instead of positive values when the power is flowing into the house inverter Also the inverter export limiting function wi...

Страница 20: ...d your system is a hybrid system then you can have a permanent earth wire since this can cause faults with an RCD before the inverter Since the inverter is a true hybrid then the bond must only be mad...

Страница 21: ...possible current leakage to the inverter For example grounded PV modules will cause current leakage to the inverter 4 9 1 PV Module Selection When selecting the PV modules you should consider the fol...

Страница 22: ...sure the PV array open circuit voltage is within the maximum limit of the inverter WARNING When sunlight falls on the solar panel it will generate a voltage A high voltage generated by panels in serie...

Страница 23: ...connection normal Normal Green LED solid light Inverter functioning normally Alarm Red LED solid light Fault Function Key Description Esc To exit the previous mode Up Increase the value of a setting D...

Страница 24: ...page Daily readings Real time readings What this page displays Total daily power into the battery kWh Total daily power out of the battery kWh SOC State of charge of the battery Total daily solar pow...

Страница 25: ...ming from the grid the power is positive If the sign of the grid and HM home powers are not the same when the PV is disconnected and the inverter is only taking energy from the grid and using the CT c...

Страница 26: ...r system take a look at the figure bellow 1 The PV modules charge the batteries 2 When the batteries reach a specific level programmable the battery power is fed into the inverter 3 The inverter can t...

Страница 27: ...e gear icon on the right top of the navigation menu What you can do from this page Access the Basic Setup Page press the BASIC icon Access the Battery Setup Page press the BATTERY icon What this page...

Страница 28: ...ss the FAULT CODES icon Set up Li BMS press the LI BMS icon 5 7 Set Time Clock To set time click on the BASIC icon and then on Time How to set up step by step 1 Touch the screen on the box you wish to...

Страница 29: ...nge the name on the home screen How set the auto dim Set a number in the auto dim box to dim the LCD after a number of seconds How to turn the beep on or off Mark or unmark the beep box and the press...

Страница 30: ...er to conduct a system diagnosis Test mode only for engineers For engineers to conduct tests 5 10 Battery Setup Page To configure battery settings click on the BATTERY icon and then on Batt type What...

Страница 31: ...etting Active battery This feature will help recover a battery that is 100 discharged by slowly changing from the solar array Until the battery reaches a point where it can change normally 5 11 Genera...

Страница 32: ...o shut down after it has reached the running time Grid Charge It indicates that the grid will charge the battery Grid Signal Indicates when the grid should no longer charge the battery Recommended bat...

Страница 33: ...itch 100 of the load to the generator and then slowly increase the charging currents to the batteries Therefore the generator must be able to supply both the charge current and the total load current...

Страница 34: ...own voltage set as either a voltage or Inverter low battery warning set as either a voltage or Restart voltage set as either a voltage or Activating Shutdown causes the inverter to enter standby mode...

Страница 35: ...ng the current until the battery is fully charged Float The charging voltage is reduced to between 13 0 VDC and 13 8 VDC and held constant while the current is reduced to less than 1 of battery capaci...

Страница 36: ...manufacturers produce for their batteries That way the chance of errors occurring during installation are greatly reduced Below there is a list of batteries that has been examined tested and approved...

Страница 37: ...e settings must be used HUBBLE No Voltage Base Charge settings must be used CCGX 48Vxxxx CAN 0 Need confirm CAN_H CAN_L SACRED SUN 48Vxxxx RS485 1 Cut Line 3 6 8 SOLAX 48Vxxxx CAN 0 KOK 48Vxxxx RS485...

Страница 38: ...limited to 100A some are lower and some are higher Ensure that voltage and current specifications provided by the battery manufacturer are followed If you are using lead acid batteries then follow th...

Страница 39: ...tor ticking Grid or Gen and set what times this needs to occur Set the time to discharge the unit to the load or export to the grid by unticking Grid and Gen Concerning the detailed figure above 1 Tic...

Страница 40: ...atteries from the Grid or Generator please ensure you have set the correct correct battery charging settings on the battery charge as shown in Section 4 10 Battery Setup Home Page If the Use Timer fun...

Страница 41: ...equency in your local area Active Power and Reactive Power Setting Go to GRID SET2 The inverter is capable of producing reactive power and feeding it into the Grid through this setting Feed In managem...

Страница 42: ...e When the voltage reaches to 260V its output power will decrease to 20 of P start DRMs logic interface for AS NZS 4777 2 2015 is used to receive and response commands from grid company and then adjus...

Страница 43: ...03 of VN VRef Q2 0 100 of nameplate reactive power capability absorption 1 100 of nameplate reactive power capability injection 1 V3 VRef 0 03 of VN VRef VRef 0 03 of VN Q3 0 100 of nameplate reactive...

Страница 44: ...Page 44 Connecting the DRM S This can be selected under advance settings...

Страница 45: ...Page 45 Plug the LAN cable into the socket marked DRMS 1 DRM 1 5 2 DRM 2 6 3 DRM 3 7 4 RDRM 4 8 5 Ref 0 6 D Ground 7 Net J 4 7 8 Net J 4 7...

Страница 46: ...6kW and 7 6 kW model respectively To parallel six inverters in a three phase utility grid is necessary to set three inverters as master and three as slaves Phase A Master A and Slave A Phase B Master...

Страница 47: ...nd the MPPTs must be kept separate If you need further help please refer to the Sunsynk website where you will find training videos and Frequently Asked Questions www sunsynk com From here you can als...

Страница 48: ...e as aforementioned six inverters paralleled in a three phase utility grid three masters Q5 What are the consequences for setting A B or C phases wrong while in parallel mode It can damage the inverte...

Страница 49: ...ower export or consumed Access this page by clicking on the Solar Turbine icon on the home page 5 19 Advanced Settings for Wind Turbine To configure wind turbine settings click on the ADVANCE icon Wha...

Страница 50: ...s are three phase PM type Therefore either a wind turbine controller or a direct connection to the MPPT via a simple protection circuit will be required DO NOT use a wind turbine that exceeds 400V Use...

Страница 51: ...known as smart load settings click on the AUX LOAD icon A nice feature of this page is that when the batteries are full and the inverter is still producing power from the solar PV or turbine it is po...

Страница 52: ...To configure Peak Power Shaving function click on the AUX LOAD icon Peak Shaving This is a technique used to reduce electrical power consumption during periods of maximum demand on the utility grid T...

Страница 53: ...ault has not been removed after re starting please contact your local vendor or service centre The following information is required 1 Inverter serial number 2 Distributor or service centre of the inv...

Страница 54: ...ort 3 Restart inverter F24 DC insulation impedance failure PV isolation resistance is too low 1 Check if the connection of PV panels and inverter are firmly connected 2 Check if the earth bond cable o...

Страница 55: ...eat sink high temperature failure Heat Sink temp is too high 1 Check if the working environment temperature is too high 2 Turn off the inverter for 30 minutes and restart Fault Information Instruction...

Страница 56: ...gh_Fault F27 DC_Insulation_ISO_Fault F59 AC_V_GridCurr_High_Fault F28 DCIOver_M1_Fault F60 AC_W_GridCurr_High_Fault F29 AC_AirSwitch_Fault F61 AC_A_InductCurr_High_Fault F30 AC_MainContactor_Fault F62...

Страница 57: ...el Voc voltage does not exceed 480V and checked the battery voltage Power on Sequence 1 Switch on AC 2 Press Start Button 3 Switch on Battery and battery breaker 4 Switch on the DC PV Isolator Shutdow...

Страница 58: ...e controller you will fully appreciate the capabilities of there inverter See section Program Charge Discharge Times This is for paralleling systems and wind turbine If paralleling inverters in 3 Phas...

Страница 59: ...here are no fault codes and Lithium battery communication is correct Weekly cleaning statement Suggest micromesh filters as an available option micro ants here are a real problem Appendix A Descriptio...

Страница 60: ...uding both active and neutral conductors and 2 Be of the type specified in the inverter manufacturer s instructions or as labelled on the inverter We recommend the use of an RCD on all circuits and su...

Страница 61: ...Data Logger should be connected to the bottom of the inverter via the connection socket marked WIFI For more information training videos software upgrades help line forum please refer to http www suns...

Страница 62: ...lding 171 Wai Yip Street Kwun Tong Kowloon Hong Kong Tel HK 852 2884 4318 Fax 852 2884 4816 Tel UK 44 151 528 9945 Tel SA 27 1108 39837 sales globaltech china com Audio Training manuals on Apple Pod C...