This tab allows the user to enter details such as the time, display name etc. Please ensure that the correct
time settings are entered as this could influence the functionality of the inverter especially if timed settings
will be use.
Before continuing with the installation, please ensure
that the inverter and battery being installed are
compatible with each other. When the inverter is
connected to the battery, the inverter should be able
to adopt the BMS parameters. This can be checked
under Li-BMS in the settings menu. An example of what
should be seen is in Figure 2 for CAN communication.
Go to the “Battery” under the settings menu. Press “Shut
Down” and set “Shut down” at 3%, “Low Batt” at 5% as
shown in Figure 3.
NB
: This differ from manufacturer,
please ensure that the correct values are set for batteries
not supplied by Segen.
Press “Batt type”. Choose battery mode “Lithium”, input
the capacity of the battery, charge/discharge currents
according to the battery bank. For the protocol, please
ensure that you follow the notes on the compatibility
table as per manual. Then tick “BMS_Err_Stop” as shown
in Figure 4.
2.1 Basic
2.2 Battery
*Note:
Ensure that the Grid and PV power sources are turned off before starting the inverter and until the
battery communication and configuration is successful. Failure to do this could result in the Pylon batteries
being damaged.
Figure 2: Li-BMS page
Figure 3: Battery Shut Down settings
Figure 4: Battery type settings