This tab allows the user to enter details such as the time, display name etc. Please ensure that the correct 

time settings are entered as this could influence the functionality of the inverter especially if timed settings 

will be use. 

Before continuing with the installation, please ensure 

that the inverter and battery being installed are 

compatible with each other. When the inverter is 

connected to the battery, the inverter should be able 

to adopt the BMS parameters. This can be checked 

under Li-BMS in the settings menu. An example of what 

should be seen is in Figure 2 for CAN communication.

Go to the “Battery” under the settings menu. Press “Shut 

Down” and set “Shut down” at 3%, “Low Batt” at 5% as 

shown in Figure 3. 

NB

: This differ from manufacturer, 

please ensure that the correct values are set for batteries 

not supplied by Segen.

Press “Batt type”. Choose battery mode “Lithium”, input 

the capacity of the battery, charge/discharge currents 

according to the battery bank. For the protocol, please 

ensure that you follow the notes on the compatibility 

table as per manual. Then tick “BMS_Err_Stop” as shown 

in Figure 4.

2.1 Basic

2.2 Battery 

*Note:

 Ensure that the Grid and PV power sources are turned off before starting the inverter and until the 

battery communication and configuration is successful. Failure to do this could result in the Pylon batteries 

being damaged.

Figure 2: Li-BMS page

Figure 3: Battery Shut Down settings

Figure 4: Battery type settings