Step 13
Press
the
SET
button again to move onto the
SIXTH PERIOD
. This is the final
period. This would be when you would want to turn off your heating at night.
Press the or arrow to set the time you want the heating to switch off.
Step 14
Press
the
SET
button again to set the setback temperature. Anything below 16°C and
the underfloor heating will not come on. Use the or arrow to set the temperature.
Step 15
Saturday & Sunday (6 & 7) will have to be programmed separately. Repeat
Steps 3-14
to program Saturday & Sunday.
Step 9
Press
the
SET
button again to move onto the
FOURTH PERIOD
. This would be
when you would want to turn off your heating in the afternoon. Press the or arrow
to set the time you want the heating to switch off.
Step 10
Press
the
SET
button again to set the setback temperature. Anything below 16°C and
the underfloor heating will not come on. Use the or arrow to set the temperature.
Step 11
Press the
SET
button again to move onto the
FIFTH PERIOD
. This would be when
you would want to turn on your heating on in the evening. Press the or arrow to set
the time you want the heating to switch on.
Step 12
Press the
SET
button again to set the target temperature. An adequate temperature
would be anywhere between 24-28°C. Use the or arrow to set the temperature.
To access the advanced settings simply
PRESS
and
HOLD
the & arrow. You will be in advanced
settings when you see CL in the top right hand corner and a 0 underneath. To cycle through the
advanced settings press
SET
. Press the or arrows to alter the settings. Press
OK
to exit
Advanced Settings
Brackets indicates
the factory default
setting
Description
CL (0)
Allows you to alter the display temperature by +/- 4°C
BL (1)
Allows you to turn the backlight on or off, 1 being ON and 2 being OFF
AH (35
°
C)
This option will let you set the maximum temperature you would like to set the
floor (F) or air sensor to (R/RF) to. Maximum for floor (F) is 20-60°C air (R/
RF) is 20-35°C
FL (5
°
C)
This option will let you set the minimum temperature you would like to set
the floor (F) or air sensor to (R/RF) to. Minimum for floor (F) and air (R/RF) is
5-20°C
FH (40
°
C)
This option lets you set the floor sensor temperature limitation 20-60°C
HE (FA)
Allows you to set Fast Heating (FH) or Slow Heating (SH)
PS (3)
Allow you to turn off programming (0), program 5 days (Mon-Fri) as a block
and Saturday and Sunday individually (3) or program 7 days individually (7)
CS (6)
Allows you to set 4 programmed events per day (4) or 6 events (6)
Ld (H)
Allows you to set the output load
3