1.  Connect to the supply tank or manifold in accordance with the latest edition of National Fuel Gas Code 

(ANSI Z223.1), and local building codes.  Authorities having jurisdiction should be consulted  before the 
installation is made. 

2.  All gas supply lines must be located in accordance with the required clearances to combustibles below 

the heater as listed on the nameplate of the heater. 

3.  Pipe joint compounds must be resistant to the action of liquefied petroleum gases. 
4.  Where  local  codes  do  not  prohibit,  a  CSA  or  U.L.  approved  flexible  connector  (minimum  5/8”  I.D.)  is 

recommended between the rigid piping and the heater.  A union and an approved shut-off valve should 
be  installed  before  the  control  valve  inlet.    The  shut-off  valve  should  be  installed  within  6  feet  of  the 
union. 

 

 

 

5.  This  appliance  is  equipped  with  a  snap-opening, 

combination gas valve.  The maximum supply pressure to 
the appliance is 14” W.C. or 1/2 P.S.I.  If the line pressure 
is  more  than  the  maximum  supply  pressure,  then  use  a 
line regulator as indicated in the following illustration, or a 
line regulator which corresponds to the supply pressure. 

6.  If a second stage regulator is used and gas seeps through 

it, the redundant combination gas valve is designed to lock 
out.    Pressure  build-up  in  the  supply  lines  prior  to  the 
heater must be released before proper heater operation. 

7.  After all gas connections have been made, make sure the  
       heater and all gas outlets are turned off before the main gas supply is turned on.  Turn the gas pressure 

on and check for leaks.  To check for leaks, apply a soapsuds solution to all connections and joints or 
check  by  one  of  the  methods  listed  in  Appendix  D  of  the  National  Fuel  Gas  Code,  ANSI  Z223.1-(latest 
edition). 

 

 
 

Certified  connections  are  recommended 
to  be  installed  as  shown,  in  one  plane, 
and without sharp bends, kinks or twists.  
The  gas  take  off  from  the  supply  line 
must  be  parallel  to  the  burner  gas  inlet 
connection. 
 
If  the  maximum  supply  pressure  is  less 
than  ½ psig, a  second stage regulator is 
not required. 

Содержание SGM10

Страница 1: ...cing this equipment In locations used for the storage of combustible materials signs must be posted to specify the maximum permissible stacking height to maintain the required clearances from the heater to the combustibles Signs must either be posted adjacent to the heater thermostats or in the absence of such thermostats in a conspicuous location IMPORTANT SAVE THIS MANUAL FOR FUTURE REFERENCE SU...

Страница 2: ...re available from the CSA at 8501 East Pleasant Valley Road Cleveland Ohio 44131 or 55 Scarsdale Road Don Mills Ontario M3B 2R3 All NFPA codes are available from the National Fire Protection Association Batterymarch Park Quincy Massachusetts 02269 1 WHAT TO DO IF YOU SMELL GAS DO NOT try to light any appliance Extinguish any open flame Open windows DO NOT touch any electrical switch DO NOT use any...

Страница 3: ...d regulations Every heater shall be located with respect to building construction and other equipment so as to permit access to the heater Each installer must follow the clearances to combustible materials for the heaters Install the heater so that the supports and hangers are correctly spaced in accordance with these instructions The heater must be supported by materials having a working load lim...

Страница 4: ... installer Clearances to combustibles as outlined in this manual should always be observed In areas used for storage of combustible materials where they may be stacked below the heater NFPA54 requires that the installer must post signs that will specify the maximum permissible stacking height to maintain the required clearances from the heater to combustibles Every heater shall be located with res...

Страница 5: ...s heater must not be installed in a spray booth where the heater can operate during the spraying process Consult your local fire marshal or insurance company Certain materials or objects when stored under the heater will be subjected to radiant heat and could be seriously damaged Observe the Minimum Clearances to Combustibles listed in the manual and on the heater at all times 4 MINIMUM CLEARANCES...

Страница 6: ...our local fire marshal fire insurance carrier or other qualified authorities on the installation of gas fired infra red heaters for approval of the proposed installation Install the warnings card supplied with each heater and complete the blank spaces using the clearances from combustibles table below See Section 18 for a printed copy of the warnings card Minimum clearances shall be measured from ...

Страница 7: ...NTING HEIGHT ORIFICE SIZE SHIPPING WEIGHT SGM3 N1 Natural 26 000 12 ft 42 0 0935 30 lbs SGM3 L1 Propane 26 000 12 ft 53 0 0595 30 lbs SGM6 N1A Natural 52 000 14 ft 32 0 1160 40 lbs SGM6 L1 Propane 52 000 14 ft 45 0 0820 40 lbs SGM10 N1A Natural 104 000 15 ft 32 0 1160 70 lbs SGM10 L1 Propane 104 000 15 ft 45 0 0820 70 lbs MODEL SUFFIX REFLECTOR TYPE GAS PIPE CONNECTION Gas Type Ignition System N N...

Страница 8: ... angled up to 45º off the horizontal When the heater is to be angle mounted make sure the controls are on the lower side of the heater Coil chains No 2 or larger or rigid supports may be used to mount the heater The long axis of the heater should be level whether the heater is mounted horizontally or angled 7 ...

Страница 9: ...the end panels so that the end flanges of the end panels overlap the side panels Attach the side panels and end panels together with the screws provided in the kit Attach the remaining screws as shown in Detail A This is to ensure that the Parabolic Reflector Extension is securely attached to the reflector The clearances to combustibles shown on the clearance label that is secured to the reflector...

Страница 10: ... is 14 W C or 1 2 P S I If the line pressure is more than the maximum supply pressure then use a line regulator as indicated in the following illustration or a line regulator which corresponds to the supply pressure 6 If a second stage regulator is used and gas seeps through it the redundant combination gas valve is designed to lock out Pressure build up in the supply lines prior to the heater mus...

Страница 11: ... enough to measure or set the manifold pressure All measurements MUST BE made when this heater and all other gas burning equipment that is connected to the gas supply system are operating at maximum capacity 3 The combination gas valve is factory set and should not require adjustment If full rate adjustment is required remove the cover screw Using a small screwdriver turn the adjustment screw cloc...

Страница 12: ...is used the required square feet of inlet and outlet vent area depending on height and temperature difference is as follows SGM3 0 4 s f SGM6 0 8 s f SGM10 1 6 s f The General Ventilation Rules outlined in ASHRAE GUIDE AND DATA BOOK should be observed when locating vents Exhaust vents must be located at the highest point above and in the vicinity of the heaters and the inlet vents must be located ...

Страница 13: ...lecting any foreign material on its surface or in the ports or when anything obstructs the venturi or the screen Maximum heating efficiency and clean combustion will be maintained by keeping the emitter and burner clean To clean the heater follow these instructions 1 Turn off all gas supply to the heater 2 Clean the reflector 3 Remove he main burner orifice and the pilot orifice if so equipped and...

Страница 14: ...back side of the emitter face and the inside of the heater g The insulation gasket which was between the heater body and the emitter face must be replaced when the heater is reassembled Order two 2 of each of the part numbers indicated for your particular model SGM3 40446080 and 40446130 SGM6 40446080 and 40446090 SGM10 40446080 and 40446110 15 REPLACING PARTS Ensure that at all times when parts a...

Страница 15: ...99030 Gas Valve 10 WC VS820A 1120 LP Gas 19 42124000 Reflector Assembly pilot 20 40715000 Pilot Housing Assembly 21 40719000 End Flue Collar pilot end 22 40707000 Radiation Shield housing 23 40649000 Pilot Flue Baffle 24 40750000 Pilot Shield Assembly 25 40706000 Radiation Shield pilot 26 42184000 Pilot Tubing 27 03462070 Pilot Generator System Nat Gas 28 03462080 Pilot Generator System LP Gas 29 ...

Страница 16: ...e Model Number when ordering All replacement parts available when ordering MODEL NUMBER SUFFIXES N Natural Gas L Propane Gas 1 Self Generating Standing Pilot ALL ILLUSTRATIONS ARE INTENDED TO GIVE THE GENERAL IMPRESSION OF UNITS ONLY WE RESERVE THE RIGHT TO ALTER ANY SPECIFICATION WITHOUT NOTICE 15 ...

Страница 17: ...S820A 1070 Nat Gas 19 30299030 Gas Valve 10 WC VS820A 1120 LP Gas 20 40720000 Reflector Assembly pilot 21 42431000 Pilot Housing Assembly 22 42425000 Radiation Shield housing 23 42421000 Pilot Flue Baffle 24 42424000 Pilot Shield 25 42434000 Pilot Tubing 26 40706000 Radiation Shield pilot 27 03462130 Pilot Generator System Nat Gas 28 03462140 Pilot Generator System LP Gas 29 03463000 Pilot Burner ...

Страница 18: ...Form 43219030 Sept 2012 17 ...

Страница 19: ...A 1070 Nat Gas 25 30299030 Gas Valve 10 WC VS820A 1120 LP Gas 26 42420000 Manifold Clamp Qty 2 27 04703000 Manifold Support Bracket Qty 2 28 03600040 Compression Sleeve 5 8 Qty 2 29 03601040 Compression Nut 5 8 Qty 2 30 03602100 Compression Union 5 8 Tube x 1 2 NPT Qty 2 31 42432000 Manifold Tubing 32 03339080 Plug 1 2 33 41063000 Reflector pilot 34 42431000 Pilot Housing Assembly 35 42425000 Radi...

Страница 20: ...Form 43219030 Sept 2012 19 ...

Страница 21: ...Form 43219030 Sept 2012 18 WARNINGS CARD This card is furnished with each heater Additional copies may be ordered under part no 43344980 20 ...

Страница 22: ...DTOANYIMPLIEDWARRANTYOFFITNESSFORAPARTICULARPURPOSEAND ANY IMPLIED WARRANTY OF MERCHANTABILITY FOR ITS PRODUCTS If any provision of this warranty is found to be void unenforceable or unconscionable then the same is hereby severed and the remainder of this warranty is hereby saved and shall remain in force EXCLUSIVE REMEDY The sole and exclusive remedy under this warranty is the replacement of the ...

Отзывы: