MOUNTING CONSIDERATIONS
•
Clearance to combustibles must be observed at all times.
•
In all cases, minimum installation height: 8 ft. (240 cm) U.S.A., 7 ft. (214
cm) Canada, from floor ground level.
•
The heater must be controlled by a thermostat, timer, or other
automatically operated device. On/off switches or direct wiring to a
circuit breaker are not allowed.
•
Verify the buildings overhead structure has sufficient strength and
proper suspension means to support the weight of the heater
•
Observe and verify all chains are plumb and vertical. A chain that is not
plumb and vertical may cause damage to the heater.
•
To maximize the heater’s effectiveness to cover the space to be heated,
it is recommended the heater be hung as high as possible and along an
uncluttered wall to give the heater’s reflector the widest possible “view”.
•
Leave enough space around the burner box to permit future servicing.
•
Choose a location allowing easy installation of the vent piping system.
•
Each suspension point must be capable of supporting a minimum of 150
lbs. (65 kg).
•
Allow for heater’s movement during expansion and contraction through
the operation cycle.
•
Heaters shall not be installed in living/sleeping areas.
•
U-tube heaters must have a reflector installed over the U-bend tube.
CAUTION: HIGH ELEVATION
•
If a heater is to be installed at a high elevation, in excess of 2000 feet
(610 m) above sea level, the installer is advised to verify it has been
properly factory modified for this application in accordance with the
National Fuel Gas Code.