![Sunnytech ST2420 Скачать руководство пользователя страница 11](http://html1.mh-extra.com/html/sunnytech/st2420/st2420_user-manual_1398815011.webp)
of duration and
boost voltage point according to the actual needs. When the
duration reaches the set value, the system will then switch to floating charging.
Equalizing charging
Warning: risk of explosion!
In equalizing charging, an open lead-acid battery can produce explosive gas, therefore
the battery chamber shall have good ventilation conditions.
Note: risk of equipment damage!
Equalizing charging may raise the battery voltage to a level that may cause
damage to sensitive DC loads. Check and make sure that allowable input
voltages of all the loads in the system are greater than the set value for battery
equalizing charging.
Note: risk of equipment damage!
Overcharge or too much gas generated may damage battery plates and cause
active material on the battery plates to scale off. Equalizing charging to an
excessively high level or for too long a period may cause damage. Read carefully
the actual requirements of the battery deployed in the system.
Some types of batteries benefit from regular equalizing charging which can stir the
electrolyte, balance the battery voltage and finish the electrochemical reaction.
Equalizing charging raises the battery voltage to a higher level than the standard supply
voltage and gasify the battery electrolyte. If the controller then automatically steers the
battery into equalizing charging, the charging duration is 120 mins (default). In order to
avoid too much generated gas or battery overheat, equalizing charging and boost
charging won’t repeat in one complete charging cycle.
Note:
1) When due to the installation environment or working loads, the system can't