USER MANUAL

       Central Battery Systems by Inverter 220V is used to detect any abnormalities of the main power 
distribution system. In case of error or emergency, the unit will convert the battery voltage stored in the
chemical form into the electric power and supply it to the inverter where the DC voltage from the battery
will be converted into the AC voltage at 220VAC 50Hz to turn on the emergency light. On the other hand, 
when the main power distribution system resumes its normal operation, the unit will stop supplying the 
backup power and start recharging the battery for later use in case of another error or for the emergency 
light test.

Remark :

 Central Battery Systems by Inverter 220V Series has 2 function modes of operation.

1. 

MAINTAINED

 (Providing lighting constantly throughout the period when the AC line lights are in  the 

    normal status and when the AC Line lights are off.)
2. 

NON–MAINTAINED

 (Providing emergency lighting only when the AC line lights are off.)

Features

Содержание INV 220V Series

Страница 1: ...VAC 50Hz to turn on the emergency light On the other hand when the main power distribution system resumes its normal operation the unit will stop supplying the backup power and start recharging the battery for later use in case of another error or for the emergency light test Remark Central Battery Systems by Inverter 220V Series has 2 function modes of operation 1 MAINTAINED Providing lighting co...

Страница 2: ...ff AC Input Low Voltage Protections Operate of Temperature 10 C To 40 C Size L x W x H mm 440x230x660 600x250x810 640x250x970 620x400x1200 620x600x1200 800x600x1500 AC VOLTMETER DC VOLTMETER LED AC Input LED DC Input LED Operate LED Testing LED Charging LED Battery Fail LED Charge Fail 24 220 _ 2 Technical Specifications Indicators Indicating the input voltage Indicating the battery voltage Indicat...

Страница 3: ...ries into 24 Volt batteries Equipment for measuring battery temperature Equipment for measuring battery temperature Transforming 12 Volt batteries into 48 Volt batteries Caution After installation attach the battery temperature measurement equipment to the front of one of the batteries Things to look out for when connecting the batteries 1 Set all the breakers to Off prior to connecting the batter...

Страница 4: ...n such as lights installed in fire escapes or in parking lots 2 Output Non Maintained This connection will not provide a 220Vac 50Hz during normal conditions The connection will only provide power during power outages This connection is suitable for things such as emergency illumination lamps Caution For the correct connection the Line should be connected into L Neutral should be connected to N and...

Страница 5: ...will not yet provide power to the Output since the Breaker AC Output is still off The indicators at the front of the unit should however indicate the following Figure showing the indications at the front of the unit Shows the current level at the Input to be about 220VAC Shows a battery Voltage at 24 or 48 Volts The indicator showing that the battery has been connected to the unit should be on The...

Страница 6: ... Volts or 48 Volts 2 Set the Breaker AC Output to ON shown in the red marking the unit should now be providing power to the load Figure showing the indications at the front of the unit Shows the current level at the Input to be about 220VAC Shows a battery Voltage at 24 or 48 Volts The indicator showing that the battery has been connected to the unit should be on The indicator showing that the inv...

Страница 7: ... Input to ON shown in the red marking after about 5 seconds the unit should stop using the inverter and use the main power supply to provide power instead Shows the current level at the Output to be about 220VAC Shows a battery Voltage at 24VDC or 48 VDC The indicator showing that the unit is receiving a 220VAC current should be on The indicator showing that the battery has been connected to the u...

Страница 8: ...inverter should stop operating and the unit should return to standby mode 3 The unit has a built in self testing system that will perform 30 minutes self tests every 30 days This self test system should start working once a current from a battery or AC Input is provided to the unit Figure showing the indications at the front of the unit Shows the current level at the Input to be about 220VAC Shows...

Страница 9: ...dicator showing that the unit is receiving a 220VAC current should be on The indicator showing that the battery has been connected to the unit should be on The indicator showing that the battery can not provide an electrical charge To cancel the Battery Fail notification command turn off and on Circuit Breaker DC Battery once AC VOLTMETER DC VOLTMETER LED AC Input LED DC Input LED Charging Fail Cau...

Страница 10: ...uit Breaker AC Output is in the OFF status Check to make sure that the Circuit Breaker DC Battery is in the ON position Check to make sure that the Circuit Breaker AC Output is in the ON position Emergency light only turns on for a short time after the power went out The battery is not fully charged The battery has degraded Fully charge the battery Contact customer service to replace the battery I...

Страница 11: ...ople not officially certified by our company The Sticker Warranty Void has been removed or torn The unit is damaged from negligence or incompetent use for example the battery is swollen the batter has been overcharged the battery has been damaged from quick charging the battery has been short circuited the battery s charged has been completely drained The unit has been stored improperly for example...