7.2.3 System protection

If the collector temperature exceeds the collector protection temperature (see 

7.2.2) by 10K, the solar circuit pump is turned off to protect the system compo-

nents. As soon as the temperature falls below this value the system is started again.
This function comes into effect no matter if the collector protection is activated or 

not.

7.2.4 Anti-freeze protection

This function must be activated if the water or glycol mixture can freeze.
If the temperature at the anti-freeze sensor (S1) drops below the set value, the solar 

circuit pump is activated and heats the solar circuit using the heat exchanger in the 

storage tank.

"Basic Setup" menu 
Display

 Meaning

Value range Factory set-

ting

Line Value

4

0

Switches on or off the anti-freeze 

function

0 = Off  

1 = On

0

5

3

Temperature at which the anti-freeze 

function is activated

-20°C  –  +7°C 3°C

8  System monitoring

In the case of an error the flashing   symbol is shown.

8.1 Sensor monitoring

The sensors necessary for the control functions and their connecting cables are 

monitored to show breaks or short circuits. If a faulty sensor or installation is re-

corded by the software, the symbol is shown   . By scrolling up and down you can 

quickly find the error source.

8.2 Flow monitoring

The controller checks the flow rate when the pump is switched on. If after 15 

minutes no flow is recorded an error message will be shown. The error message is 

automatically reset after fault correcting. 

This message, however, does not switch off the pump.

"Basic adjustment" Menu 
Indication

Meaning

 

+

 

A fault with the fluid circulation within the solar 

system

 

Settings and changes in 
this menu must only be 

carried out by a specialised 
technician. Incorrect settings can 
damage or adversely affect the 
function of the solar power 
system.

Содержание BASIC fs

Страница 1: ...Micro processor controller for solar thermal systems Installation Servicemanual Sunny Scout BASIC fs...

Страница 2: ...Pump speed modulation 10 7 2 Protection functions 10 7 2 1 Collector protection 10 7 2 2 Re cooling Holiday function 10 7 2 3 System protection 11 7 2 4 Anti freeze protection 11 8 System monitoring 1...

Страница 3: ...monitoring Large wiring space Available accessories Temperature sensor PT1000 Sensor connection box Immersion sleeves 2 Safety instructions Disconnect all appliances from the mains operating voltage...

Страница 4: ...ow freely install and wire the controller 3 2 Wall installation The device is mounted on the marked points A drilling template is provided with the device Insert the Quick Info card provided with the...

Страница 5: ...nsure proper heat trans fer and use heat conducting paste if necessary Cross sections for cable extensions up to 15m 2 x 0 5mm2 up to 50m 2 x 0 75mm2 If shielded the shield must be connected to the ea...

Страница 6: ...stantly Scroll right Choice Confirmation Main menu scroll right Choosing one menu point Confirmation of value change to save amendment 5 Operating menus 5 1 Info Menu In this mode all measuring values...

Страница 7: ...35K 3K min 100 12 Adjustment of mini mum pump speed modulation 100 rotational speed regulation off 30 100 100 5 3 Manual operation Menu Automatic operation is switched off during manual operation The...

Страница 8: ...lector protection function switching on or off 0 Off 1 On 0 Off 1 120 C Collector protection function activation temp 110 150 C 120 C 2 0 Re cooling function only if the collector protection is on 0 O...

Страница 9: ...s e PE L N A1 N S3 S2 S1 S1 A1 S3 S2 230V connections L Live from mains supply N Neutral from mains and outputs A1 Live switch output 1 solar circuit pump Sensor connections S1 Temp sensor collector S...

Страница 10: ...turned on The solar circuit pump is switched off once the collector tem perature is 10K below the adjusted value In this case the storage tank is charged up to 95 C regardless of it s adjusted maxi m...

Страница 11: ...emperature at which the anti freeze function is activated 20 C 7 C 3 C 8 System monitoring In the case of an error the flashing symbol is shown 8 1 Sensor monitoring The sensors necessary for the cont...

Страница 12: ...e reasons Measures Flashing Sensor cable broken Check the cable Sensor defect Check sensor resistance if necessary replace the sensor Flashing Short circuit in sensor cable Check the cable Sensor defe...

Страница 13: ...h on condition is not present Wait until switch on condition is reached Pump symbol rotates but pump does not work Pump connection faulty Check the cable to pump Pump is seized or blocked Bleed the pu...

Страница 14: ...tching voltage Capability per one switching output 230V 1A approx 230VA for cos 0 7 1 0 Fuse protection Fine wire fuse 5 x 20mm 2A T 2 amperes slow Miscellaneous Operating temperature 0 50 C Storing t...

Страница 15: ...the guarantee to either repair replace or deliver a functioning spare part to correct the defect The maximum repair period is 1 month with effect from receipt of the controller by the manufacturers a...

Страница 16: ...16 Operating manual for Sunny Scout BASIC fs 1316BED100 10B E 02 2012...

Отзывы: