User Manual
9 Troubleshooting and Maintenance
69
Fault
code
Description
Check method
004
Grid undervoltage,
The grid voltage is
lower than the set
protection value
Generally, the inverter will be reconnected to
the grid after the grid returns to normal. If the
fault occurs repeatedly:
1. Measure the actual grid voltage, and
contact the local electric power company for
solutions if the grid voltage is lower than the
set value.
2. Check whether the protection parameters
are appropriately set via the APP or the LCD.
3. Check whether the AC cable is firmly in
place.
4. If the fault is not caused by the foregoing
reasons and still exists, contact Sungrow
Service.
005
Grid low voltage,
The grid voltage is
lower than the set
protection value
Generally, the inverter will be reconnected to
the grid after the grid returns to normal. If the
fault occurs repeatedly:
1. Measure the actual grid voltage, and
contact the local electric power company for
solutions if the grid voltage is lower than the
set value.
2. Check whether the protection parameters
are appropriately set via the APP or the LCD.
3. Check whether the AC cable is firmly in
place.
4. If the fault is not caused by the foregoing
reasons and still exists, contact Sungrow
Service.
007
AC instantaneous
overcurrent,
AC
output
current
exceeds the upper
limit of the inverter.
Generally, the inverter will be reconnected to
the grid after the grid returns to normal. If the
fault occurs repeatedly, contact Sungrow
Service.
008
Grid
overfrequency,
Grid
frequency
exceeds the upper
limit of the inverter.
Generally, the inverter will be reconnected to
the grid after the grid returns to normal. If the
fault occurs repeatedly:
1. Measure the actual grid frequency, and
contact the local electric power company for
solutions if the grid frequency is beyond the
set range.
2. Check whether the protection parameters
are appropriately set via the APP or the LCD.
3. If the fault is not caused by the foregoing
reasons and still exists, contact Sungrow
Service.
009
Grid
underfrequency,
Grid frequency is
lower
than
the
lower limit of the
inverter.
Содержание SG33CX
Страница 1: ...SG33_40_50CX UEN Ver11 201907 Version 1 1 User Manual SG33CX SG40CX SG50CX PV Grid Connected Inverter...
Страница 2: ......
Страница 10: ......
Страница 37: ...User Manual 4 Mechanical Mounting 27 M6 4 5N m...