52
- - End
When a separate single-core cable is used as the PE cable, lead it into the junction box
through the standby grounding terminal.
5.6.4 Connection Procedure of Two Wires per Phase with Multi-core Cable
step 1 Disconnect the AC-side circuit breaker and prevent it from inadvertent reconnection.
step 2 Loosen the two screws on the front cover of the junction box with the hexagon socket
wrench provided. Open the junction box. During the wiring process, the limit rod attached to
the cover keeps the junction box open.
User Manual
Содержание SG285HX