84
Parameter
Description
Range
Active Power Setting
Persistence
Switch for activating/deactivating the function
of active power setting persistence
On/Off
Active Power Limit
Switch for limiting active power
On/Off
Active Power Limit
Ratio
The ratio of active power limit to rated power in
percentage
0.0 %–
110.0 %
DRM
Switch for activating/deactivating the DRM
function
On/Off
Feed-in Limitation
Tap
Settings→Power Regulation Parameters→Feed-in Limitation
to enter the screen,
as shown in the following figure.
figure 7-18
Feed-in Limitation
table 7-6 Description of Feed-in Limitation Parameters
Parameter
Description
Range
Installed PV Power
DC side power
3.00 kW–
20.00 kW
Zero-export per Phase
For a three-phase inverter, the feed-in power
of Phase A, Phase B, and Phase C are re-
quired shall be 0. This function has higher pri-
ority than Feed-in Limitation. If Zero-export
per Phase is enabled, Feed-in Limitation is
automatically disabled.
On/Off
Feed-in Limitation
It is supported to limit the feed-in power of the
inverter
On/Off
User Manual