User Manual
102
≥
AC over-voltage level 3 protection time;
AC under-frequency level 1 protection time
≥
AC under-frequency level 2
protection time
≥
AC under-frequency level 3 protection time;
AC over-frequency level 1 protection time
≥
AC over-frequency level 2 protection
time
≥
AC over-frequency level 3 protection time;
AC under-voltage recovery value
≥
AC under-voltage level 1 protection value +
3V;
AC over-voltage recovery value
≤
AC over-voltage level 1 protection value - 3V;
AC under-frequency recovery value
≥
AC under-frequency level 1 protection
value + 0.01Hz;
AC over-frequency recovery value
≤
AC over-frequency level 1 protection value -
0.01Hz.
The range and default value in the table above is indicative only.
The protection parameter varies in different countries. Please refer to
the standards of each country for details.
10.7.5 Communication Parameters
Click the “Communication parameters” to check the communication parameters
and set the related parameters as shown in Fig. 10-21.