Installation Manual
27
All external cables are connected to the connection terminal through the cable
entries on the bottom of the inverter.
The protective grid is located at the lower part of the inverter cabinet
.
Step 1
Open the door and find the protective grid of the connection area.
Step 2
Loosen the screws at the edge of the protective grid to remove the grid.
For DC side cable connection, remove both the protective grid and the
insulation protective grid.
7.4.3
Check Connection Cable
Before electrical connections, check all cables for insulation and intactness. Poor
insulated or partially bare cables or cables with other damages will pose a serious
safety risk, and need to be replaced immediately.
7.4.4
Cable Connection Precautions
Before cable connections, make sure the polarities of the DC cables are correct
and the connection sequences of the AC cables are consistent.
During electrical connection, do not forcibly pull any wires or cables, as this
may compromise the insulation performance.
All cables and wires should be bent to some extent.
Take necessary auxiliary measures to reduce the stress applied to the cables or
wires.
After completing each step, carefully check the connection for correctness and
firmness.
7.5
Cable Entry Holes
The DC and AC cables come inside and out of the inverter through the bottom of the
device.
Cover plates for cable inlet & outlet holes are designed on the bottom of the inverter. Holes
need to be drilled on site according to requirements.
The following three hole drilling schemes are recommended.