Solar energy coil electrical control instruction
-
CN26 is the terminal for solar input signal
This terminal is used for receiving 230V feedback signal. If CN26 gets 230V feedback signal, CN2
will output control signal, to control solar pump; if CN26 have not gotten feedback signal, the
solar pump will never turn on. And CN26 is connecting with VH-3 terminal.
CN2 is the terminal for solar pump control
This terminal utilizes the 230V control signal, to control solar pump. And this terminal is connecting
with VH-3 terminal.
Note: solar pump must be controlled through AC contactor. The CN2 is not allowed to drive
the pump directly.
CN17 is the ON/OFF terminal
This terminal is used to receiving ON/OFF signal. When the signal close, the heat pump will never
turn on. When the signal open, the heat pump will run well. And CN17 is connecting with VH-2
terminal.
Heat pump installation guide for solar pipe
For Calor Top 300D(S) model there are two routine guides for solar pipe installation. But the relevant
parts should be provided by users.
Guide 1:
. When the pump station check the solar water temperature is OK, it will output 230V signal, when
the CN26 get this signal, the heat pump CN2 will output 230V signal to drive the solar pump.